Evac Rule Cheat Sheet https://assets.cdn.filesafe.space/JUeauqFFpAgQpPWQ1TsD/media/6a8f6a30d1afbd2cbcbfbcc8.pdf Spark Series Book https://pocketedition.secureitsecurities.io/pocket-optin-855933 Join The Course https://firealarmbusinessblueprint.secureitsecurities.io/fire-alarm-blueprint Spark Series Book on Amazon https://www.amazon.com/dp/B0GQ5259GYNICET Clarity Bundle https://portal.secureitsecurities.io/courses/offers/f4a10f66-4311-49f5-9906-022de3ab310d Practice for your NICET Exam https://quizlet.com/join/t2hyD9xaN?i=6sn3ll&x=1bqt Create your own unique offer for free with the Offer Architect https://offerarchitect.secureitsecurities.io/free-architect Fire Alarm Business Blueprint eBook Download https://ebook.secureitsecurities.io/fabb-ebook Send us your fire alarm questions - info@secureitsecurities.com ➖➖➖➖➖➖➖➖➖➖➖➖➖➖➖➖➖➖➖ Learn to program alert tones and associate amplifiers with zones correctly. This guide explains the technical requirements for enabling amplifiers within an Edwards system. Subscribe for weekly fire alarm system technical breakdowns and comment below with which system programming challenges you want us to cover next.
Audio and video play straight from the show's own hosting. PodSubs stores and serves no media.
Transcript
From the show. Tap a time to play from there.
Today I'm going to show you step by step how you can turn on the amplifiers for your evac and your alert tones on an Edward system. Now keep in mind if you don't know how to write this rule or if you don't have the proper syntax, the activation will not work. So stay to the end so you can see exactly how to write this rule step by step. But before we jump into the SDU, I want you to understand what the rule is [music] actually doing. In an Edward system, every amplifier is associated to a zone. So if you're doing activation floor, floor above, and then floor below, you
will have your inputs correlating with your outputs. So depending on what floors you want to activate, you will group those together to activate the associated outputs on your amplifier. Now, the rule for the amplifier is what creates the connection in the software. Without that rule, it doesn't know what to do or how to activate. And here's the thing, this is a rule. This is not a checkbox. This is not a setting. This is something that you set that is supposed to happen automatically each and every time the input activate so that way it can activate the outputs. So we're going
to build this step by step together starting with the evac rule. So [music] let's get it. So now that we in the SDU we are looking at the rules. And before we get into rules let me just break down the difference between the evac and also your alert tones. So that's the evacuation signal. So when the alarm goes off on that particular floor, the amplifier knows to turn on that floor to evacuate that floor. Now the alert tone,
that's the warning tone. That's what's going to be sent out to the rest of the building. Cuz if there's a fire on one particular floor, we don't want everybody else in the building to actually evacuate. We just want to evacuate the immediate dangers and everybody else, hey, there's a problem. Then after a predetermined amount of time that you set with also within the rules, the evacuation tone will sound throughout the whole entire building to get everybody out. All right, so now that we're in the rules, let's go over the rules real quick. At top at the top, we have French brackets. These French
brackets here, you have a open French bracket here, and then you have a closed French brackets here. So anything inside of the French brackets, the SDU will ignore. It will not do anything. And so if I French bracket here at the top of the rules and then French bracket here at the bottom of these rules, none of this will work. All right, so let's get straight into it. General alarm. This is your rule label. Every rule must have a label. You have your fan restart label, your fan restart LED, your elevator
recall auto. So now let's look at this. If you see right here, we have semicolon. Now the semicolon separates your input side from your output side. And on your input side, you have some qualifiers that you can use. So for here, I know this may look a little confusing if you're watching this. So we have alarm. Then we have I need you to help me out with this. I don't know what this is called. So we have I'm going just call this open and close. Okay? So we're going to name this open and close. So we have open to open the input of that we're trying to activate. Right? So
alarm input. And I'm going to show you what Lar actually means. Then we close that. And this is all syntax. If you don't have this syntax, you will get a rule error. So now we separate the input side after we give it all this information including the rule label. Now we have the output side. Now on the output side, we have a bunch of activations that we're trying to do. Now what's very important to keep in mind is we have to know what we're turning on. We want to turn on the amp. These are all point types for these outputs. So we we want to turn on the amps. We want to
turn on some CC1s cuz if it was an amp, it'll say amp on. If it's just saying on then either it's a module or coming straight from the panel and then we're going to be disabling something. So how this actually work you need to include all of these opens cuz what you're telling the system is that okay amp on is the point type and then here's the quotation open not quotation but here's the open guy and then within open and close guy this is our device. This is what we're trying to control this particular point here. So, this amp that
is wherever it's at in the building is labeled, let's say, fourth floor. But this star is representing all of the amps in the building. And I'll show you what that mean in a minute because you may be a little confused at the moment. All right. So, we have inside of open and close, right? Inside of open and close is the actual device. And what is the device type? It is a amp. So, amp whatever floor amp point type speaker whatever floor module on. All right. So, you need those open and close. And you also need this guy here. So for every output that you want to activate, you
need a comma. You need to separate it all by a comma. And you need to end it all with a semicolon. So all of that syntax is needed. So what it's doing here is alarm any alarm pretty much. Turn on the evac channel, turn on the speakers, all the speakers, all the evac, turn on all the strobes, release all the doors, turn on like shut down all the fans, and disable the fan restart switch. So that way anytime the fan shut down, we're disabling this fan restart switch. Then we have the fan restart switch. Whatever that switch
label is is the fan restart switch and the switch is the identifier for the input side of that. Then we want to turn that off. What are we doing? What are we turning off? We're turning off this fan shutdown. So now really quickly, let's go back to alarm. So alarm lar, let's see what that means. So if we go to configure and then we go to objects, then once we get inside the objects, this is the objects menu. So over here we have the cabinet and the LRM. If you open this up, you have many different cabinets here for this particular system. There's a bunch of nodes here. So there's one, two, 3, 4, 5, 6, 7. So
there's seven panels or seven nodes within this network system. So inside of let's say the fourth floor, we have CPUs, we have a power supply, we have the zone amplifier, and we have the loop card. So pretty much every panel will be set up the same way. So that way each panel will have its own inputs. Each panel will have its own outputs. Right? So now really quickly, we could just go over here to where it says device type and you have all your device types. You can [music] select a spot and scroll all the way down if you want to or you can drop down the menu and get straight to
it exactly where you want to get to. Now once you get into the menu, you can use the up and down arrows to just scroll through each and every one of them. But if you know exactly where you want to go, you can just go there, hit the first two letters, and take you straight there. Now, let's talk about this. L L all of these guys got L, right? So, what it's saying is instead of saying first floor, second floor, basement, fifth floor, they use levels. They teach you this in programming and everybody just stick to this particular rule. [music]
So, if you have a basement is usually L0, you can still do it L1. It's really your preference. But all L is representing we're trying to separate each one of these devices per zone, per floor, however you understand it, right? So L1 would assume like here these areas are in the cellar. Like I said, you could use L0 or L1. So all of their smokes in the cellar is labeled L1 and then exactly wherever they're at. Right? So now if you scroll down, you have cuz we have all the smokes here. We have L2,
which is the first floor. Scroll down some more. Then you have L3 which is they have third floor and fourth floor smokes and some second floor smokes. But what makes it different from this [music] smoke to this smoke? What makes it different is the last set of numbers. So the last set of numbers makes this unique. So going through all of that when a programmer is writing L star you pretty much saying ignore or not ignore but I understand what every other character is after L. So he could have
just put star. If he would have just put star, then that would have just represented everything. All of the inputs, not just smokes. You have poles with the L's. You have water flows with the L's. You have tampers with the L's. So all of your inputs will have different levels, whoever floor they're on. This is how you will identify and separate them per floor. Then you will separate them with the last character either by number. This is the easiest way to do it. you give it a a floor designation whatever it is and then the number of how many of that device type
it is. So if you have four tamper switches it'll be L1 T one. Now another thing you need to understand is now the rule editor does not understand the space bar. So you will have to use an underscore to represent a space bar. So if you writing your rules out like L2 space bar temp space bar 132 your rules it's you're not going to have a you're going to have a problem. it's not going to work cuz it doesn't see spaces. So you will have to physically put a character and the character that we use is an underscore. So now let's go back
to the rules. We have L star so that we understand that every input water flow CO it won't be tampers cuz it's not an alarm. So we have uh pole station, smokes, ducks, heat detectors, all of those alarm input devices will be associated under L-star. Now you could also just put star like I said but Lstar just to make it a little this really up to the program really up to you. So now we have the amplifier. So amps let's go to the amplifiers right. So here we have the amplifiers. So we have amp one 2 3 4
5 6 and seven right and these amplifiers are located throughout the building. Some in the main panel and two on each floor. So now we go back to the rules and the amplifiers. So, what it's saying, amp star, any one of those amps, turn on the evac channel. So, that evac channel, cuz this is just all, this is not doing floor above, floor below, anything like that. This is just, you know, uh, full building evacuation. Now, if you had an alert tone, you will put a delay in there for 45 seconds. Pretty much copy the first. You pretty much
just copy. Actually, you do it like this. You will copy this. Command C. I forgot to copy the comma, but you bring it over just to make it look neat. Command V and then channel alert. Boom. And then that's how you would turn on the alert channel. You want to make sure you have your closed guy, your open guy, who are we talking to or talking about. We're talking about that label on the amplifier, that secondary label or that second zone. The evac zone is first zone. Channel alert zone is the second zone. Depending on the audio system, if you have more than one channel, you could do it this way. But if you have one channel, it's usually just EVAC. So
we want to turn that on. And that's how you write that. But let me get rid of that. So now when we go to the speakers, we want to turn on the speakers on whatever floor. Whatever floor speakers, whatever floor. So any speakers we're going to turn on. Any strobe booster panel we're going to turn on. Any door release and fan shutdown we're going to turn on. And this disable switch. I'll show you how to write. It should be one here to write that. Yeah, there's a bypass switch. So the next rule would be the fan restart rule. So we have switch as the qualifier. What are we trying to do with this rule? So
we need to identify what are we trying to do. [music] Do we want to alarm? We want to do something with the alarm inputs. We want to do something with switches. We want to do something with LEDs. We want to do something with supervisories. What are we trying to do is what we're trying to describe on the input side. So SW or the word switch will work in this location here. And then what switch? What switch are we talking about? So now let's go over here and let's go over to switches. So what switch are we talking about? What switch are we trying to activate? Right. So now we have a bunch of switches here. We
have the page switch. We have the stair switch. We have the fan restart switch. We have more stair switches. And then we have a bunch of spares. And then we have down here the bypass switch. So which switch are we working with? Right. We're working with the fan restart switch. What do we want to do with the fan restart switch? We want to turn off this fan restart. What is this? What is this fan restart? Let's find out. So the fan shut. So what are we doing? We turning off the fan shut. So what are we looking at? We're looking at the fans. This is the fan control. the point type to uh
for the fans. This is something when you you don't have to write a rule for everything cuz there are some point types that you can use that automatically know what to do when the system does what it does, right? So you can use the fan control or you can use non-supervised output, but I would just use fan control. So fan control for my fan relays is easier. So you could just write your levels, what fan it is, and then the number that will associate with it if you have however many fans you have. So you have going back to the rules. So the stars here for the fans is automatically understanding all of the
levels and all of whatever is in this column like those numbers that's identifying that fan shutdown that's making them unique. So it's going to know exactly who to turn on. So here we have a fan restart LED. Now we're using relay config. So what this is saying that for this for any one of these relays when they go active there's a pseudo point inside the system that turns on. So what this is saying when that pseudo point inside the system turn on anytime any one of these relays activate I want you to turn on this LED.
So that's a easier way to do it or you can just write you know a different rule to say LED what LED then turn the LED on or you can put the LED in another rule when the activation [music] actually happened. But they're actually trying to control how this thing actually happened rather than just turning LEDs on because you told it to turn on. We want it to turn on when the system knows the relay had did what it's supposed to do. This is a better way to do it, right? So now we go over to elevator recall. We have the alarm. What
do we want to activate? We have smokes, right? We have a bunch of smoke detectors. So let me show you how we would identify smokes. So we have all of these smokes here. Bunch of different area smokes. Now to identify the elevator, we will either put the word elevator into it. So here we have one example right here. So we you see we have L2. This is the first elevator lobby, right? This would be the one in the cellar. So this rule will be different than all of the other smokes slightly. So we have the level that it's on auto because I guess this is a auto
shop. And then instead of putting the number, we put the word elevator just to switch it up a little bit so we can write a separate rule to control [music] the elevator smokes differently than the rest of the system. So now the L star will still activate this guy because it knows from this point on what that star represents. So it really doesn't matter what these numbers and letters are. As long as you put L-star, it will activate each and every input device that's supposed to activate the on the input side. Right? So now let's go back over
to the rules. So now what are we doing with the um elevator recall? We're turning on that relay, the elevator recall relay. Pretty simple. Same thing here. So now we have the alarm flow. There's only a few water flow switches in the in probably in the building. So, same scenario, Lstar, any one of those levels, I don't care what number or what it is after this representation. We're going to turn this input label, any one of those input labels will activate this elevator recall output side. Right? So, now we have the bypass switch. You
already seen all the switches how we activated the fan. So, inside the switch, we identified one of them, that last switch, as the bypass switch. So now what we doing here is we're turning on that LED immediately. So that way soon as we hit the switch, this LED is going to turn on that same associated LED. Then we're going to disable the speakers. We're going to disable the strobes. We're going to disable the door release. We're going to disable fan shutdown. And we're also going to latch off the fan shutdown relays. Right? So we're going to make sure none of this activates when we hit this switch. So we
doing some testing in the building, somebody doing some work in the building, you would hit that bypass switch so they can go do what they need to do. Then the next section is our paging. Right? So anything inside of the French brackets will be ignored. Right? So here we have the all call paging. And the easy qualifier for that is just the word all call. And here we turning on all the amps, all the CC1, CC1S's, and then we want the LED to turn on steady. And we want the page LED to turn on steady. Now, the next rule I'm going to
explain a little bit differently, but all we doing here is turning on the amplifier, but we turning on the page section of the amplifier. You see up top is the evac. So, we can get the evac tone to get the people out of the building. Now, here's where we start write the rules for the speaker paging so we can press the microphone and start talking, making our announcements, getting people out the building, whatever it is we have to do when we turn on a microphone. So, we want the amp to turn on. But which channel of the amplifier are we turning on this time? When we hit this button, we want to turn
the channel page on. The first one, like I said, was the channel evac. So, now we turning on the channel page. So, what are we turning on? We want to turn on all the speakers throughout the building. We want to turn on all the stairs throughout the building. We want to We're not turning on the strobes because there's no alarm, right? So, we're not going to even have nothing about visual, nothing about strobes inside of this rule. Everything is here is speaker outputs. Then we're going to show an indication that we have the LED associated with the stairs and the LEDs associated with whatever floor that
you're actually paging. I'll see that I'm paging the second floor and I'll see that all the stair speakers are also activated. Actually, it won't even be the second floor. Excuse me. I'll see that all the LEDs throughout the building will turn on and all of the stair Well, there's only one stair speaker should be A and a B. And then all of the stair LEDs will actually turn on. That will give me a quick indication that or at least supposedly all of the outputs that I'm supposed to be speaking to is actually active. But you have to test it to see if everything is actually working on each and every floor and each
and every speaker. Next, we have individual floor page. How we work this out is using the N variable. The N variable represents [music] different flaws. Now, I'm going to show you how this work. For the switch, we want to do a switch. We're saying any switch that we press between the first floor and the ninth floor, any one of these page switches. So if I turn on third floor page, second floor page, fifth floor page, whatever paging switch I turn on, I want you to turn on the
amplifier, the channel page amplifier. I want you to turn on that specific cuz we're using the N variable. I want you to turn on that specific amplifier or rather that specific amplifier for whatever floor switch I pressed. I want to turn on that specific speaker and also that specific LED to let me know that if I hit the third floor switch, the third floor speakers will come on and the third floor page LED should be lit. Then I can hit the microphone and start speaking. So here we have the
stair paging and here we going to go switch. What type of switch are we turning on? The stair switch. We have four switches to turn on for the stairs. So any one of these switches that I turn on, I want you to turn on the stair speaker circuit for that area. Right? So we're going to turn on the amplifier. What channel? We're turning on the paging channel because we're pressing a button to make a page. We're going to select whatever speaker for that stair. Stair one, stair two, stair three, stair four, whatever. Then we want to turn on
that associated LED so we can know that we're actually speaking in that same area that we actually indicated from our press. Then we have the stair page. This is kind of like the all call for all of the stairs. So we go switch all of the switches, every last one of them, all of the stair switches, let's say. Then we want to turn on the amplifier again, the page channel, and then all of the stair speaker LEDs and the all stair page LED. Maybe there's a just one specific LED for when all of them turn on. And then we want them to turn on steady. We don't
want them to flash. We don't want them to blink. We want them to turn on steady. Then the last set of rules after this is the central station. So if you have a ModCom installed, you literally have to tell it if it's going to be zone 42, contact ID, and you have to write the rules for that. So these rules are for contact ID, individual reporting. So when you write your rule, always have your rule label. You have your rule label and what are we activating or what signal are we sending [music] to the central station. So anytime there's an
alarm from a smoke detector, we want to send the plus is the send and this the number string for smoke detector that the receiver understands. So when that series of numbers get sent over the modcom, over the phone lines to the receiver to the central station, it knows that a smoke whatever address came in from this system. And the 311 is the restore. So the ones is the activation. The threes are the restore. And you can get all of this information inside of the modcom. I'll show you that in a
second. Then you have your heat detector. So every point type, smoke, heat, carbon, pull, water flow, tampers, supervisory, local trouble. That's any trouble that happens on the system. You lose battery, disconnect the wire, it just powered up. Any trouble, that's a local trouble. You have your battery, you have your AC, you have your telco one, telco 2. Then you have your generator run, your generator fell and your generator ATS. You have to identify each individual point type and know what
that message string is for the activation and know what the message string is for the restore. And this all information is [music] inside of the SDU. So now once you write your rules and everything is in there, you will click okay to save your rules. You will close out of your object labels. You will click on rules and you will go compile rules. You will click ignore. You will compile rules and you click okay. You go through the rule compilation. Once you compile your rules, you can view the warnings or not. I usually just click no. And then here I
convert all of the databases cuz what you're doing here is pretty much turning the letters to zeros and ones. So when you download the computer can understand what the hell you did. So any changes that you make, you always compile your rules and convert all of the databases and then you download to the system. Once it's done, you just click okay. So now that you understand how to write the rules for evac page and also alert zones, it's all pretty much the same. You just have to understand what it is that you're actually trying to do or just follow the sequence of operations.
So now that we went through the SDU, so you could pretty much understand how to write a rule to turn on the amplifiers. Let's go over some of the common mistakes that you may see. Now, the mistake number one is definitely syntax error. You want to make sure you have your open guy and your closed guy. You want to make sure you have your colons. You want to make sure you have your commas. And you want to make sure you have your semicolon to close out the rules. You have your input side and you have your output side. You want to make sure what you're activating. If it's going to be an alarm input, if it's going to be a switch you're going to be pressing, if you need a confirmation from a relay, if you have anything that
you're trying to turn on and activate, you want to put that on the input side. And what are you activating on the output side? Are you activating amplifiers? You want the amp to turn on. You want the amp to turn off. You activating modules. You want the modules to turn on. You want the modules to turn off. You have LEDs. You can blink the LEDs or you can hold the LEDs steady. So depending on how you're trying to program, this is how you can actually do it inside of the SDU. You just have to decide how you want to create your levels. Level zero or level one or just put one or just put two. [music] However
you do it, you need to understand how you breaking down particular flaws when you're doing an audio system or class E type of system. [music] And lastly, compile your rules and convert your database before you download. Even if you're working on something like a map fault and you upload the loop, convert it, then download it back. Everything you do changes that information to what the CPU can actually understand and read. So if you don't save your changes and actually compile your rules and convert your database, you're not transferring that information over to the fire alarm control panel. So, that's how you would turn on amplifiers inside
of an EST3 system. And if you're looking for more information, we'll be going live every two weeks. The link is in the description. We'll be talking about this fire alarm control panel behind me. We got a few floors. We're going to be doing floor above, floor below, and also the fire floor. It's a horn strobe system. There's no speakers, so I don't have any audios, but we do have LEDs and switches where we going to be doing a bunch of funky controls and rules. All right, so link in the description. Click the link and I'll see you in the live. I peace.
Cheat Sheet https://assets.cdn.filesafe.space/JUeauqFFpAgQpPWQ1TsD/media/6a92a72e0914f11215011369.pdf Spark Series Book https://pocketedition.secureitsecurities.io/pocket-optin-855933 Join The Course...
NYS 81 Hour Fire Alarm Training https://nysfirealarmlicensecourse.secureitsecurities.io/ Spark Series Book https://pocketedition.secureitsecurities.io/pocket-optin-855933 Join The Course...
Spark Series Book https://pocketedition.secureitsecurities.io/pocket-optin-855933 Join The Course https://firealarmbusinessblueprint.secureitsecurities.io/fire-alarm-blueprint Spark Series Book on Amazon...
Spark Series Book https://pocketedition.secureitsecurities.io/pocket-optin-855933 Join The Course https://firealarmbusinessblueprint.secureitsecurities.io/fire-alarm-blueprint Spark Series Book on Amazon...