Cheat Sheet https://assets.cdn.filesafe.space/JUeauqFFpAgQpPWQ1TsD/media/6a92a72e0914f11215011369.pdf Spark Series Book https://pocketedition.secureitsecurities.io/pocket-optin-855933 Join The Course https://firealarmbusinessblueprint.secureitsecurities.io/fire-alarm-blueprint Spark Series Book on Amazon https://www.amazon.com/dp/B0GQ5259GY NICET Clarity Bundle https://portal.secureitsecurities.io/courses/offers/f4a10f66-4311-49f5-9906-022de3ab310d Practice for your NICET Exam https://quizlet.com/join/t2hyD9xaN?i=6sn3ll&x=1bqt Create your own unique offer for free with the Offer Architect https://offerarchitect.secureitsecurities.io/free-architect Fire Alarm Business Blueprint eBook Download https://ebook.secureitsecurities.io/fabb-ebook Send us your fire alarm questions info@secureitsecurities.com Zoho One https://go.zoho.com/LwT Live Events https://firealarmtraining.secureitsecurities.io/live-events Virtual Business Office https://alliancevirtualoffices.referralrock.com/l/ANTHONYRIC61/ ➖➖➖➖➖➖➖➖➖➖➖➖➖➖➖➖➖➖➖ Stop failing fire alarm system inspections. Learn why your standard electrical license is not enough for fire alarm installations. Many electricians assume their existing license covers fire alarm installation, but that is a major oversight. This video explains why most fire alarm systems get rejected by inspectors. The problem is rarely the wiring or the device placement itself, but rather the failure to recognize that these are fundamentally different systems that require specialized knowledge beyond standard electrical work. If you want to avoid costly rework and inspection failures, you need to understand the critical distinctions between low-voltage signaling and standard circuits. Treating a fire alarm system like a standard electrical circuit is the quickest way to get a rejection. By adapting your approach to meet specific code requirements, you can ensure your installations pass the first time. Subscribe for weekly trade compliance breakdowns, and comment below with which inspection challenge you want us to cover next. #FireAlarmBusiness #StartAFireAlarmCompany #FireAlarmTechnician #ElectricianBusiness #SkilledTradesSuccess #ServiceBusinessStartup #FireAlarmTraining #JackAndMaster #SchoolsOfSkills #FromTechToBoss #TradesToEntrepreneur #FireAlarmBlueprint #BusinessForTechnicians #AlarmSystemBusiness #LowVoltageLife #TechToCEO #StartYourBusiness #EntrepreneurTraining #FireLifeSafetyBusiness #ContractorBusinessGrowth
Audio and video play straight from the show's own hosting. PodSubs stores and serves no media.
Transcript
From the show. Tap a time to play from there.
If you hold an electrical license, and you think that means you already know how to install fire alarm systems, I need you to watch this video. Because the number one reason why the fire department will reject your fire alarm install is not because of bad wiring or because you don't know how to install the devices. It's the electrician who wired up the fire alarm system the same way he would wire up electrical circuits. And those are two completely different animals. My name is Anthony Ridges. And I've been doing fire alarm system for about over 25 years. I've been running my business Security Security for over a decade now. And I've seen electricians out there in the trade
crushing. And I also seen electricians get their jobs ripped apart by the fire inspector because no one told them how to do it correctly. So, in this video, I'm going to give you the eight mistakes electricians make in New York City so you don't have to make the same mistakes on your next fire alarm install. So, let's get straight into it. So, before we get into this first segment, I want to tell you a little story about an install I did downtown. This was on Thompson Street. This is when I first met the electrical contractor that we actually work with
today. So, when I first get to the job site, I meet with the electrician. We going over the project. And I'm noticing that there's like MC cable going into the fire alarm panel. And as I open up the box, I see black, white, and green cables for data, for the horns and strobes, pretty much for the whole entire fire alarm system. So, I'm looking at the electrician like, "Who installed this?" And they was like, "We installed it." So, I'm in my brain like, "Damn, we got to go through this whole entire system because nothing is going to work." So, as we going through the systems, I'm pulling down the smoke detectors, looking at the base, and I'm
finding that these guys is wired in series. Like the smoke detectors, from each smoke detector, they all wired in series as if they were installing high hats. I had to regroup, call the office, let them know what the situation was. And then it took me at least 3 weeks to actually go through this whole entire system with those three wires so that way they could actually wire the system correctly, identify what cables was going to be for data, and identify what cables was going to be for the NAC circuit. It was a lot of red tape, a lot of black tape we was using because all we had was black, white, and green. We
didn't use the green, but all we had was just black and white to work with for all of the circuits. So, we had to identify them. Then, the gauge of wiring was a little bit too big, especially for the modules and also the smoke detector bases. So, we had a terrible time with this fire alarm install cuz there was no way we could have re-pulled the cables because everything was already closed up. Long story short, the system did pass and thankfully we didn't have to take down any of these devices to cause a trouble on the system so that way the fire department could see the actual trouble. Then, he would have noticed that we had an issue, opened up another can of worms, but we actually got past
that, went through it, and every job forward after that we had to let them know, "This is the design, these are your drawings, and these are what you have to follow." So, I'm not sure if they got a set of drawings from the company I was working with at the time or they just went and freestyled the whole fire alarm system. I don't know. But, it took us 3 weeks to get that system up and running. We actually got it working, system passed, good to go. Now, we can move on to the second. And that leads me to the first mistake, depending on the requirements of the particular project you're working on, they're going to want class A or they're going to want class B wiring circuits.
And on the shop drawings, it's going to show you if there's a class A or class B circuit. If it's a class B, it's going to show you that it's going to be ending at some particular point. And if it's a class A, it's going to show you that that wire is going to return back to the fire alarm control panels. So, as an electrician on installer, you have to be able to read the shop drawings so you know how to install the system properly. Now, electricians, they really understand home runs. You run it from the panel to the end device. However, in a fire alarm system, it's usually like a
looped system, so you would have to go in and out from each of the devices that you're running in. It's actually a parallel system that you're actually wiring rather than a series type system that you actually wire when you're putting in lights and high hats and switches. Now, in the NFPA 72, your SLC and your NAC circuits can be wired under class A and class B configuration, depending on class B could be your standard two-wire loop that will terminate at the end of line, especially if you're using a NAC circuit, it's going to have a end-of-line resistor so it can supervise that NAC circuit. And
on a four-wire loop, you will have a feed that's going to feed the devices, and then you're going to have a return that's going to return back to the devices. Now, a class A circuit is a lot more durable than a class B circuit. It can work on a single open. So, if you have an open on one side of the leg, either on a feed or the return side, you will still have voltages going out in both of the directions up until the break, so that way each and every device is on a loop up until the break will actually work. So, here's where electricians get burned. This was a hotel we did in Queens that I was helping out with some electricians. We
were troubleshooting a ground fault on a data circuit. Now, they ran the wires correctly, they had the 16 for the data, 14 for the NAC circuit. As I'm measuring the data circuit without any power, I notice there's 47K on it, and I'm like, "Why is it 47K at the end of this loop? Maybe there's I didn't I'm in my mind, I'm not thinking that there's a resistor at the end of this line." And he didn't bother to tell me because he's not thinking that this resistor is causing a problem to the loop. I'm just thinking that it's too many devices on the line, it's it's cuts on the wire, it's it's
screws in the wire. I'm just thinking that this whole wire run is messed up until we actually get through the whole entire loop, and I found that the end of the line had a 47K resistor, which was killing the whole entire data loop. So, we had to explain to the electrician that only from the module you would put an end-of-line resistor, or if you're dealing with a NAC circuit, the end of that device will go in you would put an end-of-line resistor there. But, at the end of the data loop or your SLC circuit, no, you do not put no resistors
on this circuit at all. Anything that tap off of it from a module, that is what gets the end-of-line resistor other than the control relay. So, after we identified where the problem was, we found it cuz it was upstairs at the top. We removed the resistor and restored all the devices back to that data loop, fixed the panel, cleared it, back to normal. So, the moral of the story is just make sure you're paying attention to the shop drawings. You should always have a set of shop drawings before you install any type of fire alarm system. It'll let you know where to put the end-of-line circuits. It'll let you know the size wiring, and it'll let you know
if you're going to be running a class A or class B circuit. Now, this is a move me into mistake number two, and that's using the wrong wire gauge. The same as the first electrician using the MC cables with the black, the white, and then the green cables, that number 10 wire was way too thick to be putting in a fire alarm terminals. It is a reason why we use 16-gauge cable in order for it to fit securely under the screw terminals when you're installing fire alarm devices. So, using the right wire gauge is very, very important, and it also is calculating
how far the signal will travel on a cable. So, a lot of these things are predetermined. So, you have to use the right type of wire, the right type of gauge, so that way you are in compliance when you're installing your fire alarm system. The fire alarm manufacturer publish specification on the type of wiring you should use for their particular system. No matter what fire alarm manufacturer you're dealing with, they have specifications, even if they all say the same thing. It doesn't matter. Whatever your fire alarm manufacturer say is the wiring that you should be using for their system. Now, beyond the gauge with the fire alarm
wire requirements are, in New York City, you have to use a different type of fire alarm wire, and this is Teflon fire alarm cable. It's very expensive cable, and this is the cable that we can only use inside of New York City. I'll have a demonstration of what this cable look like, so you can see exactly the type of cable it is. It's not like the other fire alarm cables that they have out there. It's not soft. It's very stiff, and it's very durable. So, it burns at about 600°, and it doesn't release any toxins. So, the cable that we use out here in New York City, whether it be 16 or 14, you'll see that that cable is
very different from any other fire alarm cable that you may buy out there. Now, this is going to move me to mistake number three, and that's ignoring device placement. Now, I understand when construction has happened, the first guy that usually come in is the AC guys because they're going to be taking up the most space. Usually, it's the plumber then the electrician. Still, everyone also have plans that they have to follow. So, when we're designing systems and you put your high The electrician have their high hats in a certain spot, the sprinkler tech will have their sprinkler heads in a certain spot, you still should be able to mount
that smoke detector in a spot that's feasible, that's going to still be able to cover that whole entire area, section, or room properly. Now, what most people know is a 30-ft spacing for smoke detectors, that's pretty much standard. But, where it get tricky is where you have slope ceilings, depending on a slope incline or decline. If you have joist beams, depending on the size of the joist, this will also dictate the type of smoke detectors, the amount of smoke detectors, and where you will have to place these smoke detectors. So, it's very important to pay attention to your shop drawings when the engineering is designing their system for you to
install it. So, just make sure when you're installing the devices, you're putting it as close to as where it represents on the drawing, so that way you are installing the system within compliance. If you're an electrician and you want to add fire alarms to your business, then click the link below, you can join me at the Fire Alarm Business Blueprint. It has everything you need to know how to operate your fire alarm business. You don't need to go through the course, the 81-hour course, to get your fire alarm license if you already have your master electrical license. All you have to do is submit the paper, all you have to do is submit the application, pay your fees, and you will get your fire alarm license. Then from
there, I can show you how to market, position it, and actually make money, and generate income for your fire alarm business. Link is in the description. I'll catch you on the other side. Now, mistake number four is not understanding the fire department filing process. Now, I understand there's a lot of paperwork. This may not be your requirement. This may not even be your job, but it's still a process that you will have to understand. The engineer is the one who will file the application, design the drawings. The engineer will then pay the fees, but they get reimbursed by the client. Once the the drawings are
approved, we will then have to fill out a project authorization. This is all specific to New York. When we get the project authorization a back approved, then that's pretty much giving us our go ahead to install the fire alarm system. Once we install the system and completed, we have to then fill out a 433. The 433 shows the fire department that here go the installers of the fire alarm system. We have the electrician's information, and you'll have the fire alarm company's information. The electrician will stamp it. The fire alarm company will put the S97
certificate. They will list out all all of the devices on the floors, wherever the floors. They will list out each and every one of the devices on whatever floor they're on, the whole entire system, the type of wire you use, everything like that. Then you will have to submit that A433 as as pretty much a completion when you're submitting your request for the final inspection. So once all that paperwork is done, you have your as-built riser diagram, you have your record of completion cuz you installed the system, you tested everything to the central station, you know everything works. Then you call for
your final inspection to get the fire department out there to actually finalize your system. That is the entire filing process for a New York City fire alarm job. It may seem like a lot of steps, but there are other vendors that are taking up those tasks. You as the fire alarm company should be the one delegating these tasks to either the engineer, the expediter, or the electrician. Now mistake number five is mixing fire alarm circuits. Now this can be very dangerous cuz you can put 24 volts on a data circuit, or you can put AC on a data circuit. You don't want to mix the wiring because 24 volts and your
NAC circuits generally use the same type of wiring. So when you're running your wires, you want to identify what cable is serving what circuit. If you have 16 wire, you want to tag it and label it data. If you have 14 wire that's supplying power, you want to tag it and label it 24 volts. If you have another 14 wire that's serving your NAC circuits, you want to tag it and label it NAC 1, NAC 2, 3, or 4, whatever NAC circuit it's serving. If you tag and label your wires, you can never mix and match and cross cables. So, when it's time to power up that system, you can
power it up with confidence. Now, mistake number six can cost you. This can cost you a fine, this can cost you a violation, cost you another re-inspection that you would have to pay for. And that's skipping your pre-acceptance test. You must test 100% of everything. If you have one device connected, or if you have 1,000 devices connected, you need to ensure that each and every device function as is programmed, and each and every device relays that signal over to the central station, and the message says exactly where the location is. Everything must
work. This is a life safety system that you're installing, and you want to make sure if there's ever an emergency, the system will respond in the way it's supposed to, so that people can get out of the building. So, it's your job to make sure you're installing it correctly each and every time. So, it's your job to know that this system is 100% functional after you install this system. You don't want to guess, you need to know for sure that this device will shut down the elevator, or recall the elevator, or shut down the fans, or turn on stair pressurization. You need
to know if it's going to activate the horns and strobes. If you have speakers, you need to make sure that it's clarity going through the speakers. If you have an overload, if you have an overload, or if there's some horns and strobes, or some speaker strobes that's not working, then maybe you need to add some more power. You need to go back and do some recalculations, but your job is to make sure you do 100% test that everything works. Phone lines, batteries, AC, everything. Now, we're leading into mistake number seven, and that's not programming the system correctly. Now, I understand that programming is
challenging, can be challenging, is more for the advanced technician, but I want to give you a thorough understanding of programming. If you could understand how the system actually operate, what's supposed to do what, when a smoke detector activate, what are the functions that's supposed to happen, when a pull station is activated, do you know the functions? If you can understand what the functions are, the next thing to get through is understanding the language of whatever system that you're working on. Rather it be zone configuration, correlations, writing rules, custom controls, whatever it is, once you understand the language,
it'll be easy to program any system cuz if you understand the function and then you thoroughly understand the language, it's easy to do any system out there that you're working on. Now, some electricians may be very good at putting panels together, wiring up things very nice, but they may not be computer savvy, they may be a little slow on the computer, so they may not be able to have the mind of a programmer to think as such. Now, that doesn't mean you can't program, that just mean you have to practice a little bit more. So, if safety is always in the forefront of you knowing that you're providing this, you'll get better at what it is that
you're doing on a daily basis. Now, mistake number eight can cost you your business, this can cost you everything, and that's not knowing how to price out a fire alarm job correctly. Now, this last one is the most expensive electricians can actually make, and this doesn't show up on inspection day, this shows up a few weeks after you already started the job. You're behind on schedule and you're troubleshooting problems you didn't even budget for. Now, you're starting to realize you're losing money every hour you spend on this project. So, electricians, I don't want you to price your fire alarm jobs as an electrical contractor. I want you to start pricing the job as a fire alarm
contractor. We're going to put on a different hat so that way we can price our jobs correctly and actually make money in our fire alarm business. The first thing you need to understand is fire alarm labor runs a lot slower than every other trade out there. There's a lot of paperwork we have to get past, inspected, prepare, and do and submit. There's a lot of waiting. Fire alarm labor runs a little bit slower than electrical labor, especially on a per device basis cuz each device needs to be tested, inspected, and fully functional. And once they're fully functional, we now have to prepare the paperwork and
document everything. So, your device count is not your device install time. You have to account for commissioning, programming, and documentation for every project that you're on. You have fire alarm materials that carry a significant markup. You have the central station you have to install. You have the paperwork for the central station that you have to fill out and activate. So, when you understand that your smoke detectors, your modules, these are proprietary to you, especially if you have a fire alarm manufacturer. No one else can buy it but you, because you can buy it directly from the manufacturer. So, you're going
to get a dealer price from your fire alarm manufacturer, and then there's always an MSRP price. You don't want to pass off your dealer price. You want to be able to make money on the fire alarm devices that you're actually installing. It's a proprietary system, so only you can provide this. All right, so let's recap what we went through this entire video. Number one, don't wire the fire alarm control panel the way you think it should be wired. The shop drawings will tell you if it's class A or class B. And also the size gauge that you need for each circuit. And number two, using the wrong wire gauge. You don't want to use
the wrong wire gauge or the wrong wire type when you're installing a fire alarm system. And number three is device placement. You can't just place a device wherever you want to. They have to go in the exact spot or close to the exact spot as designed by the engineer. And number four, not understanding the fire department filing processes, especially in New York City. And number five, mixing fire alarm circuits. 24 volts with data, data with the NAC circuits. You don't want to mix fire alarm circuits. And number six, calling for inspection when you didn't fully test
the system 100%. And number seven, not knowing how to program the fire alarm system. And number eight, not pricing out your fire alarm correctly so you can actually make money. So, if you're an electrician looking to put fire alarm into your business, I'll be going live every two weeks talking everything about fire alarm from installation, central station setup, business, marketing, everything. The link is in the description. Come join me live. You can ask your questions live and we can chop it up there. All right? I'm Anthony Richardson and I'll catch you in the next video. Peace.
NYS 81 Hour Fire Alarm Training https://nysfirealarmlicensecourse.secureitsecurities.io/ Spark Series Book https://pocketedition.secureitsecurities.io/pocket-optin-855933 Join The Course...
Spark Series Book https://pocketedition.secureitsecurities.io/pocket-optin-855933 Join The Course https://firealarmbusinessblueprint.secureitsecurities.io/fire-alarm-blueprint Spark Series Book on Amazon...
Evac Rule Cheat Sheet https://assets.cdn.filesafe.space/JUeauqFFpAgQpPWQ1TsD/media/6a8f6a30d1afbd2cbcbfbcc8.pdf Spark Series Book https://pocketedition.secureitsecurities.io/pocket-optin-855933 Join The Course...
Spark Series Book https://pocketedition.secureitsecurities.io/pocket-optin-855933 Join The Course https://firealarmbusinessblueprint.secureitsecurities.io/fire-alarm-blueprint Spark Series Book on Amazon...