Master The NEC | Episode 65 | 2026 NEC and 120.6 Noncoincident Loads Finally

Jun 28, 202643 minAudio
ShareXLinkedInFacebookWhatsAppEmail

This episode we talk about the 2026 National Electrical Code and how finally 120.6, which was previously 220.60, is not clean and straight to the point. In this little podcast we will bring it to life and explain how you would utilize it in an everyday situation. A casual conversation about how to treat the loads. Listen as Paul Abernathy, CEO, and Founder of Electrical Code Academy, Inc., the leading electrical educator in the country, discusses electrical code, electrical trade, and electrical business-related topics to help electricians maximize their knowledge and industry investment. If you are looking to learn more about the National Electrical Code, for electrical exam preparation, or to better your knowledge of the NEC then visits https://fasttraxsystem.com for all the electrical code training you will ever need by the leading electrical educator in the country with the best NEC learning program on the planet. Become a supporter of this podcast: https://www.spreaker.com/podcast/electrify-electrician-podcast--4131858/support.

Audio and video play straight from the show's own hosting. PodSubs stores and serves no media.

Transcript

From the show. Tap a time to play from there.

Speaker 1Welcome to the Master of the NEC podcast, the ultimate destination for anyone passionate about the electrical trade. Whether you're a season electrician, an eager apprentice, or just someone who wants to dive deep into the world of electrical work, you've come to the right place. Join your host, Paul Abernavi, a true authority in the industry with over thirty eight years of trade experience, as he electrifies your mind within depth discussions, expertips, and valuable insights.

Speaker 2That will keep you ahead of the curve.

Speaker 1Each episode, Paul will illuminate the complexities of the trade, decode the National Electrical Code, and share the latest industry trends, all while empowering you to take your electrical career to the next level. So gear up, plug in, and get ready to supercharge your knowledge because with the Master of the NEEC podcast, the power is in your hands.

Speaker 2Now get ready. Here is your host, Paul Abernavi. What up, everybody? Paul Abernat you here, Thanks for joining me on today's podcast Here at Master the NEC Podcast, where we talk about the National Electrical Code and of course all things electrically related. Glad you could take time out of your day to join me for this podcast episode. It's been a minute since we've talked the National Electrical Code. I've been very busy working on the stack caddy project, which

Speaker 2is a separate website folks, if you get a chance, go look at it stackcaddy dot com. Some great products over there to make your life as an electrician just a little bit easier. Plus some cool stuff as well, like a wirenutkoozy and you know, all kinds of good stuff, so check that out. We constantly have new things coming. But we have some neat ladder trays and step caddies and just some neat stuff. And if you're an electrical inspector, we have a neat little inspector caddie over there as well, so check that out over on stackcaddy dot com. But

Speaker 2you know, we've been busy working on that and trying to get the twenty twenty six edition going. But including that, I've also been busy working on some articles for E. C and M magazine. As you may have heard, I am going to be writing for them. I'm one of their NEC experts and I'm going to be writing some articles, I think six of them that we're going to be doing for the next year every other month, and I'm going to be focusing on inspector electrician relationships and different things where they get in disputes and interpretation and all

Speaker 2those kind of things. But I'll also be doing some videos explaining some code things for them as well as some podcasts also, so check that out with EC and M magazine. So I've been busy with that, and I've also been extremely busy with Thermal Electrician as well as the CBCP program and just so much stuff going on here at the Academy that it's kind of caused me to not be able to do any videos in a while, and I have not been able to do any podcasts really in a while. So you know, bear with me.

Speaker 2This will all cycle back around and we'll get back to the normal schedule where I'm posting all kinds of content, especially with the twenty twenty sixth edition of the NEC soon to be adopted by a couple states. I think in September the Texas will pick it up in Massachusetts maybe soon, or they may be in the amendment stage to it, you know how they got to change some things. But anyway, all that's around the pike and we're working on our twenty twenty six program for the fast tracks in case you haven't heard, and it's taking a little

Speaker 2longer than normal because of the illustrations and graphics. It's just a lot of work and I don't have the same amount of time as I used to, so I'm trying to get that out as quick as I can. The good news is most of the stuff that we're doing, you're still a good year out, maybe eight months out where your state is still going to be on the twenty twenty three or twenty twenty. So we've got plenty of products for that, so check it out and if you're interested in learning the NEC. But of course, thank thank you for joining us here on this podcast where today we're going to talk a little about the twenty

Speaker 2twenty six edition of the NEC. We're going to talk about a significant clarification and I think it's the way it was supposed to be, but everybody, even including me at times, can get confused with it when it comes to that twenty five percent for the largest motor in a calculation, as well as understanding non coincident loads and how they would work together. And we kind of straightened that out in the twenty twenty three edition, I think everybody was pretty clear on how you would do that, but they've made it. The code panel made it so

Speaker 2much easier to understand in the twenty twenty six and of course now everything makes better sense, right, So we're going to try to make sure that we clear that up and we're all done with that, and now everybody can move forward. When it comes to non coincident loads in that infamous additional twenty five percent, which by the way, you're not going to see it say that in the code, you just have to understand that when you have multiple motors or motors and other loads, that you're going to take the motor at one hundred and twenty five percent

Speaker 2plus a some of the other loads. And based on the language of the code, if you have multiple motors in four thirty dot twenty four, which you will, if you have a bunch of appliances that are in a building or in a dwelling, you're going to take the largest one at one hundred and twenty five percent and the sum of the other which are probably already going to be accounted for when you do the appliance calculation. So anyway, we'll talk about all that. That's what we're going to be covering on today's podcast. So buckle up and make sure you got your codebook, and again feel

Speaker 2free to pause the podcast. Remember now we have over one thousand episodes available on all your popular platforms. You just go searching for Master the NEC Podcast and you'll find our podcast. I am a podcaster. I love to podcast way more than I love to do videos. Just I like the challenge of being able to convey a message in audible form rather than just having an image or an illustration. I think that sometimes you can tell

Speaker 2whether or not somebody really has a grasp of the topic by how they can explain it, and that's what I like to do. I like to do that. But at any rate, let's go on and get into the day's today's topic. So first things first, you all know that in the twenty twenty six edition of the National Electrical Code that the calculations that were previously in the twenty twenty three were article two twenty and in the twenty twenty six edition of the NEC that got moved over and it's now article one twenty. So again not a

Speaker 2whole lot of technical changes. Still got Part three, which we call the standard method, Still got Part four, which is the optional method. Still have Part five, and I mean you still have all of the same technical information. It's just been moved into chapter one and you're going to see a lot more of this because we've already started working on the twenty twenty nine edition of the NEC And I know there's people out there that say, don't change it. But the effort is to try to

Speaker 2make things a little easier to flow. We can't make it any easier to understand, and when we try every cycle, we try to make things easier to understand. But the real issue is to try to make it flow a little better, keep the calculations up front where they need to be, and just kind of let things flow a little bit. So the twenty twenty six edition, we're starting to dip our toe in moving around significant articles, and so that was what we did with the article to twenty got moved to one twenty. So people ask me

Speaker 2all the time, can I take an exam it's on the twenty twenty six if can I use a twenty twenty three codebook. Absolutely, the technical information to be the same, just you just need to be aware that the codes sections may change a little bit, right, article may jump around a little bit. But as long as you've prepared for that, you'll be okay. You just have to know how to utilize the NEC and how to be able to jump back and forth and use the table of contents, use the index, those type of things, and then understand some things will change. And in some states you can

Speaker 2write in your codebook, so you can make a little note in your codebook or something like that, but again, only do that in a state that allows you to mark in your cobook. Now, if you're already licensed and you just got your codebook in your truck, then you can mark all you want in your codebook. It's your codebook, you own it, and you can mark whatever you want. All right, So let's get started first. So what we want to do is let's look at the scope really quickly of one twenty so that we know what we're dealing with U. And of course we're going to focus on the non coincident load aspect and that infamous twenty

Speaker 2five percent for the largest motor that people go looking for that language and don't find it, and they say, well, where's that in there? Well, I'm gonna explain to you where that comes from. But we need to look at the scope. Always read the scope, especially if you're digging into the NEC and you're not overtly familiar with it. Take time, whatever article you're in, stop and go read the scope and see if exactly what's covered in this scope is what you're needing that type of thing. So here it is one twenty one. The scope says, this article provides requirements for calculating brand circuit, feeder and service loads.

Speaker 2Part one provides the general requirements for calculation methods. Okay, so we're going to look at that, and obviously we're in Part one for the non coincident load. Gives us the direction here, and then it says Part two provides calculating methods for branch circuit loads, which we will use these for our load calculations in Part three or Part four. And then you have Part three and Part four provide calculation methods for feeders and service loads. Part four five provides calculation methods for farming loads or farm loads. Part

Speaker 2six is going to be calculating methods for health care facilities. Part seven is going to be calculation methods for Marinas, boat yards, floating buildings. It's typically talking about the receptacle loading, by the way, but it's going to give you that direction there. And then we get into part eight, which provides calculation methods for recreational vehicle parks. Okay, so that's the scope of one to twenty. It's nothing different than it was when it was two twenty. Okay, let's get

Speaker 2that out of the way. It's just a movement, and you just have to get familiar with the fact that it's moved into chapter one now instead of being in chapter two. Okay. All right, let's go on and tackle this issue about non coincident loads in one twenty dot six of the NEC. Okay, so here's what it says non coincident loads. It says for two more non coincidence loads shall be permitted to use the single largest of these loads in the calculation of the total load. Okay.

Speaker 2So we're looking at non coincident loads and we need to know what those are, and we do have some direction here in one. It's going to give us some clarity to that, which is great. But once we determine which of the loads that are considered non coincident loads, then we'll take the larger of the two or three or four or whatnot. Okay, so we'll kind of see how that would play out. Now, again, as educators, we tend to want to use AC versus heat as the

Speaker 2primary example all the time that you would see in a dwelling application, because I mean, that's just the easiest way to try to do a comparison, right, because it typically the heat wouldn't be on at the same time as the air conditioning. Of course it's a heat pump, then it may be which means that that isn't a non coincident load. But that's the concept, and that's why we usually will compare a heating load versus an air conditioning load, right. And for most electrical exams, they're just

Speaker 2going to give you the AC load and then give you the heating loads and you have to understand how to compare them and how to do this type of thing. But we're going to kind of break it down a little bit. So that's the first part of it. I can take the largest of the non coincidence loads and just go with the largest value, okay, and then you just totally discount the lesser value when it comes to the load calculation. For example, if I have a certain amount of load and I have two non coincident situations

Speaker 2pieces of equipment, okay, and so this piece of equipment can't operate while this one's running. This one can't operate while this one's running. This one's pulling one hundred amps and this one's pulling eighty amps, And I'm adding this various load to my load calculation. Then if I do everything based on the one that's a higher load load, then anytime the one that's the lesser is running, but the one that has the greater load isn't running. But I sized everything far as my load caalc to the larger of the two, then it's okay. It doesn't matter

Speaker 2because it's going to be less and I sized everything based on the larger value, So that's okay. The only problem that ever comes in with that is if by chance, I am going to end up running these two loads simultaneously, and then of course that would be a that would not be a situation where there are now non coincident loads. So that is absolutely something that the design engineer has to take into consideration the electrician it's doing it, especially if you want to utilize the rules in one twenty six when it comes to non coincident loads, So it

Speaker 2truly has to be a non coincident load. So now we understand that, we understand we can take the larger, the single larger of the of the loads that are non coincident loads. And again, if it's three loads and the third one is larger than the other two, then I size it to the large one. And they're all non coincident loads, means they're not going to operate simultaneously. Then what happens is, I'm okay, I just take the largest value and I can discount the other values in my load calculation. Makes sense. Okay, So now it says

Speaker 2how do I determine these values? So to determine how I do the comparison of these non coincident loads, it says determination of the largest non coincident load shall include treatment of any motor operated and combination loads as specified in one twenty eleven A. So we're gonna have to take the time to look at one twenty dot eleven A because now we have directions on how to determine

Speaker 2which the load of these non coincident loads, which one is the largest one, and so we'll get directions for that. Okay. Now the last line here is clarity on what is what constitutes a non coincident load, and it says non coincident loads shall be considered to be one of the following. Okay. So the first thing says, look for feeders or services. If you have two or more loads that are unlikely

Speaker 2to be in use simultaneously, then there you go for a feeder or service load calculations. If I've got these two or more loads and it's unlikely that they're going to be un simultaneously, okay, then those would be considered a non coincident load. I say be careful with this because this is a this is a determination. It is made based on analysis of the circuits and how they're supposed to run and how they could run, and that would be the engineers would design this out or look at the system. Whereas the next item says, because it's

Speaker 2it's basically any one of the followings. Here's the second one that makes it a little easier to understand. The second one says for brand circuit feeders or services. It says two or more loads that are prevented from being in use simultaneously by listed equipment. So this is where you know, I talk about the interaction between an electrical inspector and electrician in understanding whether something is unlikely. So

Speaker 2because you know unlikely doesn't mean impossible, right, Whereas if I have some piece of equipment that is listed, that makes it impossible, okay, barring some event we can't control, it's impossible because of the equipment's nature and how it's designed, like kirk Keys, where you can have you know, two different services coming in and one can't come in if the other one is the way the switching is right, So it's inherent to the equipment, and it's listed equipment that's going to isolate one from the other. Well that clearly,

Speaker 2if I have a piece of listed equipment, that's going to say that this load cannot run when this load is running, whether it's some kind of inherently the way the equipment is made, whether it's part of a listed device, whatever it may be, that one's easier to be able to push to the inspector and say, look, the reason I'm taking this load and I'm discounting this load is because I have a piece of equipment that's listed that's going to keep this load from being on while this

Speaker 2load is on. That makes sense. That makes sense to me. The argument that can creep in is item number one, and that is where you have these two loads or more and it says that they're unlikely to be used simultaneously. Doesn't say it's impossible. Two people could turn something on. They're just unaware of a sequence, and then they both run at the same time, so that one, you know, obviously, if an inspector or somebody is getting deeper into it,

Speaker 2or maybe even a plan reviewer looks at it and says, okay, I understand this where it would be unlikely, but you need to show me how it would be unlikely. That's reasonable. I mean, I would you know, I don't have a problem with that. I mean, if that's the case, and it is like this piece of machine would not run because it's it needs this other machine to run in tandem with it, and it can't run when this one's not run. If there's some kind of means that that makes it unlikely, then it's inherent to what however it's designed.

Speaker 2Then that's one thing. But if I also have a piece of listed equipment that's going to prevent it so that it can happen. Then that's you know, that's for me, that that's a no brainer. Then that is clearly a non coincidental load, and I'm gonna take whichever one yields the largest load, and I'm going to size my loads to that. That makes sense to me. The only argumentative one could be item number one. But I think today most people will design things out and the way equipment may be laid out, that may be very obvious that

Speaker 2this can't run when this is running or whatnot without any listed equipment. But you get two options. Here are two paths to be compliant here. And so again I can't speak for every possible application that could be conceived in this. I'm just saying that the local AHJS and I talk about this all the time that we all have to be open minded about how this may be done into the design in the layout that either way, that's how you would create a non coincident load situation.

Speaker 2And again, this would allow us to take the larger of those non coincident loads and treat that load in the calculation rather than the ones that are of the lesser value because they're not going to be running at the same time that the larger one's going to be run. You get me. Okay, Now, that's pretty straightforward, and that gives us a direction of being able to take the loads and understanding what's a non coincident load. Now, the problem that we had in the twenty twenty three edition

Speaker 2of the ANEC was making reference to imply that it that the and it's had to do with the justification for TO twenty dot sixty through the last couple of cycles where references were made to TO twenty dot fifty, which is from motors and things like that, and it really muddied the thing up. Okay. And what I mean by that is if if I'm comparing let's say, AC to heat, and I'm taking the AC, and I'm taking

Speaker 2the air compressor which is the largest motor and at one hundred and twenty five percent, okay, and I'm taking that because that's what the language said in the twenty twenty three and I'm comparing it to the heat. If the if the heat was greater than the AC, and I will tell you vast majority of the time it will be if there is resistive heating and things like that, Okay, I'm for for example's sake, if the heat is the larger of the two and it is truly non coincidental

Speaker 2with the AC. Okay, let's just say that if it's truly non coincidental with the AC means that one can't be on when the other's on, then let's say I DiscT I get rid of the AC loads because I'm going with the heat because it's a greater value under this non coincident load application. Okay, So the one hundred and twenty five percent, which is what was directed to us to utilize into twenty dot sixty, you're not gonna you don't see that now in one twenty dot six

Speaker 2because what you're gonna do is you're gonna get that inferred when you go over to one twenty dot eleven A. So that means we have to look at one eleven A. Okay, So if we go over and look at one twenty dot eleven A, it says motor operated in combination loads. Now this is actually broken down, and I would have loved to see this broken down in a one two three, just like we started doing in a lot of other

Speaker 2sections where it's easier to follow kind of just broken down into an itemized it just makes it easier to follow, and we didn't. And that's okay because it's still there. It's still all there. It's still broken down into paragraph. But here's what it starts out with. It says, where a circuit supplies only motor operated loads, the conductor sizing requirements specified in four thirty twenty two shall apply. Now you think that this only is applying to this conductor

Speaker 2sizing here, Well, we're not into ten. So what it's talking about is you're going to use this same scenario in order to do the load calculation. So the same concept. So for a motor only loads, if all of my loads were the non coincident loads, if they were all motor loads, then I would simply take the motors at one hundred and twenty five percent if they're continuous duty motors under four thirty to twenty two for a single motor,

Speaker 2If that's in our example, and whichever one is the larger, that's the one I go with, and then I discount the others because again, if that motor, the larger motor's running then and the others are not because they're all truly non coincident loads, and there's no harm, no foul. If everything is sized based on the largest load, there is no harm, no foul. But that is driven by the fact that all of those all of these we're talking about our motors, and in a commercial industry facility

Speaker 2they may be the case. So you may have non coincident loads, but they just happen to be, you know, motor loads, and this is how you would utilize it. But to determine the larger of those non coincident motor only loads, you would use for thirty dot twenty two for that okay, for that application. Now if and that's again, if it's the circuit is supplying only motor operated loads, Okay. Now it goes on to say, all right, well, the second part says it says, where the circuit supplies only air conditioning equipment, refrigeration equipment, or both, the requirements of

Speaker 2full forty dot six shall apply. So when it comes to the air conditioning and refrigeration, you're going to be up in article four forty and you're gonna be at dot six, which is basically to pull things from nameplate values. Okay, and so the rated load current you're going to get all of those information from there, and you're going to use that and you're going to compare. Okay, you're going to compare with your other non coincident loads. Okay, So where you're gonna get that direction? Now, it says for

Speaker 2circuits supplying loads consisting of motor operated utilization equipment that is fastened in place and has a motor larger than one eighth horse power in combination with other loads. And I will remind you that in an HVAC system, the air conditioning compressor is probably going to be larger than an a to howars power, and that is going to be a piece of fastened in place motor operated utilization

Speaker 2equipment under these conditions. Okay. So it says, if that's the case, then the fasten in place with the motor larger than one eighth horse power in combination with the other loads maybe a condenser fan, maybe a heat pump or whatever, okay, to calculate, shall be not less than one hundred and twenty five percent of the largest motor load, which would be that air compressor er yeah, compressor, yeah, And then the plus the sum of the other loads associated in accordance with four point thirty dot twenty four.

Speaker 2So in terms of the motor aspect of it, okay, one hundred and twenty five percent plus the some of their loads, Okay, and compare that way. That's how you would tell. So if you're utilizing that and you have again you have a fastening place motor operated utilization equipment, and the motor is larger than eight horsepower, and you have other loads as well, then you take that load at one hundred and twenty five percent and of some of the other loads together, right, and that may be

Speaker 2your largest load. And that's what you would use in your comparison of these non coincident loads. You with me, So this is giving you three ways to determine the loading. And I think I can break it down into maybe even even more of a you know, kind of a step by step process. Right. So if we're thinking about this, and we haven't even talked about one twenty dot fifty yet when it comes to motors, because that twenty five percent,

Speaker 2if everybody's thinking, if if I'm using the motor, uh, and I'm doing it at one hundred and twenty five percent, it's the largest motor and then the sum of the other loads then that twenty five percent that may be covered by referencing one twenty fifty may already be covered. But if I'm doing a heat versus AC, for example, and the heat is still larger than the AC, even if we did the AC at one hundred and twenty five percent plus some of the other loads, if the heat is still larger, then that AC value is gone.

Speaker 2Therefore that motor is gone. So then and only then in one five fifty, well I have to hunt for the next largest motor to comply with one twenty to fifty because the AC now is not in play anymore because in the scheme of the loads, the heat was larger. So that's what got utilized. Again, that's the cleanest example that we use for dwellings. It's just simple AC and heat. Right, So let me give you an example. I try to

Speaker 2give an example of maybe how this this may work. So let's see here. So let's say we have a calculated air conditioning combined load of seven five hundred VA and we have an electric heating load of ten thousand VA. Well, obviously, if these are truly non coincident loads, then the larger of the two is the heat at ten thousand. So

Speaker 2that means that the AC load is under this portion of the calculation, right, because it is. If it is truly a non coincident load, then we went with the larger of the two. So it makes sense, right because in a as far as load calculations go, Hell, if I size everything for the ten thousand VA, what do we care if that's not running, but the seventy five hundred air conditioning is running because it's less than ten Who cares? Now, granted, you're gonna size everything to the

Speaker 2air conditioning separate, just like you know the conductor sizing. You're gonna do that separate. We're talking load calculation right now. Okay, overall load calc Okay, not your brand circuit calculation, not your conductor sizing, not your overcurrent device. That's different. We're talking in a load calc here. Okay, So the heat is larger, so you omit the AC. So the compressor is no longer part of the feeder or service load calculation. It's just been removed from the equation. Now, that does

Speaker 2not remove us as we move further into the load calculation when it comes to one twenty dot fifty, because one twenty fifty is dealing with motors, right, or HVAC or air conditioning, right, So we have to still deal with that. So now under the twenty twenty six a EC one T fifty A and the reference motor rules and four to thirty dot twenty four four to thirty

Speaker 2dot twenty five four to thirty dot twenty six for the motors, that remains part of a calculation that's not gone yet. Okay, So if I have omitted the AC compressor, it's part of the AC versus the heat in a situation where they are truly non coincident loads. Again, we're not talking a heat pump because that wouldn't be a non coincident load. There's a different count for that. Take nameplate values for that. Okay, We're talking where you may have a true non un coincidental load. Means that thermostatically

Speaker 2the AC can't come on with the heat if that's the case, or you could have baseboard heating. And if you have baseboard heating and you're going to be taking that, then you're going to be taking that baseboard heating at one hundred percent of its value. Right. So at the at the end of the day, we have to understand that the differences in the two and how we would calculate that because under the heating, if it's fixed electric space heating, then that would be one twenty fifty one and that is basically at one hundred percent of the

Speaker 2total connected load. Okay, all right, so we just need to understand that we all use the AC versus heat as an example when we're teaching this stuff. But remember this could this could be any situation where you have two separate loads that can be classified as non coincidental loads because they're not going to be simultaneously used at the same time for your calculation. But that does not remove our situation in one fifty. Okay, Now, let's assume

Speaker 2that in our situation, the heat was greater than the AC, so we emitted all the AC. Let's assume that those were non coincident loads for argument of sake. So therefore, since we've omitted the AC, when we get to one twenty fifty, now we still have to find the largest roommating motor. And let's assume we have a well pump at nineteen hundred and twenty VA. Let's assume we have a blower that blows the heating around at six hundred VA. And let's say we have a disposal, garbage disposal at

Speaker 2five hundred VA. Well, in this scenario, the next largest motor, true motor, would be the hell well pump, the well pump, and it's at nineteen hundred and twenty VA. Well, you do that, multiply that by twenty five percent, because we only want to get the twenty five percent. You say, well, why, because we're already accounting for the well pump in our normal appliance calculation. We're already accounting for it. So all we're trying to do is grab that additional twenty five

Speaker 2percent in order to meet the application. Now you say, well, wait a minute, how does that work. I'm like, because these are multiple motors. So remember what we said in four point thirty twenty four. It says take the largest motor at one hundred and twenty five percent and the sum of the other motors. So I've already taken the sum of the other motors. I've already figured in the well pump, I've already figured in the heating blower, I've already figured in the disposer. All of that up when we did the appliance calculations, So there are more than

Speaker 2one motor here. So that's why we take the largest motor at one hundred and twenty five percent and the sum of the other Well, you've already taken that well pump into the calculation, so we just need to grab that remaining twenty five percent. And I think that's the hardest part for folks to grab because it doesn't say grab that twenty five percent. All we're doing is trying to do with one twenty fifties asking us to do. That's it. That's all we're trying to do. So it's a mental gymnastics that you have to do and understand that.

Speaker 2So for example, that nineteen hundred and twenty VA for that well pump, that would give us an additional four hundred and EIGHTYVA to add to the equation. Right, so you're going to have one hundred percent all the other motors in there, and then you're going to have four hundred and eighty VA for that additional twenty five percent of that largest motor. Makes sense. Now, remember that that's okay that you could have other allowances in there for multiple appliances, Okay, four or more, you get a reduction that's fine, that's allowed as well. Okay, So don't confuse

Speaker 2the two. That's just a totally different step. And again we're talking standard method part three right now, okay, because that's typically where people get confused on this heat versus AC is a totally different process in the optional method chain. Okay, right, So under the twenty twenty six one of the things that was important is that the distinction needs to be made that the AC compressors one hundred and twenty five percent treatment under one twenty eleven A is used when

Speaker 2determining whether the cooling or the heating is the largest non coincidental load. And once the heating wins this battle, let's say, then the AC is omitted. That is where one twenty fifty is then applied to the motors that are remaining in play. You get what I'm saying. Those that are remaining in play, now get this. So the rule is, and if I had to do it step by step for you, I would say, first, calculate the AC properly under one twenty dot eleven A. Next, I

Speaker 2will compare the AC with the heat the one twenty dot six in other words, taking the larger of the two next, I would say, retain only the largest of those two loads, and then the last step apply one twenty fifty to the motor remaining in the structure that is now the next largest motor, because probably the air conditioning compressor was the largest motor, but since that was

Speaker 2removed because of the comparison of those non coincident loads, you got to go hunting for the next largest one. Okay, So yes, the next largest motor is going to receive that additional twenty five percent. It's getting it through one twenty fifty after the larger non coincident load has been already established. Okay, So yeah, hopefully that makes more sense on how that's you know, kind of flows, right, So

Speaker 2just remember when the heat wins the ac compressor is omitted, you still got to get that additional twenty five percent in order to comply with one twenty dot fifty, because it tells you if you got multiple motors, and that's what four thirty twenty four says, if you have multiple motors, take the largest one at one hundred and twenty five percent and the rest that their value. Sung Well, again, you've already taken those motors into probably your appliance calculation. So all you got to do is try to capture that largest motors additional twenty five percent that's missing in

Speaker 2order to comply with the two fifty excuse me, the one twenty dot fifty rule. It's not brain surgery, but everybody wants to find that that miraculous words that say take the additional twenty five percent. It's there. It's just you have to read between the lines in one twenty nine to fifty in order to get there. Okay, now this was literally the same concept in the twenty twenty three It was just confusing for folks the way was written. Lastly,

Speaker 2I will remind you if again I didn't make this clear in the twenty twenty six edition of the National Electrical Code, article two twenty is moving to one twenty. Technically, it's the all the same informations there. But this is a great example in one twenty dot six where it's now been broken up so that you can have the clear direction on what a non coincident load is and then it directs you to how to calculate it. Now, for me, I would have liked to see one twenty

Speaker 2dot one twenty dot eleven a broken down into items, the first one with the motor only, second one with the AC okay or hermatic refrigerant motor type of thing that's dealing with four forty and then see, I would it would have been nice to have it broken down like that, But you know what, I can't blame anybody but myself because I did not submit it that way. It's kind of fairly new for us in the code to start breaking things out and itemize format. Usually a bunch of people submit these things and it usually gets

Speaker 2broken out, and but this one didn't. And I don't know that it's necessary because the periods end each sentence make it very clear how this is stacking the structure. But at the end of the day, I'm sure that you know, somebody will complain about that structure and then it'll have to break it down even more. But that's that's hopefully that explains it to everybody. I would not make this more difficult than it really needs to be. Moving forward, take your heat if it's if you're talking

Speaker 2heat versus AC, take your heat at one hundred percent plus any of the other associated loads right turn around, and then take your AC if the air compressor is the largest motor, then take it at one hundred and twenty five percent plus some of all the other loads that are associated with it, maybe a heat pump, I mean not a heat pump, excuse me, a air handler, condenser, fan, whatever, and then compare that to the heat. If these are truly non coincident loads. Now here's the interesting thing. What

Speaker 2if the AC does is greater than the heat depending on where you're at in the country and whether or not you have heat strips or not. If you're in a warmer climate like Florida or somewhere like that, then you'd go with the AC. Well, if you did the AC loads at one hundred and twenty five percent for the air compressor, then guess what you do not have to go searching for the next largest motor in one twenty dot fifty because you've already accomplished that by taking it at one hundred and twenty five percent and it won. It was larger than the heat. So not only do

Speaker 2you take that value for the non coincident load value, but you also are using that value. You've already accounted for that additional twenty five percent under one twenty doin fifty as well. Okay, so you're good to go, right. So that's just kind of one of those things things that it depends on, you know, what situation you're in, which wins and those type of things. So hopefully that clears it up a little bit for you. Of course, if you have any questions, as always, you know, you

Speaker 2can leave comments, you can send us an email, you can go to let's ask Paul, which is available still. You can go through our website fastracksystem dot com and you'll see in the navigation under info tab you'll see where it says let's ask Paul. Click on. It doesn't cost you anything. Just fill in the information and send it to us. If it's about a podcast, and maybe give the episode or give a brief summary of what your questions about, and I'll be glad to answer it. Don't make me do a whole lot of work going back, because I do so many that it's really I can't

Speaker 2even remember what's in half the episodes I do. So you know, kind of feed me a little bit of your question and I'm more than happy to answer it for you. If I confuse you, I apologize. I do the best I can. But that's how I understand it. That's how I interpret it, and you may interpret it differently, but that's it. Folks. Well, next time, stay safe, God bless them. We'll catch you on another episode of Mastering the neceed till then be safe.

Speaker 1Thanks for tuning into another electrifying episode of the Master of the ANEC podcast. We hope you're feeling more powered up and ready to tackle the electrical world with the knowledge and confidence you need to succeed. Remember, in the electrical trade, knowledge is power, and we're here to make sure you stay plugged into the latest insights.

Speaker 2Tips and code updates.

Speaker 1If you enjoy today's episode, don't forget to subscribe, leave us a review, and share the podcast with your fellow electricians and industry pros. Until next time, keep your tools sharp, your circuits clear, and you're my focus because here at the Master of the ANEC podcast, we're all about sparking your success. Stay safe, stay smarked, and keep mastering the trade. From all of us here at Electrical Code Academy, thank you for all your support, and we will see you

Speaker 1on the next amazing Master then EC podcast episode.

Speaker 2MHM

Open the transcript file

Hosts and Guests

Nobody is credited on this episode yet.

Credit the people on this episode

Be the first to rate this episode

More episodes

All episodes
  1. NiteNerds™ — The Future of Permanent Outdoor & Landscape Lighting Is Here!

    Nov 12, 202631 minAudio

    NiteNerds™ - The Future of Permanent Outdoor & Landscape Lighting Is Here! What if your home could look absolutely stunning every night of the year - with the touch of a button? Welcome to the world of NiteNerds™, where...

    Credit the people on this episode

  2. MASTER THE NEC PODCAST | E81 | Electrical Code Knowledge and 2026 NEC Updates PT 3

    Oct 18, 202655 minAudio

    ⚡ MASTER THE NEC PODCAST 🎙️ Hosted by Paul Abernathy Master Electrician | National Electrical Code Expert | Electrical Educator ⏱️ Episode Length: 55 Minutes ⚡ ABOUT THIS EPISODEWelcome to Episode 81 of Master The NEC,...

    Credit the people on this episode

  3. MASTER THE NEC PODCAST | E80 | Electrical Code Knowledge and 2026 NEC Updates PT 2

    Oct 18, 20261 hr 23 minAudio

    ⚡ MASTER THE NEC PODCAST 🎙️ Hosted by Paul Abernathy Master Electrician | NEC Code Expert | Electrical Educator⏱️ Episode Length: 1 Hour, 23 Minutes ⚡ ABOUT THIS EPISODEWelcome to Episode 80 of Master The NEC, where...

    Credit the people on this episode

  4. MASTER THE NEC PODCAST | E79 | Electrical Code Knowledge and 2026 NEC Updates PT 1

    Oct 18, 20261 hr 4 minAudio

    ⚡ MASTER THE NEC PODCAST 🎙️ Hosted by Paul Abernathy Master Electrician | NEC Code Expert | Electrical Educator ⚡ ABOUT THIS EPISODEWelcome to another episode of Master The NEC, the podcast dedicated to helping...

    Credit the people on this episode

  5. What The HECK? Do you have a 2026 National Electrical Code Course?

    Oct 3, 202641 minAudio

    The National Electrical Code is a minimum standard - but what does that actually mean?In this episode of Master The NEC, Paul Abernathy takes a deeper look at one of the most misunderstood concepts in the electrical...

    Credit the people on this episode