ELECTRIFY™ | Electrician Podcast

ELECTRIFY™ | Electrician Podcast artwork

MASTER THE NEC PODCAST | E80 | Electrical Code Knowledge and 2026 NEC Updates PT 2

Oct 18, 20261 hr 23 minAudio
ShareXLinkedInFacebookWhatsAppEmail

⚡ MASTER THE NEC PODCAST 🎙️ Hosted by Paul Abernathy Master Electrician | NEC Code Expert | Electrical Educator⏱️ Episode Length: 1 Hour, 23 Minutes ⚡ ABOUT THIS EPISODEWelcome to Episode 80 of Master The NEC, where electrical code education meets real-world industry experience! The National Electrical Code (NEC) is more than a collection of rules and regulations. It's a comprehensive electrical safety standard that requires technical understanding, critical thinking, and the ability to properly interpret and apply its requirements. Hosted by nationally recognized electrical code expert Paul Abernathy, Master The NEC is dedicated to helping electrical professionals move beyond simply memorizing Code sections and develop a deeper understanding of the principles behind electrical safety and Code compliance. With decades of practical electrical experience and firsthand involvement in the NEC development process, Paul brings a unique perspective to electrical code education. 🔍 WHY MASTERING THE NEC MATTERSUnderstanding the National Electrical Code requires more than knowing where to find an answer. True Code proficiency comes from understanding the intent of the requirements, recognizing how different sections interact, and applying those requirements correctly in actual electrical installations. Master The NEC encourages electrical professionals to: ✅ Think Beyond Memorization - Develop a deeper understanding of NEC requirements and their technical foundations. ✅ Improve Code Interpretation - Learn to approach electrical Code questions with greater confidence and accuracy. ✅ Connect Theory to Practice - Understand the relationship between written Code requirements and real-world electrical installations. ✅ Strengthen Technical Knowledge - Continue developing the skills necessary to navigate an increasingly complex electrical industry. ✅ Stay Focused on Electrical Safety - Recognize why proper Code application matters to the protection of people and property. 🎯 WHO SHOULD LISTEN?Master The NEC is designed for electrical professionals at every stage of their careers, including: ⚡ Apprentice and Journeyman Electricians ⚡ Master Electricians and Electrical Contractors ⚡ Electrical Inspectors and Plans Examiners ⚡ Electrical Engineers and Designers ⚡ Electrical Instructors and Educators ⚡ Individuals Preparing for Electrical Licensing ExaminationsWhether you're new to the electrical trade or have decades of experience, there's always more to learn when it comes to the National Electrical Code. 🚀 TAKE YOUR ELECTRICAL KNOWLEDGE TO THE NEXT LEVELWant to go beyond the podcast and develop a stronger understanding of the NEC?Explore comprehensive electrical training, NEC educational programs, and electrician licensing examination preparation through the Fast Trax® System. Our programs are designed to help electrical professionals build real Code knowledge - not just memorize answers. 🌐 VISIT: https://FastTraxSystem.com 🎙️ ABOUT MASTER THE NECMaster The NEC is presented by Electrical Code Academy, Inc., a leader in professional electrical code education and electrician training. Hosted by Paul Abernathy, the podcast is dedicated to promoting technical accuracy, electrical safety, and a greater understanding of the National Electrical Code. ⚡ KNOW THE CODE. UNDERSTAND THE CODE. MASTER THE NEC.Keep Learning. Keep Growing. Never Stop Mastering the NEC! #MasterTheNEC #NationalElectricalCode #NEC2026 #ElectricalTraining #ElectricianTraining #ElectricalCode #ElectricalSafety #MasterElectrician #ElectricalEducation #FastTraxSystem #ElectricalCodeAcademy #ElectricianExamPrep Become a supporter of this podcast: https://www.spreaker.com/podcast/electrify-electrician-podcast--4131858/support.

Audio and video play straight from the show's own hosting. PodSubs stores and serves no media.

Transcript

From the show. Tap a time to play from there.

Speaker 1Welcome to the Master of the NEC podcast, the ultimate destination for anyone passionate about the electrical trade. Whether you're a seasoned electrician, an eager apprentice, or just someone who wants to dive deep into the world of electrical work, you've come to the right place. Join your host, Paul Abernathy, a true authority in the industry with over 38 years of trade experience as he electrifies your mind with in-depth discussions, expert tips, and valuable insights that will keep you ahead of the curve. Each episode, Paul will illuminate the complexities

Speaker 1of the trade, decode the National Electrical Code, and share the latest industry trends, all while empowering you to take your electrical career to the next level. So, gear up, plug in, and get ready to supercharge your knowledge, because with the Master the NEC Podcast, the power is in your hands. Now get ready, here is your host, Paul Abernathy.

Speaker 1What up, what up, what up, everybody?

Speaker 2Welcome to another episode of Master the NEC Podcast, where we talk about just about anything that has to do with the electrical industry. And we kind of focus on the National Electrical Code, probably primarily. But, you know, I'll talk about just about anything, and chances are I'll ramble into anything. So... Thanks for joining me. If you've never listened to my podcast before, we have over a thousand episodes that date back many years. All of the topics are pretty much still relevant, and you can just go searching through it. But if you want to find all

Speaker 2of our episodes, all you got to do is go to any search engine and type Master the NEC Podcast, and you are easily going to be able to find a list on various listening platforms, Spotify, Spreaker, Deezer, Apple Podcasts, Google Podcasts. Maybe you already have one that you prefer. It doesn't matter. It's available on all of those. We're in syndication. And I've been doing podcasts longer than anybody else in the industry. And if you think I haven't, I will challenge you because I can pull back episodes

Speaker 2dating way back when I used to upload them via AOL, you know, that old dial-up. So been doing this for decades. And so I'm glad you stumbled on us. Hopefully you share with other people, let people know about it. We uniquely get about 300,000 downloads across the entire platform. And that's all of our podcasts that simulcast it, whether it's Electrify, Let's Ask Paul, The Grounding and Bonding. or even this Master the NEC podcast, or even on our other platforms, YouTube and FastTracksTube. So we aggregately collect the data and

Speaker 2we consistently get over 300,000 unique downloads a month. So again, we thank all of you for that. Absolutely. A bunch of All right, a bunch more of that shallow clap. There you go. So anyway, thanks for joining me. Now, this episode is, we're going to be picking up as a part two to a previous episode I did with the 2026 Changes part one. And so that episode, go back and listen to that episode. I can't remember the number.

Speaker 2I'm thinking it was episode 79 of it, but I don't, you know, you got to look at the title. But, and you can look at the date because I believe it was dated October 18th. So of 2026. So you can go search it that way. I don't do a real good job of indexing these things. And again, I have people that complain about that. But you know what? It is what it is. So, you know, if you find some value in it, appreciate you subscribing and sharing it with other people. All right. And if you don't like it, piss off and move on. You don't have

Speaker 2to listen. That's your prerogative, right? Not here to cater to you unless you enjoy it. All right. So we're going to get into some more changes and some detailed response. And I'm kind of going to backtrack a little bit from my part one. I'm going to drop back because I think we're probably missing some significant changes. So, you know, that's it's something that we want to, you know, make sure we do cover. All right, so we're kind of going to go back because these are important things that

Speaker 2are very relevant to your day-to-day. And that is there's a change that took place in Section 110.3b. And the actual relationship between the manufacturer installation instructions and the NEC requirements were kind of clarified. So electrical equipment, in general, it must comply with the applicable NEC, I love that word, applicable, or applicable, applicable NEC requirements and the manufacturer's applicable installation

Speaker 2and use instructions. Now, a manufacturer, now this is important, many people need to understand. A manufacturer cannot establish an installation method that eliminates the mandatory NEC safety requirements. Remember that thing I always say about the minimum? The NEC is the minimum. And this goes to prove that for all of my haters out there that say, well, the NEC is not a minimum. I hate the minimum. I always do more than the minimum. That's you. You do you, boo. But the reality is it is a minimum standard. Anything below that threshold is a violation. and a safety hazard.

Speaker 2Anything above it is just going above and beyond the minimum. And you're perfectly okay to do that as long as you charge for it or your customer's aware of that. And you don't try to force it on somebody if they don't want it. But again, maybe it's how you do things. That's fine. I'm not here and here and there. I'm not really here to say anything otherwise than that. But at the end of the day, the code is the bare minimum. And this went a long way. For example, suppose a manufacturer's instructions specifically specify an arrangement that is

Speaker 2inconsistent with what the mandatory GFCI requirements are in 210.8. So an installer cannot ignore the NEC merely because the instructions describe that arrangement. This has become a very hot topic issue with GFCIs and EV systems and and manufacturers putting out statements about not to use this GFCI device. And at the end of the day, the NEC is the minimum safety standard that if adopted in that jurisdiction,

Speaker 2it's put out by that state, that's what you follow. So if a manufacturer tells you to go below the minimum, that's a problem, okay? So the installer must select the equipment and an installation method that complies with both the applicable requirements. They have to meet the information from the manufacturer, but they also have to understand that the National Electrical Code is a minimum safety standard that they cannot go below, okay? Now, the revised portion of this also recognizes that instructions can

Speaker 2be provided electronically, including through a QR code or even on manufacturers' websites. So, The manufacturer also made it clear that they can give you direction. It doesn't have to be constantly published documents that may need to be changed rapidly. It understands that the QR code will send you to a location which can always be relevant. And so a lot of AHJs didn't like that. They were like, well, I want the paper. I want the paper. Well, reality, this kind of lays out and says, look, chill out.

Speaker 2Here's a QR code on the equipment. I don't necessarily have the literature right here in my hand, but if you scan that QR code, and I think some jurisdiction will say, nope, I don't want to do that. You scan it, you print it out, and you give it to me. I'm like, dude, get into the modern times, whatnot. You got a phone, scan it yourself. But anyway, it is what it is. So listing and labeling do not give a manufacturer authority to override the NEC. Okay, that is important. They can establish additional conditions governing the proper

Speaker 2installation and use of their equipment, but they can't give you things that would fall below, again, the minimum standard. And I bring that stuff up all the time. And I get my share of haters who will say, the code's not the minimum. It's not the minimum. Dude, shut up. It is the minimum. And you ask yourself this, If I install something and it's not compliant with the NEC, am I going to get rejected? Shit, yeah, you are. So I didn't meet the minimum acceptance threshold. Stop arguing

Speaker 2with me on this shit, folks. People argue with me about stuff, then they just want to pound their chest. You know, Code Panel 5 got it wrong, in my opinion, with the equipment ground and conductor back in the 2026. NFPA just put out an article or a study that basically says I was right, that it's so confusing that it needs to be clarified, and there was no data that was presented. Stop arguing with me. This is what I do for a living. I wouldn't bring it up if it wasn't important. Dude, relax. I'm bringing things up

Speaker 2because they're important. Whether you agree with them or not, you need to absorb it and understand it. Okay, next change that we'll talk about is there was a change in section 110.26. Now, what has changed? For those that understand it, that's the working space and equipment door clearance has some clarification that was added in the 2026. Now, the requirements involved safe access, egress, Equipment doors and working space measurements were clarified. So the detailed explanation is the

Speaker 2change addresses how equipment doors affect required access and egress. So a common dispute occurs, for example, when a switchgear's doors are open and they can be opened up to 120 degrees. But in that case, personnel may not work with them positioned at 90 degrees. right? So the revised provisions clarify how the potential obstruction must be eliminated, okay,

Speaker 2and how it must be evaluated. Rather than allowing a designer to assume, whoever the electrical designer is, to assume the doors will always remain fully open, So I guess this is the kind of thing when you look at the code, dude, you're going to have to paint me a mental picture. You're going to have to give me an example, okay? So let me paint you a mental picture here for this change. So I have two electrical equipment enclosures face one another, and let's say it's a relatively narrow electrical room. So right across from each other,

Speaker 2kind of like a galley style, right? You know, you're facing one of them and the one's to your back, okay?

Speaker 1Okay.

Speaker 2Now, even if the doors can open completely against their respective enclosures, the designer must evaluate the applicable access and egress condition when the doors are open to 90 degrees. Okay, so open 90 degrees straight out from the equipment. They must evaluate if the case is, if it's open like this and somebody's trapped in there, how would they be able to get out of this scenario? So the required working space is not simply an architectural dimension measured with

Speaker 2every enclosure that's closed. They have to think about this stuff now, and it's forcing them, the designer, to think about it when they're open. So accessibility during actual servicing and maintenance is essential design consideration. Not just somebody saying, well, look, I can open something all the way to 180 degrees and it's not really blocking my... No, it has to say, you know, people say that the door can be open to 180, but at the end of the day, it

Speaker 2might not be in a situation where you can adequately work in it at 180 that it has to be positioned at 90, which is straight out perpendicular. So The design professional has to take this into consideration and it makes common sense. So it's going to make those galley style and you might have the working space, but we now have to look and say, okay, you've got the working space. Now we have to understand whether or not doors are open. Is that going to trap somebody in? And that's the thing that the design professional has to

Speaker 2look at now. Not so much you, the electrical guy, unless you're doing your design and a lot of master electricians can do the design, right? So, you know, it's kind of one of those things that, you know, you always got to determine what level of role are you involved in it. But this is mainly geared for the design professional. That one, that one is. The next one is probably one that's very popular. You've heard us talk about this on other shows that we've done. And this is the change when it came to the general lighting and general use receptacle during a load calculations in Article 120. Like,

Speaker 2so I said in Part 1 that calculations move from 220 to 120. So, In the 2026, 120.41, for example, it says in 120.82, it says what's changed here when it comes to dwelling unit general lighting load reduction. So general lighting and general use receptacle load calculation was reduced from 3 VA per square foot to 2 VA per square foot. Now, historically, 3 VA per square foot assumptions was developed when residential lighting loads were substantially higher. incandescent

Speaker 2lamps and things like that. Now we have LEDs, the energy codes, all those type of things are enforced and jurisdictions are really heavily enforcing energy codes and the ability for the lights to have photo cells and shut off and, you know, managing that power. So the widespread LED uses and changes in the various equipments to meet the energy reduction codes and things like that are dramatically changing how we calculate the loads in a dwelling. For example, under the 2023, when it was three VA per square foot,

Speaker 2if I had a 2,500 square foot dwelling, then that was 2,500 times 3 VA, that's 7,500 VA. That's what would contribute to the general lighting and general use receptacle, okay? Now, under the 2026, that gets dropped down because now it's 2 VA, so that's 2,500 times 2, so that's 5,000. So that's 2,500 VA that is dropped right away, okay? So 2,500 VA... is, you know, dropped. And basically, that's

Speaker 2huge when it comes to, you know, a load calculation, depending on the size of the dwelling. Now, keep in mind that it's about a 33% drop reduction in the general lighting load. So you might think, yeah, it's not a big deal. But 33% of the general lighting and general use consumption because of the energy codes and because of more efficient LED lighting and things like that, That is huge. That's 33% reduction over the 2023's allowance. Now,

Speaker 2this change affects the general lighting portion of the calculation. It does not eliminate other requirements. We still got to add in the minimum of two small appliances at $ 1, 500. We still have the laundry circuits at $ 1, 500. You still have to have those things added in there. And of course, you do get to apply when it's a dwelling. You do get applied the demands. First $ 3, 000 at 100%, remaining $ 117, 000 at 35%, and then above that at 20%. You do have your still, under the standard method, you do have

Speaker 2some reduction allowances, right? That didn't change. But the VA per square foot did change. Now, by the way, interesting note, is that for branch circuit, determining the number of branch circuits you need based on whatever your load is, that's still 3 VA. So don't confuse the two. If you're trying to determine how many branch circuits I need for that, then you would use 3 VA. If you are doing it for the load calculation, you would do the 2 VA.

Speaker 2So again, if you were doing it to 2,500 and you were doing it for branch circuits to determine the number of branch circuits, that's totally different. You would still be using the original 7,500 value in order to break it down and find out how many branch circuits you would need, general use branch circuits. Don't confuse that with the load calculation in 120. That one is, we're specifically talking about when you're doing a load calculation. That's when you're going to use the two. Otherwise, you're just determining

Speaker 2the number of brand circuits, three VAs used. Again, I hate to be redundant, but you know how I teach it. And I want to, because that is something that people will get confused. That is why I tell you this over and over again, because I want you to understand three VA didn't go away. It's just not being used for the low calc. Makes sense? Next change we have to think about is the optional dwelling calculations, okay, in 120.82b. So what has changed? Well, under the optional dwelling unit calculation,

Speaker 2and by the way, On an exam, you're probably going to always be using the standard method unless they state otherwise. Same as you're going to be using copper unless they state otherwise. And you're not going to use exceptions unless they allow for exceptions. Kind of tips to remember when you're taking an exam. But at the end of the day, most people are going to probably use in the real world, we're going to always use the optional methods because it's going to result in a smaller service or a smaller feeder application. Right. And the code permits it. So why

Speaker 2not use it? Right. I mean, it's there. It's not like it's an it's not an exception. It's it's a method that you can use. So most people. So that's real world versus kind of exam. And people say, well, why the hell do you teach the standard what we call the standard method? Why would you even teach that if you're not going to use it in the field? Well, because you need to do the standard method to be able to size neutral conductors. So you've got to know how to do it. Plus, again, there are certain applications where you have to use the standard method because there's

Speaker 2not an optional option. Is that right to say it that way? An optional option. So, yeah. So you got to know how to do both of them. And I see all the time on social media when I'll post various questions and I'm posting them for a reason because I keep data. So sometimes you wonder why I post something on TikTok or why I might post something on Instagram. And it seems like a basic question. Um, And people say, Paul, duh, that's a basic question. Why would you post it? Because I'm taking data. We're constantly absorbing data here. And what

Speaker 2we're seeing is that the vast majority of people are getting things wrong. So while you may be the smartest man or woman in the room and think, I don't need this question. This is stupid. That's a basic question. Dude, you got to remember that there are thousands of people out there that are learning and they're not all as smart as you. Okay. And so, and I say that facetiously, but at the end of the day, we have to take data for everybody.

Speaker 1Okay.

Speaker 2So now the change is under the optional method, the unit calculation method. the dwelling unit calculation, the first 8 kVA or 8,000 VA, okay, or 8,000 watts if you want, or 8 kilowatts, anyway, of applicable general load is calculated at 100% rather than the first 10 kVA. So now it's the first 8 at 100% and then the remaining after that is at 40%. So rather than starting again,

Speaker 2another energy code kind of reduction here, instead of having to go 100% all the way to 10 kVA, I'm able to do the 100% at eight KVA, 8,000 versus 10,000. And then anything over that, I can take at 40%, right? So the adjustments reducing the calculated demand under the optional method, okay? So let me give you kind of a, let me paint you that mental picture and maybe how this would work out in real life. So let's do an illustration of,

Speaker 2let's say a 20 KVA of applicable general load. So let's just assume this is what we've got. We've looked everything, we've added everything up. We have 20 KVA, right? So under the 2023 method, obviously the first 10,000 at 100%. So that's 10,000, right? And then the remaining load would be 4,000, right? Because you take the 10 away and then you got the 10 remaining over the 10 and you're applying 40% to that. So that's 4,000. So the calculated demand is 14,000 VA, right? So that is... what

Speaker 2we'd be utilizing for our load calculation under the optional method, under the 2023 edition of the NEC. Now, under the 2026, we're doing the first 8,000 at 100%, so that's 8,000 VA, which, by the way, to avoid confusion for people, VA is what we like to get to when we're resolving everything for a calculation, okay? We're trying to resolve and get to VA, okay? So when we say 10kVA, that's 10,000 VA.

Speaker 2When we say 10 KW, that's 10,000 watts. Or we say 10,000 watts, we'll just say 10,000 W watts overall. So just be in mind that the K mean 1,000. And so put ahead of KVA, it's just 10,000 VA. Or you can write it out as 10,000 VA. But in most calculations, we're trying to resolve everything into VA.

Speaker 2So get into that practice of trying to resolve it and understand that they're used in the NEC synonymously. Okay, so 8kW is the same as 8,000 watts. And so when it comes to 10kVA, it's the same as 10,000VA. It's just kind of get into that mentality. All right, under the 2026, the first 8,000 is at 100%, and the remaining is at 40%. So that would be 4,800VA. So together, that's 12,800VA. Okay, so the reduction in this

Speaker 2example is 1200 VA. Okay, so, you know, you may not seem significant, but, you know, it does. And just think about how you would apply this and it can add up pretty quickly, but that is a reduction. And it's basically the same kind of mentality is why we reduced it in the standard method, why we reduced the VA per square foot, you know, kind of scenario, kind of the same understanding, if you will. Now, contractors need to distinguish between a reduction in the calculated demand and

Speaker 2a reduction in the required circuit ampacity. Those two things are not synonymous, okay? So we have to understand the difference between you're doing a low calculation and you're actually determining the number of circuits that I need, things like that. So we want to make sure, again, don't confuse the two. And fall into not understanding the difference between doing a actual load calculation versus maybe determining the required numbers of

Speaker 2branch circuits and whatnot like that. Okay. The next thing is, let's talk a little bit. This one is 120.82D. And this is EV charging loads have been addressed in the optional dwelling units. Now, for the longest time, it was under the standard method. It was there, 7200 or the nameplate, whichever is higher. Now, it kind of left us, you know, kind of left hanging a little bit in the optional method. Now, I always said, if it's a load, it's a load.

Speaker 2You got to account for it. It's a load, right? But in here we have the ability to do that. And so the EV supply equipment loads receive explicit treatment under the dwelling optional calculation method. So for the 2026 provisions require that the applicable EVSE loads to be included at 100%. rather than having the optional general load demand factor applied to it. For example, if an EVSE rated at 48 amps on a 240 volt circuit represents 11,520

Speaker 2VA of charging load. The optional calculation cannot simply treat this equipment as another general household load subject to that 40% demand factor, okay? It's taking it at 100% and adding it to the calculation, not adding it in to that where you had the first 8,000 at 100% and then the remainder at 40%. Now, properly configured power control systems, which we talked about in part one, there's expansion. We

Speaker 2might not have talked about it, but you do have allowances now up in 725, 724, 725, for these configured power control systems, and it may provide an alternate load management approach when applying the provisions are satisfied in order to keep the loads from exceeding a certain value. So that may be applicable. So the code recognizes the distinction between diversified loads in a household and sustained electric vehicle

Speaker 2charging demand. And it basically is just saying, look, we're going to tell you how to account for these. You're not going to be lumping everything in and do the first 8,000 at 100%, and then, ooh, that EV falls under the remainder at 40%. No. It is taken at full value, and you're going to add that in addition to whatever you're calculating. Now, I would have done that before anyway, but here it just kind of adds a little bit more clarity to that. Next, we'll look at is,

Speaker 2we already covered 210.8F in a previous, and that's outdoor outlet GFCI protection thresholds was moved from 50 to 60 amps. Then again, it brings in more outdoor equipment that falls within the scope of this requirement. Even larger HVA systems, again, that September 1st, 2026 allowance exception is passed. So, you know, the manufacturers have to come up with devices that can handle that high frequency or special purpose GFCIs that can

Speaker 2not trip. And you remember, like I said in part one, this really came from issues in Texas, which started the thing because a lot of those mini splits were tripping breakers and it gets hot in Texas, as you know. And again, it's a balance of life safety and a balance of life and, and people were overheating and dying because the, the air conditioning wouldn't, wouldn't stay on. So again, having to address that, um, is, is something, uh, that

Speaker 2had to take place. Okay. So anyway, still gives you the allowance to do GFCI protection, class a devices, yada, yada, but it expands that a little bit, you know, now. Okay. So, uh, I guess a practical example was an outdoor 60-amp outlet, hardwired, okay? Again, understanding the definition of outlet. We're not just talking about a receptacle. That's a device, okay? Hardwired is an outlet. It's a point in the system where it takes power from the system, and it's going to do that typically at the disconnect or whatnot. All right, so, and again,

Speaker 2for those that want to argue that, I say that is why you need to go back and read definitions and understand what outlet means. Just because we slangly, is that a word too, slangly? Just because we call them when we're walking around a house is going to add an outlet here. I'm going to add an outlet here. Yeah, the box that you're putting the device in is an outlet box. And it's a point in the system where you're going to be taking power from the system. So the bigger picture is it's an outlet. but it's really a receptacle device that's mounted in an outlet box. You

Speaker 2get me? But there's people that still don't get that. So anyway, so I guess with that said, as we're seeing the rapid introduction of high frequency leakage current characteristic devices that are basically high frequency GFCI technology that I believe that You know, I know that Eaton says that they have, and they're just incorporating that into their circuit breakers already without having something separate. I believe, you know,

Speaker 2I could be wrong. It's not like I'm never wrong. It just happens to be a bit of a rarity. You know, I can hear the haters now. But at the end of the day, I can't say the same thing for Schneider. I can't say the same thing for Siemens. I can't really speak for the other. But I do believe Eaton is doing this and incorporating this high frequency deal. But again, don't hold me to that. Hopefully they are, because again, this is a big issue because the expansion

Speaker 2of the NEC adding all these additional appliances to GFCI protection, and we just, you know, we're going to see things trip. And The terminology when it comes to nuisance tripping, it's different than tripping because it's really tripping. There is a nuisance tripping thing where it's frequency and it's just doing it over and over and over again to the point where somebody is going to circumvent the safety prospect of it. And that is a nuisance versus it's really tripping for a real reason. That's why you have to have an

Speaker 2electrician get in there and determine whether or not we're talking about a legit issue or is this a nuisance thing. But if we don't fix the problem, then people are going to bypass things. And that's not going to be the mission of what GFCI is trying to do. Right. So the high frequency leakage occurs and it creates compatibility problems without necessarily representing the same physiological hazard that we would see from a normal 60 hertz current system. And

Speaker 2the frequency fluctuation and changes can cause appliances to have a compatibility issue. And, you know, the development of a high-frequency compatible GFCI device is really intended to address these operation characteristics that hopefully the manufacturers have really addressed that. So in a practical sense, a GFCI device is evidence, okay, when it trips that that the device detected a condition without it operating within its physical operating characteristics. It does

Speaker 2not by itself establish the origin, frequency, or severity of the leakage current. That's what the electrician's for. And that's why it requires troubleshooting to do that. But we were seeing modern HVAC equipment causing problems, and that's what started the whole issue. Okay, and compatibility. And then, of course, things expanded in Article 422, which I'm on, Code Panel 17, and kind of correlating with 210.8 with Code Panel 2.

Speaker 2It became a mess. Who owns this? Who's responsible for this? Just a mess. So hopefully, maybe that's all cleared up. I don't hear the chatter as much. Certainly not about the GFCI. I still hear a fair amount of chatter when it comes to AFCIs. But not so much for the, the GFC has anymore. I'm assuming they've, they've worked this out. Right. All right, the next 2026 NEC reference is section 210.12E. Obviously, this is the most favorite topic of most people out there, right?

Speaker 2The AFCIs. Yes, you all love those AFCIs. They do save lives, okay? But they're not without their challenges and many things. But again, nothing's perfect and it's always evolving. And I think that they're good insurance to have and they're the necessary component. Now, I'm not a big fan of expanding things just to do it because, hey, we might as well do it because we want to add places to it. I'm not a big proponent of that.

Speaker 2But anyway, so additional flexibility is provided for installing AFCI protection when modifying or extending existing branch circuits. So The revised rule allows a branch circuit AFC device at the first receptacle or switch in a qualifying modification and extension application. Now this can simplify upgrades in existing buildings when replacing an old panel breaker with an AFCI circuit breaker is

Speaker 2really impractical because the equipment's older. Yet you're changing and modifying a circuit So the manufacturers had to come out with the device type that go in outlet boxes to be able to accommodate this. So this arrangement must still satisfy the branch circuit protection requirements. But they do give you options here. And this isn't new. This is just kind of clarifying and making it even easier to be able to make it applicable to those conditions where you

Speaker 2may not be. be able to find a compatible breaker that would go in a panel, maybe a legacy type panel, something that's a little older. Let's give it a practical example here. So the electrician is hired. It comes in. You're extending the bedroom brand circuit to accommodate additional circuits, well, additional receptacles and different outlets. Maybe it's lighting outlets or whatever. So you're expanding this existing circuit that may not have required AFCI protection at the time it was originally put in, but now it does because you're expanding it. You're modifying it.

Speaker 2You're extending it. Now, rather than the electrician assuming that, only a panel board type AFC device is acceptable. The electrician can evaluate whether the first device method complies with the revised provision. Okay, so this change gives them flexibility. It provides the installation flexibility. It doesn't eliminate the requirement for AFCI protection, right? It just expands it and allows a little more flexibility, and the manufacturers already had these devices.

Speaker 2So they're available in the circuit breaker type. They're available in the device type. They would go into a receptacle or switch box. So they do have the different options out there. So again, all this did was make sure that we reaffirmed flexibility is there. That's all it really was. No significant beyond, but the flexibility is there. All right, the next one. Probably not my favorite change because I believe this whole deal with these kitchen countertops and peninsulas

Speaker 2and all that. I think it's all crap, but I get it. Everybody's going to say, Paul, NFPA put out documents. It saves lives. I'm like, well, you know, own up, you know, tape your cords up, whatever, you know, just because people pull stuff off and pull stuff. I get it. I get it. I'm not, I'm not, God, how do I say it? I'm not, I don't have compassion for the fact that people got hurt. I'm just saying shit. People sell ladders and people fall off ladders all the damn time. Maybe you don't belong on a damn ladder.

Speaker 2You know, I'm just saying, right? I'm just saying. Anyway, so this change is prohibited locations were clarified when it comes to kitchen countertop receptacles. Under the 2026 NEC, section 110.52A5 and, excuse me, 210.52A5 and 210.52C4. Now, what exactly changed? The receptacles within 24 inches below the surface of certain dwelling unit kitchen countertops are prohibited under the revised provision. Now,

Speaker 2here was a weird thing. Under the 2023, you no longer could have, I mean, I'm just talking generally, the receptacle that's serving the island, let's say, or serving a peninsula, could not be below the countertop surface. You know, there's some exceptions that were in there or some allowances in there for built into the counter or built into the cabinet designed that way. I'm not talking about that. The general rule and everybody was arguing about is now I can have the receptacle on the side, not lower than 12 inches and not under any overhang that's more than

Speaker 2six inches, which has been there for a while. And we went from where you didn't have enough receptacles to then, based on pushing by IAEI and the electrical inspectors, we need more receptacles there. So then it expanded and went from a 12 by 24 measurement to a, based on the square footage measurement of the countertop, to add more. So we expanded, so they wanted more receptacles out there, to all of a sudden, out of nowhere, we don't want any receptacles anymore. Right? I mean, it's not required. Now,

Speaker 2you still had to take a circuit there and keep it in a junction box or have access to it, maybe an open floor or a raceway that's there to get circuits over there if necessary. But we couldn't put them below the countertop. They had to be above the countertop or in the countertop, but they couldn't extend more than 20 inches above, but they couldn't be below. Okay? That's the general synopsis of it. The problem is that sometimes... where this is that might be considered wall space or a wall divider. And people were putting a receptacle on

Speaker 2the actual underneath the counter. And it wasn't to serve the countertop, but it was actually jurisdictions would say, okay, I consider that wall space. And so by putting it there, It was totally different because it wasn't serving the countertop, but it was still in that space, and it is technically below the countertop. So the argument was, well, somebody's going to plug a damn cord in it, and we've got the same problem we've been trying to eliminate. Even though it may be facing a living room or some

Speaker 2other area, and it needed to be there because they considered that wall space a whole other argument there because there's a difference between wall space and a cabinet, but that's for a different podcast. So, The problem is when you put the receptacle in there to be compliant, theoretically, a cord could reach it from serving the countertop. And so how do we address that? So now they're saying, look, since a typical appliance that serves from a countertop is about two feet. It's a typical appliance, toaster oven, yada, yada, yada.

Speaker 2So the code says, okay, I understand that you have to have receptacles below the countertop that may be serving a wall space requirement in 210.52A for general. But now... we're going to say that's fine. We want you to have that, but it can't be within 24 inches of this surface of the kitchen countertop. So it puts it just down below that. The countertop, like nobody's going to go grab one of those little brown extension cords that they pick up at the checkout at Lowe's or Home Depot.

Speaker 2Nobody's going to do that. By the way, that's the reason we put more receptacles on an island back years ago because people were not having enough and they were running extension cords over it during holidays and get togethers in order to be able to do crock pots and shit like that. So I don't know that we solved anything here. I really don't. It's kind of one of those common sense things that, you know, we can do everything we can to try to protect ourself, but are we really, are we really protecting ourselves? Anyway, so there you go. So the change addresses the unintentional consequences that

Speaker 2were in the 2023 division, which you may still be under, which would allow that receptacle to be below the countertop. As long as it wasn't there as a purpose to serve the countertop, it still could be there because it was there because of wall spacing requirements, right? So as the code, I believe this is what they believe, is the underlying hazard is that a child or another person, maybe the elderly person, may pull the appliance cord extending over the countertop's edge, causing the appliance containing hot liquids and cooking materials to fall. That was always a case.

Speaker 2And I get it. But at some point, we got to remember what the NEC is really there for. You know, we can't protect people from themselves. Stupid is as stupid does. I'm just saying, you know, don't be flaming me in the comments. I'm just saying that I didn't, I'd rather have the receptacle at my island. I'm gonna be honest with you. I'd rather have it and I can get some tape if I'm gonna do it during a holiday and I've got little kids and I can tape it up or, you know, do something and tape it against

Speaker 2the counter or whatever so they can't grab it. I'm just saying, you know, you gotta take responsibility, okay? Enough of that soapbox. So practical application. Again, I like to paint that mental picture. If I'm installing a receptacle on the side of a kitchen island, six inches below the countertop, does not become simply a compliance simply because the receptacle is an optional one. It's there for some other requirement and it's not to serve the countertop. Still not going to, in the 2026, you could have, 2023, you could have

Speaker 2said that's not for the countertop. That's to serve the wall space requirements. And the height of the wall space requirement is as long as it's not higher than five feet, right? So you had an argument there. Who's going to win? So in this case now, they're saying, look, I'll let you have one, but you're going to have to put it down lower. You're going to have to put it so it's at least 24 inches away from the countertop, further down. And I think that's doable. I think with most countertop heights, that's not an issue. It still can be down 12 inches or whatnot up from the floor,

Speaker 2and it's going to look fine. But that allows you to have a receptacle there. And so that clarity was needed here. So this essentially, it's designed to distinguish receptacle intent to serve a countertop surface from other receptacles that may be permitted, not required, permitted elsewhere within a kitchen cabinetry or surrounding wall spaces. And it may indeed be required, for example, because of a wall space requirement. And so this kind of gets rid of that argument of the

Speaker 2two things.

Speaker 1Okay.

Speaker 2The next change we'll look at in this episode is 230.70A. And this is one in two families service disconnect required outdoors now. So you heard me talk about in part one of this series. If you haven't watched, listened to that, go back and listen to it. I talked about how we used to have the emergency disconnect in 230.85. That got pulled out. of 230.85 and it's kind of in 225 application, but it removed it. So it didn't get rid of it, but when it comes to service, it

Speaker 2makes it a moot point now because they're going to require for one and two family, they're going to require that the service disconnect be required to be outside. Okay. So what has changed in 230.78? Service disconnects and means and emergency disconnect requirements for one and two family, because you still do have emergency disconnect requirements. It's just under 225. Okay, you still have that. But they kind of consolidated everything. So the service disconnects must be generally located outdoors in

Speaker 2a readily accessible location. Thank God we have a definition of what readily accessible is. Either on the dwelling or within sight of the dwelling. And thank God we also have what's within sight, 50 feet. Okay, not more than 50 feet within sight. You know, if it's 50 feet, but it's around the corner and it's not within sight, then it's not within sight. Right? Thank God for definitions. Do you remember in part one I said it's so important to learn definitions? It really is. You know, we get paid to do things once. We don't get paid to do things twice. And stupid little mistakes can cost

Speaker 2you money. That type of thing. Um, so special situations involved, remote service equipment and feeder supply dwellings must be evaluated. And again, so you do have some allowances under 225.41. You do have some exceptions if you happen to already have a service disconnect within sites. So there's, there's other allowances there, but it's kind of been broken up now where more of your emergency disconnect stuff are found in 225 and your service requirements, uh, are going to require

Speaker 2that outside, uh, service disconnect now. So kind of tying all those things together and cleaning it up. So practical example, I guess, is a residence with the service equipment located inside an attached garage may require a different design when installing it under the 2026 edition. This is very common. Whereas I'd put an emergency disconnect outside in the 2023 and feed the service equipment could be inside. It's gonna be outside or inside nearest point of entry. But I

Speaker 2have my service disconnect, my emergency disconnect requirement and 230.85 in place under the 2023 edition. may require you to rethink this under the 2026. So rather than using a separate outdoor emergency disconnect arrangement that leaves the actual service disconnect indoors, maybe the design now has to comply with the fact that the revision is that the outdoor services disconnect requirements have to be now outdoors. So maybe that

Speaker 2unit outdoors is not just the emergency disconnect now, Maybe it has to have the ability to actually be the service disconnect. So then if that's the case, the panel that's inside now becomes a feeder and four wires set up, separation grounds and neutrals, yada, yada, yada. Hopefully you think about that in your design, that type of scenario. So This is an important distinction because between what a service

Speaker 2disconnect is and what merely an emergency means of disconnecting power is two distinctly different things. And the code now is addressing which you need, especially for the one and two family application. Okay. So again, it's costly for people that are designing this because, you know, I still get questions all the time about emergency disconnects. And once we started going down that path, now we're going to see a change. Where, again, at least with emergency disconnects, one of the options is to use an emergency disconnect that

Speaker 2was also service equipment rated so that you could get your get out of jail option. So now it just simplifies the concept. We want a service disconnect outside. We're not going to call it an emergency disconnect. We're going to call it a service disconnect. Now you've got a feeder going to a separate building. Now, depending on whether or not one of the exceptions applies, if it's a feeder, then you'll have an emergency disconnect there, okay? So you have different rules. And again, we won't get into the

Speaker 2two details of that. That's the nuances. You'd have to look in our 2026 fast track. We will get into those details. But here, we're just kind of telling you about these changes, okay? The next one is 230.70b. Since we're there with A, we might as well, you know, talk about B, right?

Speaker 1So.

Speaker 2B is 230.70. B says service and emergency disconnect markings were revised with more specific identification requirements. Okay. So for one and two family dwelling, the disconnecting closure is marked emergency disconnect. That's what it is. As prescribed appearance and placement. So it's telling us, okay. So if it is an emergency disconnect, okay. It needs to have white letters on red background. They have to be at least a half

Speaker 2inch high. Located on the front exterior of the enclosure and durable and permanently affixed. So we're not talking about ink jets, right? If you have an emergency disconnect. Okay, so this is applicable if you're using emergency disconnect. The biggest significant here is, I don't know how many times I got questions from folks saying, can I put it on the inside of the door? Can I put it inside where you open the flap? And this makes a distinction that it has to be on the exterior. You don't have to open it to see it. A lot

Speaker 2of these panel covers may have locks on them. Okay, still considered readily accessible. Trust me, that's not going to stop the fire and first responders. Um, but at the end of the day, um, being on the front of it says what it is blatantly right up. And of course, durable means no ink jets. It's gotta be something that's made to handle the environment. The, you know, so it's not going to smear, it's not going to warp. It's not going to fade, uh, those type of things. And it has to be permanently affixed, whether it's a, um,

Speaker 2a phenolic label, uh, one of those, it's probably going to be, you know, riveted on or one of those metal ones that stick. And it's like a 3M stuff that that stuff's never coming off. You know, however it's done permanently affixed means it's not something that is just, you know, cling type peel and wrap, you know, they can easily be pulled off. Okay. So for other occupancies, uh, not talking about the emergency disconnect. So for applicable other occupancies,

Speaker 2service disconnects means must be identified as service disconnects.

Speaker 1Okay.

Speaker 2And following the rules for the normal marking for those again, pretty similar, but the identifying label is no longer simply a matter of applying whatever wording happens to be available. Okay. Whatever the electrical contractor has a marker and it's, you know, now it's the revolve, the rules are, are important because the characteristics of the marking matter and the durability, the size, and all that kind of stuff does matter, okay? So that's important distinctions to be aware of. Again, it's not

Speaker 2something you have to commit to memory. It's just you know that if you're putting a service disconnect, you're putting an emergency disconnect, you have to make sure that your markings are compliant. So if you're doing those, then you know that I'm just going to be looking in 230.70b and that's going to give me the direction. Don't have to memorize it. No need for that. Just be aware that it's there. Now, that brought me to the feeder supply dwellings and emergency disconnect locations. So this is the feeder aspect of not the service disconnect, but now the feeder.

Speaker 2I told you in 225. So 225.31 and 225.41. So what's changed here is the disconnect provisions were revised to better coordinate the with the requirements for dwelling unit service disconnects. For example, not every residence receives its power directly from service conductors terminating at the dwelling. It could be remote structure, and it comes to that structure first, and then that's where the service disconnect, and then it goes over to the dwelling. I did this quite a few times on

Speaker 2some very expensive homes with very fancy windows. A rock around it and they like they said no we want to build the bushes and we want to put us You know put it so that the panel is over behind it on a wall And we didn't want it to be visible and we didn't want anything like that onto the house. Okay That's fine. You know, we do have some options back in the day. That's what we would do But let's see how that would play out today So some properties have service equipment at a remote structure, pedestal,

Speaker 2or other location where the feeder then supplies the home. Now, the revised NEC recognizes the need for an accessible emergency disconnect arrangement at or within sight of the dwelling. Now, this is intended to ensure, obviously, emergency responders can disconnect power without needing to reach remote equipment located elsewhere on the property. So the location of the utility service point, the location of the service disconnect and the location of the dwelling emergency disconnect are separate considerations and should not

Speaker 2be confused. They each have their own requirements. Okay. To be aware of. Now, the only big difference in the way we used to do it is we could go and put the service equipment behind a kind of a wall and And then, you know, still within sight, you could see the house, you could see the house itself, but it would go down and in and then come into the building and the equipment would be inside, right? And so the dynamics of this change, because now even

Speaker 2in that scenario, the emergency disconnect for the feeder to the building is still going to require the emergency disconnect to be located on the building outside. So You know, it's one of those things. Now, there is an exception for this. If your service equipment outside is within sight of the building and all that, and it's not further than 50 feet and it's within sight and you meet all the applicable provisions of what we just talked about when it comes to service equipment, then the difference is

Speaker 2that you're not going to have to have the additional emergency disconnect. But you have to look at each situation separately. And that was just something we did for really, really fancy homes who just did not want that on the side of the building. But again, there are many cases where that's not going to be something that we can do, that type of thing. So it just kind of throw that out there. The different configurations, I can't cover all of them in a podcast, but there was a time when we would put the service equipment remote and then go down and under and actually come up in the building,

Speaker 2you know, that type of thing. So anyway. There's different allowances, but that was what we used to do back in the day on those real expensive multi-million dollar homes. Okay, where else are we at here? Oh, let's see here. Okay, next one we'll look at is Article 200. And the grounded conductor identification has expanded. So what has actually changed in Article 200? The identification provisions were revised to permit an additional method of distinguishing a grounded conductor. So a

Speaker 2grounded conductor 6 AWG or smaller may be identified using a single colored stripe other than green when the applicable identification requirements are satisfied. Now, this can be useful in an installation with multiple systems or circuits where identifying which grounded conductor belongs with which specific set of ungrounded conductors is extremely important. So the grounded conductor and the equipment grounded conductor are not interchangeable. And hopefully people understand that

Speaker 2just because something's called grounded conductor, when you intentionally grounded system is not the same as an equipment grounding conductor. Okay, so they're not interchangeable. So expanding the grounded conductor identification options do not eliminate the distinction of the identification requirements for equipment grounding conductor. It just gives additional options for identifying the grounded conductor when it's six gauge and smaller. Okay. And in the past, it would be, you know, typically

Speaker 2it'd be white or gray, that type of thing. I mean, so it's just an expansion of the allowableness to identify smaller conductors. Now, for me, as a manufacturer of wiring cable, that was significant. Oh, hold on for a second, folks. I just dropped my freaking mic. For me, it's significant because when you make a product, and if you look at the size of six and smaller, it allowed for things like continuous white outer finish, continuous gray outer finish,

Speaker 2and then it went into three continuous white or gray stripes along conductor entire length, on other than green. So it didn't give any provision for a conductor with a continuous white or gray outer finish, but I need a single colored stripe other than green. So this allowed for what many people look at it and say, well, okay, I know it was kind of allowed before, kind of a little murky, but you have a lot of products

Speaker 2out there like a MC cable with multiple neutrals. And so how did that identification and many people cause, you know, cause confusion in that, which really shouldn't have been a big deal. But there's other different types of striping methods, whether it's the ring striping or continuous stripe on the side. There's other ways to do that and identify things. But for clarity, 2026 said, you know what? I get all that. We're going to let you have a conductor and it

Speaker 2may be continuous white or it may be continuous gray outer finish or But as long as it has a single colored stripe, other than green, and it doesn't have to say, it doesn't have to be the entire length, you know, when it says a single colored stripe, it could be different variations of striping, like ring striping, or it doesn't say a continuous stripe. It can be broken. Again, nuances, nuances. But it does allow that option, as long as it's not green, because we don't want to distinguish anything with green to confuse people. of anything to do with the

Speaker 2equipment grounding conductor. Two distinct different functions, right? Don't want to ever confuse the two, okay? Because people will get confused. They just will, right? Okay. Next change we're seeing is, for those out there, is the change is in 210.70C, okay? Now, this is dealing with automatic lighting controls, and it cannot be excessive means of operation in certain spaces. What does

Speaker 2that mean? So lighting control provisions were revised to prevent certain spaces from depending exclusively on automatic controls so that something did not go out automatically while we're working on the equipment. right? And create a problem, create a greater hazard. Now, in spaces such as attics, utility rooms, I'm just throwing them, you know, I'm brain farting it out. basement areas. A

Speaker 2person that's performing a maintenance could be left without illumination if the occupancy sensor, which is typically what they would use, if the occupancy sensor fails to detect any movement because you're maybe reaching into equipment and you're outside of the pickup range, let's say, or whatever of the sensor, that can leave a serious hazard for somebody that's maybe working around equipment And now all of a sudden they may be moving parts or something. Again, we're not going to say what people should do, what they should shut off.

Speaker 2And it's not our position to say that. That's whatever people do, they do. But this created a safety concern, right? So the revised provision addresses this hazard and by retaining appropriate manual control capabilities. So a practical example is an electrician is, say, working in an attic. should not be forced to wave their arms continuously to keep a motion-controlled lighting outlet energized, if that's what's being used in that space.

Speaker 2So energy efficiency and automatic lighting, they're beneficial, and we see that changing. People are wanting this, the automation, have things not, if somebody forgets to cut something off, I get it. but they cannot eliminate the safe operating functionality that's required for occupants or maintenance people in that specific space. So the code is just elaborating more on that and making it very clear that there is going to be a required manual process with some of these applications. And

Speaker 2really one of the significant elements of this is that, and I'm going to read this from the code, It's in all occupancies, so this is not dwelling specific. This is all occupancies, because again, this can take place obviously in all occupancies. It says, this is the 210.70C3 component. It says, control to automatic means shall not be permitted to control all illumination in attics, underfloor spaces, or utility rooms. Okay, and notice that it didn't say anything in here. And

Speaker 2I'm looking real quickly. You notice basements is in the charging statement of C. But in this one, it says control by automatic means shall not be permitted to control all illumination in attics, underfloor spaces or utility rooms unless a manual means to bypass the control is provided. Now, you would think, and again, maybe I'm just missing something here, you would think that they would add all of them in there. If that's in the charging statement, you would

Speaker 2think they would add basements in there, right? Because basements is in the first one. The point of control shall be at the entry that permits access to the attic or floor space, utility room, or basement. But then item three says, oh, these automatic controls apply to everything but not basements, right? So maybe that gets caught in the 2029 edition. I haven't looked, to be honest with you. But again, that seems like that's probably an oversight. Maybe

Speaker 2I'm missing something. I could be, but it seems like that was, the whole thing on 210.70c is talking about attics under floor spaces, things like that, that in basements, that you would include basements in that. There's a lot of commercial locations that do have basements. You go down into it, And they're going to do the automatic lighting. But, you know, that really should be an option in there to make sure that there's a manual override to that.

Speaker 2I'm just saying. Maybe I'm missing it. I could be missing it. Let's see here.

Speaker 1All right.

Speaker 2Surge protection expansion to additional occupancies. So in 2026, Article 215, 225, and 230, including Section 230.67. So what changed is, again, the rapid expansion of surge protection requirements were expanded to cover additional occupancies, including sleeping quarters in specific emergency service facilities and dormitories under applicable provisions. So All this is

Speaker 2saying is at the beginning, we had requirements for surge protection, for services, applications. We had even a feeder applications for this. That's why you've got 215, 225 in there as well. And you had the specific provision for surge protection under services and do 30.67. Well, all it's doing here is saying, you know what? We had those locations and of where this equipment is. And now we're expanding it to additional.

Speaker 2So emergency service facilities, you know, where first responders may be that we're expanding this out or even into dormitories under specific provisions. So this is just an expansion to where you may be now adding surge protective devices to locations where you never added it before. Okay. So that's kind of, deal with that. So, and what was the reason? So I guess the expansion is this when it comes

Speaker 2to surge protected devices, they work. Um, I have them on my panel. I have the, you know, what a kind of like a cascade effect. I have a one in my panel and then in, and I happen to have a, a QO panel and it's, uh, you know, I have one in there, plug in design and, misconception that it has to be close to the main. The manufacturer recommends it, but it's not a requirement, and it's going to work fine anywhere in the panel, so don't fall for that crap. But anyway, at the end of

Speaker 2the day, I also have protection at my computers downstream. So I have that redundancy type of cascading protection on my equipment. because I believe it happens, whether it's transient, whether it's switching stations, whether it's internal transients that are developed, because I have so much equipment in my dwelling that it could happen. So I'm adding that extra protection. But modern facilities, so this change is targeting the modern facilities that contain a lot of electronic life safety systems, very

Speaker 2important communication equipment, interconnected alarms, and other devices that are vulnerable to transient overvoltages. They just are. And by adding these locations where you're going to have emergency service facilities, you're going to have a lot of these type of extra non-ordinary systems that then we are worried about that transient overvoltage is taking effect on it and causing it to be a problem. So the expanded requirements recognize the importance of protecting those systems beyond traditional residential installations. So

Speaker 2now we're moving out further into other than dwelling applications. So surge protection requirements, you're no longer something designers should associate exclusively with residential is now expanding into all different types of occupancy classifications and specific service and feeder arrangements. All must be looked at and evaluated by the design professional or anybody that's doing modifications or upgrades and whatnot. You have specific rules for that as well. So you have to take all of those things into consideration, okay?

Speaker 2It's important that you do. All right, the next change that we have is one I do not like. And I talked about it in episode one. NFPA seems to agree with me. They recently came up with a report that says, wait a minute, there is a lot of confusion when it comes to the equipment ground and conductor sizing, especially when it comes to parallel applications and parallel raceways. But that brings me to nonetheless the change in 250.122H, which used to be 250.122F. Now, this provision for equipment

Speaker 2grounded conductors installed in parallel circuit conductors were reorganized and clarified. And I don't agree with the clarification, but the code is what it is, and I enforce what it is. Whether I disagree with it or not, it is what it is. So, historically, a wire-type equipment grounded conductor installed in each raceway containing parallel circuit conductors was sized using the overcurrent protected device that's protecting the overall circuit. So if I had parallel sets and it was a 1200 amp service, you didn't parallel out the equipment grounds. They

Speaker 2were full-sized in each raceway. And yes, those conductors could have been larger than the largest ungrounded conductor in that raceway because it's collectively, it was adding all of the legs that were in the multiple sets together to treat it as one circuit, right? And that was based on the 1200 amp overcurrent device, and that's why your equipment ground could be larger than any of the paralleled ungrounded conductors, because that fault current can't... You can't bank on it following all those available paths. It's going to follow wherever

Speaker 2the fault happens. It's not going to distribute evenly because of other impedance and reactance in the circuit. So our goal was to make sure the overcurrent device tripped. That was our goal.

Speaker 1So.

Speaker 2During the 2026 process, a couple individuals in a task group decided to take upon themselves. It wasn't something that was submitted. It was taken upon themselves to want to say that the equipment ground never has to be larger than the largest ungrounded conductor in a raceway. And that based on the fact that there was breakers would trip based on fault current, based on the size of the ungrounded conductor, that it obviously meant that the equipment ground

Speaker 2never needed to be larger either. What they didn't take into consideration is that you have a lot more impedance involved in the equipment, and we're trying to ensure that it clears quickly. We're not banking on the trip curves and stuff with circuit breakers. When it comes to the ungrounded conductors, the hot conductors, we're trying to make sure that if there's a direct ground fault, that an equipment grounded conductor can handle that fault. Now, if you have data that says otherwise, we would have loved to have

Speaker 2seen it. I would have loved to have seen it because I'm the first one that says, shoot, man, I don't want to make something larger than it needs to be. But the problem was no data was submitted. at all. They just went and changed it and said, no, it never based. Now, what's funny is the code cycle before that in the 2023, we all agreed that that when you had multiple sets that you took at least one of the conductors, and let's just say that it's a three-phase system, you took one of the phases, say blacks,

Speaker 2from each one of them and added them together, and that was the total circular mill, that together they act like one conductor. That's why they're being run in parallel. And that was the size of the circuit conductor. And when we said the code never required the equipment ground to be larger than the largest circuit conductor... ungrounded conductor, it's treating all of those ungrounded conductors as a single conductor, because that's the whole principle of why we're doing paralleling. And that was fine, because it's still a 1200 amp, 3000 amp, 5000 amp piece of equipment that we need

Speaker 2to make sure that we trip. And the problem with this is I could parallel this sucker out 10 sets, and that ungrounded conductor could get grossly smaller because of the paralleling, And if we go by the new rule in the 2026, then the equipment ground and conductor never needs to be larger than the largest ground and conductor. And we know that those equipment grounds aren't being treated as a true parallel application. We now run the risk that a ground fault may not clear the overcurrent protected device.

Speaker 2And no data was submitted, but that's what they did. And I argued against it. Joe Andre argued against it. You know, God rest his soul. And They just ignored us. Well, NFPA just came out with a document saying, whoa, whoa, whoa, wait a minute. Y'all need to rethink some of the stuff that you're doing. And whether that got fixed in the 2029, I have no idea at all. But either way, I wrote my articles. I published it. I made my statements in 2024, and it is what it is. So

Speaker 2I'm just going to teach you what the code is because y'all are tired of me rambling on. So in the 2026 clarifies that the limitation concerning the EGC, equipment grounded conductor, relative to the largest ungrounded conductor installed in parallel raceways and cables, that was clarified. So important technical distinction. The classification does not create a general rule allowing an installer to divide the table 250.122 minimum size by the number of parallel sets. So we're not doing that. The

Speaker 2size procedure is permitting the maximum required size to be performed, performance of a ground fault current path remain separate considerations. So in the 2026, it's just saying that if I have six sets and they have 500 KC mill ungrounded conductors in each set, that the equipment ground never has to be larger than the 500, regardless. And so if I parallelize that, Paralyzed. If I paralleled that out into

Speaker 210 sets, and let's say it dropped the ungrounded conductors down to four-aught, then the equipment ground in each raceway would not need to be larger than four-aught. Now, I patently disagree with that concept, but if it works, it works. You know, still need to see if that works, but in light of the recent document from NFPA... It basically tells me they should not have changed it without documentation. And that is why I've kind of drawn back from

Speaker 2my participation as heavily as I used to, because I just don't believe in the process is true the way it used to be. I think that people can make changes now on code panels without any justification. I think that should be argued. And if nobody presents anything that is that data, that's substantial, that we can't change what's been established. And it was amazing to me that everybody in the room, except for Joe, forgot everything that we talked about during the 2023 cycle. And the only reason we didn't make the change then was because of how

Speaker 2we did it. There was an informational note that we didn't agree with that was introducing things like the Gemi software to be able to reduce the size of equipment ground based on engineering design. They would take full responsibility. But the problem was now we break things up and accept them differently. Back then, we took it as a complete document. And so if we didn't agree to something, we threw it out. But guess what? We lost all the other changes that we worked on. That was a problem. So when they threw out the fine print note or

Speaker 2informational note that time, it erased everything that we did up to that point for clarity. And everybody was on the same page. It's amazing how three years later, everybody forgets all the work that we did. And then a task group just comes together and starts saying at night, they go, oh, well, we need to get rid of this altogether. That's what really happened. And don't let anybody tell you otherwise. I was there. That's exactly what happened. It's bullshit. And I just hope people don't lose their life over it because I don't want to be the guy that says, I told you so. In fact, somebody

Speaker 2even said, I said, you know what? Are you telling me that everything that Augusta Soares did and published is is wrong, and they were as bold enough to say that, yes, he was wrong. Who do you think you are to say Augusta Sorger's wrong when you just, you sit on a code panel and you may not even work specifically in the field that has that kind of expertise and knowledge, but you're making these bold statements. Maybe it's true. Maybe

Speaker 2I'm the one that's wrong here. But without the data to support it, you can't make changes like that. I'm just saying. Okay, damn, I didn't mean to get on that soapbox. But this is an especially worthwhile topic for evaluating whether the size methodology accounts adequately for the available ground fault current, conductor impedance, clearing time, and circuit configuration. In fact, the NFPA... Research Foundation published a study on

Speaker 2October 9th, 2026, examining the technical basis of equipment ground and conductor sizing, including parallel installation, and the study provides a useful foundation for questioning whether existing rules are sufficiently supported by fault current performance analysis. So, it's not about whether I'm right or I'm wrong. I can tease that and I can say I'm right, yada, yada, yada, but that's irrelevant. The point is, this acknowledges that you should not,

Speaker 2and this is to you code panel members, you should not be making changes to the code without substance and substantiation. Not just because you feel it's better, not because you think you know it's better. This is an important document. Lives are involved. Clearing over current protection devices is important. The timing of how they clear is extremely important. There was nothing that was submitted that would talk about anything to do with impedance and the process of that fault

Speaker 2current performance and evaluating anything to do with the clearing times and circuit configurations and understanding that you can't treat equipment grounds as parallel, but we're able to parallel the grounded conductor and the ungrounded conductors because of how current divides. But we understand that it's not going to work the same way with equipment grounded conductors because of the extended paths and the impedance on those extended paths. Why would you change something? That was all I brought to light. And of course, I was vilified for it, of course, right? Yeah,

Speaker 2it is what it is. All right. Obviously, we're going to have a part three to this because I've gone long and I ranted and I'm sure some of you have already clicked off and say, Paul, you're full of shit. You rant too much. You talk too much. I don't really give a shit what you think about it. I'm going to do what I do because Paul does what Paul does. So the last one we're talking about is the creation because we're on CodePanel 5 is the creation of Article 270. So that was a good move. So I support that. So Article 270 is, which was Part 10,

Speaker 2by the way, really in 250, got pulled out and now it's in its own standalone article because again, we're dealing with all those over 1,000 volt AC applications, right? And over 1,500 volt DC applications. So it was relocated from Part 10 into article 270 and And there was a lot of significant technical revisions that took place. So one important development involved sizing wire-type equipment ground conductors for these high-voltage systems. So unlike the familiar table that we're

Speaker 2all familiar with in 251.22, the method relies on the rating of the circuit's overcurrent protective device. Y'all are all familiar with that. We just finished talking about it. And I don't want to bore you and go into a nausea again. But the new Article 270 provisions use conductor-based criteria. and corresponding tables based on the conductor characteristics. So section 270.122 includes size requirements associated with the ungrounded circuit conductor sizes and their particular application rather than basing it on an overcurrent protected device. So a practical example is that a 5,000

Speaker 2volt or a 5kV feeder, and let's say with three four-aught copper phase conductors could have an equipment grounding conductor determined under the applicable new Article 270 table rather than the traditional low voltage EGC sizing tables. So again, a designer has to take these things into consideration. So if you're designing systems now, and this is what you're dealing with, you should not assume that the equipment grounding conductor size

Speaker 2methodology is is identical with a 480-volt distribution system when you're dealing with something that is 4,160-volt distribution system. In the past, many people even forgot to go to part 10, creating very costly repairs, okay? When somebody did something wrong and you get that knowledgeable inspector who walks in and goes, ah, by the way, You're missing something. You didn't go to

Speaker 2part 10 of 250. Now pulling it out and putting it in 270 is going to be a little bit easier for people to follow. And I think that's important. And it's worth it. wild change that I think took place. So kudos to CodePanel 5 for that. I had nothing to do with that. There was Eric Stromberg and a bunch of those other guys who did that. And I think that was necessary because it really just correlates information that we already had in part 10 and elaborated on

Speaker 2it and bring some new information because we're expanding that over a thousand volt application, over 1500 volt DC applications all the time. So we needed that separate clarity and that's what this does. And that's what we're doing a lot in the 2026 as well as moving forward in the 2029. Much more clarity in how it does. All right. So we're ending it right there. That's kind of all the things I want to talk about in part two of the NEC and part two of this podcast. We

Speaker 2will pick it up in a third podcast where we will elaborate. We'll start into the wiring methods, conductors, and installation practices. We'll start in... you know, Article 300 and move through that. And hopefully you'll get something out of that. Until next time, folks, stay safe. God bless. We'll catch you on the next edition of Master the NEC Podcast. And I will do my best to number these so you know part one, part two, part three the best I can. Take care. God bless.

Speaker 1Thanks for tuning in to another electrifying episode of the Master the NEC Podcast. We hope you're feeling more powered up and ready to tackle the electrical world with the knowledge and confidence you need to succeed. Remember, in the electrical trade, knowledge is power, and we're here to make sure you stay plugged into the latest insights, tips, and code updates. If you enjoyed today's episode, don't forget to subscribe, leave us a review, and share the podcast with your fellow electricians and industry pros. Until next time, keep your

Speaker 1tools sharp, your circuits clear, and your mind focused, because here at the Master the NEC Podcast, we're all about sparking your success. Stay safe, stay smart, and keep mastering the trade. From all of us here at Electrical Code Academy, thank you for all your support, and we will see you on the next Amazing Master the NEC Podcast episode.

Open the transcript file

Hosts and Guests

Nobody is credited on this episode yet.

Credit the people on this episode

Be the first to rate this episode

More episodes

All episodes
  1. NiteNerds™ — The Future of Permanent Outdoor & Landscape Lighting Is Here!

    Nov 12, 202631 minAudio

    NiteNerds™ - The Future of Permanent Outdoor & Landscape Lighting Is Here! What if your home could look absolutely stunning every night of the year - with the touch of a button? Welcome to the world of NiteNerds™, where...

    Credit the people on this episode

  2. MASTER THE NEC PODCAST | E81 | Electrical Code Knowledge and 2026 NEC Updates PT 3

    Oct 18, 202655 minAudio

    ⚡ MASTER THE NEC PODCAST 🎙️ Hosted by Paul Abernathy Master Electrician | National Electrical Code Expert | Electrical Educator ⏱️ Episode Length: 55 Minutes ⚡ ABOUT THIS EPISODEWelcome to Episode 81 of Master The NEC,...

    Credit the people on this episode

  3. MASTER THE NEC PODCAST | E79 | Electrical Code Knowledge and 2026 NEC Updates PT 1

    Oct 18, 20261 hr 4 minAudio

    ⚡ MASTER THE NEC PODCAST 🎙️ Hosted by Paul Abernathy Master Electrician | NEC Code Expert | Electrical Educator ⚡ ABOUT THIS EPISODEWelcome to another episode of Master The NEC, the podcast dedicated to helping...

    Credit the people on this episode

  4. What The HECK? Do you have a 2026 National Electrical Code Course?

    Oct 3, 202641 minAudio

    The National Electrical Code is a minimum standard - but what does that actually mean? In this episode of Master The NEC, Paul Abernathy takes a deeper look at one of the most misunderstood concepts in the electrical...