Master The NEC | Episode 58 | A Few Code Questions and What’s Happening Now

Apr 14, 202657 minAudio
ShareXLinkedInFacebookWhatsAppEmail

This episode is powerful because it addresses a question posed via the Let’s Ask Paul Portal at https://FastTraxSystem.com. Today’s questions are about using a 15A Receptacle on a 20A Commercial Branch Circuit and a classic Transformers Question. Of course, we will also chat about anything, so come on and listen. We are excited to announce that we have passed 2,000,000 unique downloads this year. Thank you to everyone for your support and for keeping the podcast alive while I have been taking care of my wife and family. Listen as Paul Abernathy, CEO and Founder of Electrical Code Academy, Inc., the leading electrical educator in the country, discusses electrical code, electrical trade, and electrical business-related topics to help electricians maximize their knowledge and industry investment. If you are looking to learn more about the National Electrical Code, for electrical exam preparation, or to better your knowledge of the NEC, then visit https://fasttraxsystem.com for all the electrical code training you will ever need by the leading electrical educator in the country with the best NEC learning program on the planet. Become a supporter of this podcast: https://www.spreaker.com/podcast/electrify-electrician-podcast--4131858/support.

Audio and video play straight from the show's own hosting. PodSubs stores and serves no media.

Transcript

From the show. Tap a time to play from there.

Speaker 1Welcome to the Master of the NEEC podcast, the ultimate destination for anyone passionate about the electrical trade. Whether you're a season electrician, an eager apprentice, or just someone who wants to dive deep into the world of electrical work, you've come to the right place.

Speaker 2Join your host, Paul.

Speaker 1Abernavi, a true authority in the industry with over thirty eight years of trade experience, as he electrifies your mind with in depth discussions, expertips, and valuable insights that will keep you ahead of the curve. Each episode, Paul will illuminate the complexities of the trade, decode the national electrical code, and share the latest industry trends, all while empowering you to take your electrical career to the next level. So gear up, plug in, and get ready to supercharge your knowledge because with the Master of the NEEC podcast, the

Speaker 1power is in your hands. Now get ready. Here is your host, Paul Abernavip What.

Speaker 2Up, everybody, Welcome to another episode of Master the NEC.

Speaker 3I'm your host, Paul Abernathy. Thanks for joining me for the podcast. Hey, it's twenty twenty six. We're already believe it or not, We're already in April, and I'm telling you we have already hit two million unique downloads for the podcast. And you know, that's quite amazing because I do not do near the number of podcasts that I used to do. But I guess when you have over a thousand episodes out there, people are still listening. So again, I appreciate all of you. I promise I will get back on the wagon and start getting out some more

Speaker 3episodes for you, kind of some updates and some things around that you've seen happening in the last couple of months. I want to talk about tonight and answer some you know, some couple of co questions that I that I got. One of those co questions is based on a video that I did on TikTok about mc cable, So i'll talk about that a little bit, kind of give you some insight on it, because it's amazing to me that I could be somebody in the industry who has eleven patents on mc cable and still when I post something, people still question it as if they came from some

Speaker 3authority position to.

Speaker 2Be able to even question it.

Speaker 3But anyway, I find it interesting and that video was a transition where MC cable transitions into an EMT. And so it's always also funny too because I'll post an image and I put em T tubing and everybody's like, well, of course t's tubing, So huh haha, it's EMT tubing. It's EMT, not EMT tubing. Well, if you know the kind of situation we deal with in social media, if I did not put the tubing on the end of it, somebody would misunderstand it or misrepresent it and they wouldn't understand. So, uh,

Speaker 3it is what it is, right, So electrical metallic tubing is a tubing. It is not a conduit. It is a it is a raceway. But anyway, so the transition and so it's it's very common in commercial applications to stub up e MT. Stub it up, put a ninety on it, and put it above this is the drop ceiling, and then somebody comes along later and they'll bring something down to it.

Speaker 2Most of the time, back in the day when it was electrical, I used.

Speaker 3To put we used to put four inch squares on the end of it, and so even though we'd stub it down, we'd still put a four inn square on it and transition that way, not because of the not because of what I'm going to talk about as far as the markings, but just it's just the way we did it. And then there's a lot of times when it was for data or communication, we just stub up a ninety. But anyway, interesting fact that UL fifteen sixty nine, which is the standard for MC cable, you can get away with not marking the conductors that are inside of an MC cable. Of course the three ten in the

Speaker 3National Electrical Code provides for that as well, but because usually we put the markings on the reel, there's a label that gets mounted on a reel.

Speaker 2That type of thing.

Speaker 3But so the vast majority of MC cable it's just you know, it's just the metal armor, the metal cladding, and there's nothing on it. Now, if it's PVC jacketed type of MC, then you know, we'll put writing on the PVC material, but uh, the covering outside sheathing over the armor. But for normal h MC cable, it's typically we're not gonna not every manufacturer will mark the individual conductors that are inside of it.

Speaker 2Some do, some don't. That's the prerogative of the manufacturer.

Speaker 3It's got a ribbon in there that's got pertinent information on it, but that doesn't mean that. And I saw online where somebody said that you could take EMC and transition it with a listed transition fitting, which is a real thing, right. It's a fitting that lets you go from one type of wiring method to another so that you're not kind of guivering something up or creating a Frankenstein piece of equipment to trainransition between one to the other. Even though it's probably worked forever in the field, somebody's

Speaker 3probably used a probably a rigid coupling and put connectors on each end and probably transition. Reality is that's not a listed transition fitting. And so so when they transition, you strip off the armor and use a transition fitting which will clamp down on the armor of making that bond at the armor, and then the individual conductors are stripped, you know, strip the armor off, and they go down the actual raceway in this case to say an e

Speaker 3MT tubing. And you know, they argue, we do it all the time, and we do do that. People have been doing this for a long time. And when you didn't have the transition fittings, you just would use a box in transition, right, so the problem really is that the conductors are required to be marked when they're not being used inside of an assembly. Now a fast majority many of the manufacturers may mark the conductors inside of their MC cable and then some may choose not to

Speaker 3the fact of matter is the fifteen sixty nine in the UL standard, which is the construction standard, doesn't really require that to have.

Speaker 2Those markings on the individual conductors. And in the NEEC.

Speaker 3Again it even gives you the allowance to have it on the literature. I have it on the actual label on a real or coil, that type of thing. The problem is when you strip off the armor. And again I'm not telling people what to do. They're free to do whatever they want. But when you do that, and if the conductors inside of the armor are not marked, which they didn't have to be because they're part of a cable assembly, once it's stripped out, it's no longer part of that cable assembly. Now it's okay for termination inside a junction box, it's okay for terminations in the cabinets,

Speaker 3but you're transitioning from a wiring method to a wiring method. So we have those rules that have to be met and so if the conductors are not marked well, then they technically cannot be used in the intended method as conductors in a wiring method like that, because again they were okay in an assembly but not in an individual raceway in this case an e MT tubing. So you know, you get a lot of people that have heartburn online that make a lot of comments, and again you know,

Speaker 3most of the time when the nasty comments come in, I will block you. Look, there's no secret out there. People say Paul blocks people. You damn right I do. I'll block your ass and a heartbeat if there's a thought that you're going to take a thread and take it off rail because you're feeling like you have freedom of speech and you can say what you want.

Speaker 2You do not have freedom.

Speaker 3Of speech on a forum that's controlled by me, No different than I don't have freedom of speech on a forum where they can just remove my content like a TikTok or an Instagram or a Facebook. They remove it all the time. Okay, so get over it. The reality is I'm not gonna let you spew false and misley information when I obviously wouldn't post it if I didn't know better. Now, if a manufacturers do mark their conductors, have at it transition fitting and just go at it. It's perfectly fine, and it's not about It's not about

Speaker 3the conductors at the termination when you get down to the box or cabinet. It's about what's in the wiring method. Now again, I know that I have a vast number of people that'll say, good lord, Paul, I've had an inspector that's never failed me. What's the harm. I'm not saying that there's a harm. It conductors a conductor. The sheer fact of the matter is we can't control what other people may do, how they may read something, what they may do to My sons share his pictures all the time of some of the pool installations that he

Speaker 3sees because he's in the pool industry, and I am horrified, knowing that I sit on CO Panel seventeen, but to look at some of these swimming pool installations, it makes me think, no damn electrician did that. And they're supposed to be doing that, but there's no way electrician did that. If they are, they're a pretty shoddy ass electrician. So that's one of those things that I that I look at all the time. So you know, you can almost you have to. We have to make an effort to protect people from themselves, unfortunately. And the same thing that

Speaker 3I'm talking about with the MC cable where the conductors aren't marked, also transitions over into like non metallic sheath cable. It's the same, it's the same concept. Okay, very rarely do and manufacturers put any markings on the insulated conductors that are inside of the cable assemblies, whether it's non metallic sheath cable, MC cable, AC cable, they can if they want to use up stock they may have which is individual single insulated conductors and they just trying to use it instead of having to make some more or

Speaker 3something than they could. If it's equivalent to THGN or tw for example, with a non metallic sheath cable, then you can do that. But you know, if there's no markings on there, it's fine as long as it's in the cable assembly and when it gets determination, it's fine. It is not fine to strip the conductors out and use them outside of that. And this, really, I'm be honest with you, this applies to any cable assembly. If the conductors are not marked and you strip them out

Speaker 3and they're not marked, then they're not going to be compliant with three ten and so it just it just is what it is. And you know, people want to argue until they're blue in the face.

Speaker 2I get it.

Speaker 3Copper's copper, aluminum's illuminum, I get it. But the fact of the matter is the code is a minimum safety standard. Everybody bitches that they don't do the minimum.

Speaker 2Well, hell, if you.

Speaker 3Don't even use the conductors properly, then you're not even meeting the minimum.

Speaker 2So you can't have it both ways.

Speaker 3You can't be in Eric Swolwell and complain about somebody and then commit the same crime.

Speaker 2Okay, you know what I'm saying. You get me, You know I think you get me.

Speaker 3Anyway, that was a great conversation over and take talk. If you're not following me over in TikTok, consider following me.

Speaker 2It's master the NEC.

Speaker 3By the way, it is Master the NEC on all of my platforms. So if you see something with the space between master and the or a space after the NEC or whatever, you know it's not me because I'm the only one that has master the NEC on all the platforms except for LinkedIn, where it's just my name Paul Aberta, I think okay, And I'd love to follow you on LinkedIn as well if you're a business you want to follow And I give a lot of business advice, a lot of advice for marketing your electrical contracting business, and I love to help you, uh and answer questions

Speaker 3for you for that too. If it's going to help your business be successful, it's what I want you to be successful as an electrician, as a contractor and whatnot. Okay, So anyway, that was an interesting discussion over on TikTok.

Speaker 2What else were arguing about.

Speaker 3Oh yeah, still got the ongoing argument in feuds with Syporter. As always his little minions or are fast at it. I blocked him most of them, but they still come over to my social platforms and post something knowing that nobody will ever see it.

Speaker 2So you know, I'm still living in all of their minds and that's fine.

Speaker 3We did put up a legal notice to Sigh, and it seems like he's complying a little bit with it, okay, clearly admitting that he's knows that he's in the wrong.

Speaker 2But he's also an extreme liar in misleading in an attention orr. But you know, people say, well, why don't you let him comment back. He first of all, he won't comment.

Speaker 3Secondly, he's doing it all for clicks, so he doesn't bother me, so I don't lose any sleep over there. Some other guys were really worried about him. He does not worry about He's insignificant in the realm of the world that I roll around in, and he's just he doesn't matter. Okay, his whole existence just doesn't matter to me. But it's funny how he would post this recent thing he did with some kind of I didn't even know anything about it, but it's some kind of conspiracy I think.

Speaker 2The more I'm learning.

Speaker 3After I was drug into this and he started doing these videos again, I guess he needs some more attention. I guess the sales from home inspections must be going off. He didn't have near the the client base that Inspector Preston has, obviously, and I guess they're running out of the Horton Holmes to inspect out there in Arizona. But it's it's what was funny. As he went into this conspiracy theorist thing where I was, I guess I was conspiring with and I'm no new to this conspiracy thing, right.

Speaker 3Remember remember what happened in the issue with this copper clad thing. I was part of some conspiracy thing that never happened. Anyway, I guess I'm I look like one of those guys that would be involved in that. I guess I guess I look like, you know, I'm not not a mafia guy.

Speaker 2Maybe I look like I don't know. I think I looked like a little roly poly, but whatever.

Speaker 3So anyway, the rumor was he started spreading this garbage to his MENI his little followers, little.

Speaker 2Dead heads out there in uh. Uh.

Speaker 3And incidentally, his his following grew because he was on TV because he was trashing a builder. Uh and the builder ended up filing a complaint against him, uh and he got reprimand letter, but they didn't do anything again because he has a free he has you know, it's his business. He can say what he wants about any He can say what.

Speaker 2He wants about me.

Speaker 3I really don't care, and he does and I don't care, you know, I I'll be honest with you. I can't say anything about his inspections. I've said stuff about when he calls out something that's wrong because he thinks he knows electrical But as far as his inspection techniques, I mean he was, he was an INTERNACHI member.

Speaker 2I don't he's not anymore. I was.

Speaker 3I'm a CMI. He's a CMI. I was a CMI had long before he was ever a CMI. I was one of the very first certified Master Inspectors from INTERNACHI.

Speaker 2And the the CMI board in Colorado.

Speaker 3But I don't have anything about him other than that, you know, and but he seems to want to throw my name around a lot.

Speaker 2And that's fine. His little minions say some really nasty stuff, and that's fine too. I don't really care.

Speaker 3But at the end of the day, making an assumption that I was part of something that I don't even one hundred percent know what went on exactly. What I've gathered is that he calls somebody's wife to get fired, probably frivolously making up stuff, uh, and she got upset, rightfully so, and fired a nasty I don't know if it's an email, a text, or letter. I'm not I'm not one hundred percent sure on that because I didn't

Speaker 3know anything about it until it was shared to me that SI was doing these these videos with me in it. Now he's done videos before where he's taking what I've said out of context and uh, and it is a little clip. He runs a lot which I'm flattered where I call him an nobody.

Speaker 2Because he is.

Speaker 3Really he's a nobody just because you think you got a couple hundred thous or whatever one hundred thousands of followers. Look at who they are. Really, I mean, you're not my client base. They're not my client base. They're not electricians electricians that if there's electrician out there that takes a home inspector's side and doesn't understand when something's cut up and used improperly, then I probably wouldn't want you in my courses or taking my classes anyway. So you're no loss to me. Okay, I don't sleepover you. But

Speaker 3I guess what happened is that said something and I don't know the details, and I purposely didn't get wasn't involved in any of it. But it seems like I'm put on this board where he's got this yarn, this yarn strung up like some kind of CSI thing. And I don't see his videos, I really I don't. I swear to you, I don't watch his videos.

Speaker 2The image that I.

Speaker 3Use to kind of make little funny clips or videos is what's shared with me.

Speaker 2I don't watch them.

Speaker 3Our attorneys do. They have an account. They keep an eye on him because of his recent actions, but other than that, I don't follow him because it just doesn't appeal to me, the same as I don't, you know, in fairness, I don't watch electrical videos. I don't watch Dustin's got a great channel with Electrician you, but I don't watch Dustin's videos.

Speaker 2It's nothing that I can learn from those videos, and so I really I could.

Speaker 3I could never watch when I get it when I have a channel that has thirty five thousand or forty thousand on this platform and twenty on this one and thirty on this one, and we get three hundred thousand unique downloads a month on our podcast because I started podcasting, I'm still one of the few that are still podcasting out there.

Speaker 2I get it.

Speaker 3But at the end of the day, your people listen to me for code and my insight, I don't. I don't watch other Electricians videos because I don't want to. I don't have the desire to watch somebody run condo it or pull conductors in raceways, or talk about things that I already know about at nausea.

Speaker 2Okay, it's not.

Speaker 3I can't get into watching transformer videos when I've done tons of Transformer videos. I can't get into watching motor videos when I teach it all the time, and I understand very detailed about motors. So I mean, I'm sorry, I just can't. It's no disrespect to any of them that do them. We need it, but I just can't. I can't do it. It's not my my thing.

Speaker 2Now.

Speaker 3That doesn't mean you folks out there don't, Okay. You know, if you're an up, you're learning the trade, you're trying to gain knowledge. Those things can be extremely beneficial. I watch YouTube all the time. Now I'm not watching them for electrical but I tell you what, I I listen to podcasts almost every day still. You know, some people say podcasting's dead. Dude, dude, we're still doing. You know, we've done two million unique downloads so far this year.

Speaker 2It's it's up well.

Speaker 3Beyond the three hundred average three hundred thousand downloads a month at this stage. It went crazy the last last two months and it's on pace for this month.

Speaker 2You know, I appreciate every one.

Speaker 3Of you out there that listen and share our podcast, and I still request topics. It's just now all you got to do is just go to our website fastracksystem dot com and you'll see in the navigation there is a let's ask Paul link.

Speaker 2I just don't do it through the old way.

Speaker 3Right now, we as a corporation have have grown and so now everything is internally through our site rather than third parties, using third parties like WIS and things like that.

Speaker 2We just don't have to do that anymore. Thank God.

Speaker 3I mean, I'm blessed that we have been successful and y'all done it. Y'all made it successful. All of you out there that have been a part of our programs, we really appreciated. One of the guiding lights of I shouldn't say, guy, one of the well guiding light is to is to always try to keep providing new things, new avenues for.

Speaker 2People to get knowledge. That's what my goal is, right.

Speaker 3So when we create platforms and programs, right, we try to create them so that we can give an avenue for you to be able to watch the things like Dustin's videos, or Mike's videos, or my videos or somebody.

Speaker 2That's the goal. Now.

Speaker 3When we created fast tracks Tube, for example, we created a unique platform that is that we're always adding new videos. It's exclusively where we're going to have our twenty twenty six videos. And incidentally, we've got a couple of them that are dropping here in the next couple of days, going to be open to everybody that's a member. Once the course is done, our twenty twenty six course, then all of it won't be available. But until then, I'm going to try to make as much of it as available as I can to everybody that subscribes for the

Speaker 3ninety nine bucks because I think, you know what, that's a lot of money, even ninety nine bucks is you know, still you're giving up.

Speaker 2Your hard earned money, and I appreciate it. But we're going to try to make.

Speaker 3As many of the videos available over there. And yeah, I think the fast Tracks Tube is awesome because it gets rid of all of the commercials. It still gives the some of the providers, the software that we use still gives them the click value. They still get the views, but it's a way that our system can it still shows. It doesn't show the ads, but their ads are running.

Speaker 3They're just I don't know how to explain it. They're not shown to the viewer. So it's pretty complicated how this works on the back end. So you know, they're getting credit, people are getting credit for views, but we're able to do it into an ecosystem that's just easier to watch. It's a neater platform. It's a little more focused than you would get on YouTube, which you know, YouTube's still great that type of thing, but so just a little different delivery. If you haven't seen it. We do have some free videos over there. You know, you

Speaker 3can find them over on fasttrackstube dot com. So it's also fast tracks TV as well. You can find it there too. But so, yeah, that's been great. This past year has really seen that grow as well. There's a lot of great videos. We just just uploaded a couple of the other day and there's a ton of them in there. It's definitely a gold mine for anybody that's trying to learn calculations because we have an eight hour video over there that you can you know, it's it's yeah,

Speaker 3it's tough to sit eight hours and watch calculations, right but again it's it's beneficial. You'll walk away learning something from it. And we actually sold that webinar back when we did it. I can't remember. I think it's three or four hundred dollars for eight hours, you know, webinar in well worth it then, but now it's just included in the ninety nine.

Speaker 2So we haven't done.

Speaker 3A full eight hour calculation series again since that last one.

Speaker 2I think we got I got to talk to Jeff.

Speaker 3I think we need to probably do one this year now that we have the twenty twenty six is really out and states are going to start adopting it in the next six months or more. They're in the if not in the process now doing it. Texas will probably do it in September. Maine probably already has. But so we got to start rolling those things out there to do that. Most of your states out there, you're still going to be on the twenty twenty three or twenty twenty four for while yet still, so you don't have to worry too much about that. So but we'll make

Speaker 3sure we have most of that content complete by then for those that are interested. But yeah, that's a great platform and it's been doing wonderful things. People love fasttracks Tube, so again, and you.

Speaker 2Can leave comments there as well. I don't know if you knew that, but you can actually watch a video and leave a comment or give a thumbs up or whatnot, just like you can on any other platform. So encourage you to check that out. Okay, what other question? Did I have a recently electrical question?

Speaker 3Let's see, I thought I had a question that I wanted that I was going to just talk about today.

Speaker 2Let me see if I can dig that up.

Speaker 3Okay, this question says, Hey, Paul, quick question for you. I'm working out of the twenty twenty three code and specifically in a commercial office setting. We are are we allowed to install fifteen and receptacles in a commercial setting? I always install twenty AMP year but I am looking in the code and can't find any code that wouldn't allow me to install fifteen AMP receptacles. Thanks for your help. PS, I missed coffee Hour. Okay, yeah, so this is a

Speaker 3long time listener who follows us on and when we did the coffee Hour and things like that. So great, great question. So most people are familiar in the NEEC, and I've talked about it before. About the receptacle ratings and everything that falls under two ten dot twenty one. And he is in the twenty twenty three edition of the NEEC by the way, So he's asking about receptacles ratings and specifically allows a fifteen or a twenty amp to be installed on a twenty amp circuit, just like you probably are familiar with how we probably you probably

Speaker 3have done this in a residence. You've done it in a kitchen on a counter in a kitchen counter, You've used a fifteen app rated device and put it on the twenty amp circuit and it's okay. So there isn't really any difference, nothing changing. So could you do it in a commercial setting, Well, the answer is yes, but you have to understand a few things. Typically in a commercial environment like that, you're going to have drawings, and the drawing is going to have requirements and rules on those drawings, and those drawings are probably going to call for it to be twenty operated devices. And so I

Speaker 3think in my forty years in the industry and early in my career, I did a lot of commercial work. With my brother, we did commercial stuff too, and I can tell you that I recall that when an engineer would put on there, there's a twenty amp circuit, and they would they would actually denote on there that it was a twenty operated receptacle.

Speaker 2So and again this rule table two ten twenty one.

Speaker 3B three, it's four where it says circuits that are serving more than one receptacle. So a duplex, by the way, is more than one receptacle. It's two receptacles. Even though it shares a a yoke. It's still so the rules in two ten dot twenty one B three would apply. But I can tell you right now it's going a lot more is going to be can you do something?

Speaker 2Yes? Is it going to be okay? Sure?

Speaker 3Here's the problem also, is that again, if the specifications say one thing, then you need to follow the specifications. You create a conflict. And the inspector's going to look at these drawings and he's going to look at this, and you know code is the minimum. So the engineer design professional that may be what they want. So in theory, could you do it?

Speaker 1Yes?

Speaker 2Now, the other thing you got to be.

Speaker 3Aware of is the permissible loads, uh and things like that. So a lot of times in this scenario, these are going to be like a cordon plug connected for receptacles where you'd be putting cordon plug connected type of loads and you're supplying two or more receptacles, and again I do plex would be then you have some limitations because if it's a fifteen amp receptacle, then the maximum load is twelve amps on if it's a twenty amp then the maximum load is sixteen So it could play an effect on the loading of what you're putting on these circuits and how he designed the system and how he

Speaker 3may have laid it out. So I encourage you, listener, very loyal listener, appreciate you. I don't think he would be upset if I said his name is Manny. Many's a great guy. He follows us all the time, very dedicated. We appreciate that two ten dot twenty one B Manny look at B two and B three. So but to answer your questions, no, nothing from the code perspective. Then it's clear that you can put a fifteen app rated device on a twenty ant brand circuit.

Speaker 2I like that.

Speaker 3Now, if it's a SIMPLEX, that's different. That's a single single receptacle application, right, you gotta be careful because it says a single simplex. Receptacles installed on an individual brand circuit, I mean that's the only thing on it shall have an ampacity the receptacle I shall have an opacity rating not less than and so obviously, if it's a twenty eight brand circuit, then this single simplex cannot have a fifteen ant because it would be less than the rating of the brand circuit. It could be more, and this

Speaker 3tricks people up in our prep questions all the time. It can be more, but just can't be less, right than the receptacle installed on that individual brand circuit shall have an opacity not less than the brand circuit. So if it's a twenty anight brand circuit, it's a single simplex, then it's got to be at least twenty Okay, And that kind of throws people because again, if the same thing falls into where it's forty and fifty amp and people want to know that type of thing, it's the same Conceptay. As long as the receptacle that it's being

Speaker 3installed on it is not less than what the rating is of the brand circuit, then it's fine.

Speaker 2I can put a fifty on a forty. That fifty is not less than the rating of the brand circuit. I tend to screw people's brains up a little bit. They get kind of funky with it.

Speaker 3But in your situations, yeah, it's really probably the reason we've always done it is because engineers and design professionals when they see a twenty amp commercial. And also the other thing is they also tend to want to have commercial devices. And I don't know this to be a fact because I'm not in that world, the device world, but I don't know if they actually make commercial grade fifteens.

Speaker 2I'm sure they probably do. You know, somebody out there is gonna say, Paul, you're stupid. You don't know that one.

Speaker 3No, I don't because I always installed twenty amps in it. You know that type of thing. So but anyway, there you go. I don't regularly ever recall fifteen amp circuits in a commercial setting except for.

Speaker 2To lighting that type of thing. That's just me.

Speaker 3Okay, So anyway, I hopefully I answered your question, Manny, you know, kind of giving you a little bit, maybe more than you wanted. But that's the that's the that's the kind of the everything, the way you got to look at it. Okay, all right, we got any other questions Okay, let's see, there's another one came in not too long ago. I still got to catch up on a lot of these, but this one came in, so it's the first time I'm seeing this one. Let's try to let's try to answer this together. Here it says, and I'm not I really don't use names of people, but in the future, folks, if you want me to

Speaker 3give you a shout out, because again, there's nothing wrong with the answer asking questions. Okay, you know, don't feel like you can't ask a question, and you want your name because every you know, everybody loves a good shout out, right, So anyway, this this question says, I have a question for you, sir.

Speaker 2It's about transformers.

Speaker 3Okay, it says, out in the field, for example, we usually size a seventy kVA transformer with a primary overcurrent of ninety amps incoming and a secondary overcurrent of two hundred amps. Okay, it says, but but if you use four fifty dot three B, you size primary overcurrent at two hundred and fifty percent. Hey, I'm gonna give you a little thoughts about that. Because you can go at

Speaker 3primary at fifty. You don't have to go all the way up to two hundred and fifty and I'll tell you why most do not. But anyway, so it says, but if you use four fifty dot three B, you size primary at at two hundred and fifty percent and secondary ocurrent at one hundred and twenty five percent, why is it standard practice to use the field to use the field example and not the code compliant example. So I'm going to assume that you mean why you very

Speaker 3rarely ever see the primary UH protection for that transformer at two hundred and fifty percent. And I've talked about this in my transformer videos. Encourage you to go watch them. They're over on r fast tracks Tube. First of all, if you size the primary protection for that transformer at two hundred and fifty percent, then there's a high probability that you're not going to protect the conductors on the primary side. Okay, so typically those conductors if something is

Speaker 3translated into say a continuous load, and usually a design professionals that the worst case scenario will do the primary side conductors at one hundred and twenty five percent.

Speaker 2And if they.

Speaker 3Size the primary protection of the transformer at depending on whatever their amps come out with, if they size that at one hundred and twenty five percent, then basically.

Speaker 2They're doing double duty.

Speaker 3They're protecting not only the primary side conductors, but they're also protecting the transformer itself.

Speaker 2So it's double duty. Because what you could do is if you did.

Speaker 3Two hundred and fifty percent, then you're either going to have to size the conductors properly, okay, or you're going to end up overside having to over size the primary side conductors, which nobody wants to waste money in oversizing something that's not necessary. Right, if you're using your transformer rules, certain things you can do and you can't do.

Speaker 2So.

Speaker 3Typically, the only time we ever see the two hundred and fifty percent on the primary side is if we have a feeder that's going to these transformers that may be supplying multiple transformers. And if that's the case, then you have this collective amount that is on the load side of a disconnect, and you want that disconnect, let's say, to serve multiple duties, you know, be the disconnect primary side protection.

Speaker 2From multiple transformers. Okay.

Speaker 3If that's the case, then you know you can go up to two hundred and fifty percent. Right, of course, there is also a little note there that says, if a transformer happens you equipped with coordinated thermal overload protection, and you will know that by the price of the transformer, it's quite it's provided by the manufacturer. Then it gives you you some additional allowances where it can be not more than six times the rated current on the transformer for transformers not having more than six percent impedance, and not more than four times the rated current on a

Speaker 3transformer where they have more than six but not more than ten percent impedance. So there are some other allowances that may even let you go a little higher than the two hundred and fifty percent, to be honest with you, but it's all based on what protection is inherent by the manufacturer. Now, when it comes to two hundred five percent, if you want to use the two hundred fifty percent, you can and as long as those conductors are still protected. But nobody's going to use the two fifty to protect that and then size it down to protect the conductors.

Speaker 2You get what I'm saying.

Speaker 3So it's the reason you see that in the field is typically because it just it just makes sense. There's no real need to go to two hundred and fifty percent, and nothing says you have to it's it's you can go up to. It says the maximum rating and setting is two hundred and fifty percent, doesn't mean you have to use two hundred and fifty percent. So if you use one twenty five, it's still code compliant. You get what I'm saying. So it's just the standard standard practice in the industry to protect do to do double duty

Speaker 3and protect those primary conductors as well as the transformer itself, and so whatever protection's there, that's that's mainly serving as the protection for the transformer, but inherently it's also going to be protecting the primary side conductors as well.

Speaker 2Does that make sense, okay?

Speaker 3And then of course the secondary is going to be that one twenty five. Again, that's the max. So you can go up to one hundred and twenty five percent. Doesn't mean you have to go all the way up to it.

Speaker 2You can do it at one hundred percent if you want. All right.

Speaker 3Hopefully, hopefully that answers that question to somebody. But that's again I get it. It's what you it's what you see out in the field. But that's the kind of the rationale but hopefully that makes sense. That's the rationale behind it. Let's see we got anything else. Let's see here, Let's see here. Okay, he says, here's a question that came in. It says, I was wondering, I have had an inspector call me multiple times on the clear nylon on Romex being damaged. Okay, says I was wondering if

Speaker 3you had any code reference that I could tell this inspector that this is not part of the integral system for the wire.

Speaker 2Thank you for your help. Okay.

Speaker 3So this is a little bit confusing because typically none of the manufacturers put any.

Speaker 2Nihlon clear nylon on their sheathing.

Speaker 3So this leads me to think you're maybe you're talking about the clear niyelon that's on the conductors inside of the non metallic sheath cable, which this case, Romax is a trade name for South Wire. That's their their non metallic sheath cable. But we don't put any clear anything on the sheeting. Sheathing is usually PVC extra rooted sheathing. It is, you know, if it is damaged, they do make a cable repair method to do it repair the cable.

Speaker 3It does not have an insulation rating it typically is rated for equivalent to whatever the conductors would be, which this case would be ninety degree. But it's still not insulation. It's just a sheathing. Can it get damaged near an install Absolutely, as long as you repair it using a proper method to repair it, and of course it.

Speaker 2Has to be acceptable to the AHJ.

Speaker 3But in this case, when you say clear nylon, this makes me think that you're talking about the conductors inside, which are very similar to THHGN. Of course, the standard UL seven nineteen allows for conductors in non metallogy cable to be equivalent to THHHN as far as construction or tw tw tends to be a little thicker, doesn't have any nylon on it. So typically the equivalent to THHN is still going to have the nylon on it. Okay, extruded over it a thin layer. Now I can tell

Speaker 3you that that nylon that gets extruded over it very thin like four mills, that has no insulation value either. Typically, when we have THN in being the nylon, typically that is to help reduce the coefficient of friction during the pool and offer some level of protection to the insulated conductor. Now, the caveat to That is, if I was installing single insulated conductors in a raceway in an oil and gas environment like out on an oil rig, or maybe in

Speaker 3a piece of equipment that is switches that are immersed in oil or some way that they're in a rupture, it could get oiled down into the raceway into these conductors. Then I have to make sure that nylon is not damaged. Okay, that extruded nyelon over top of the insulation.

Speaker 2But anywhere else. Ninety nine point nine nine percent of all normal installations out there, if the nylon gets chewed up, it's no big deal. It doesn't hurt anything.

Speaker 3Why because it doesn't inherently bring any value to the installation.

Speaker 2It really doesn't.

Speaker 3I know people want to argue about it, but it doesn't. It's sacrificial it Now in a nonmeatalogy cable, what you're seeing is it typically most of us are going to use stems of THHHN and we're just not going to put any markings on it because it goes inside of the assembly, so we're not going to spend the money to put the ink on there. But it's still got the nylon on it. So if it gets damaged. It really doesn't matter. It shouldn't get damaged if it's inside the cable assembly with the sheathing over it and it's

Speaker 3wrapped in paper jute. But at the end of the day, that's what you're talking about, because I'm not aware of any clear nylon that's on top of the romax or non metallic chief cable, So I can only assume you're talking about the conductors inside and so hey, so it's sacrificial. And we know that's also the case with this non metality sheaf cable because these conductors aren't designed to use in a wet location anyway, so you certainly couldn't use it in an oil and gas location because non metallic sheath cable, for God's sake, So.

Speaker 2The NYE line is in there.

Speaker 3If this nigh line on those conductors, it's just there for the ride. It doesn't do anything as far as creating any additional value.

Speaker 2It's just there.

Speaker 3And most of us manufacturers just we don't want to make something special for a low margin product. Well, it used to be really low margin, and then after COVID, non metallic sheaf cable kind of skyrocketed in price. I'm sure y'all seen it by going to the supply house. Well, it became it was a low margin product and it turned into a damn good margin product because it's easy to produce and it uses the same inners that we would use for anything else. We just get to save a step and not put printing on it because it's inside of the cable assembly. So they use whatever we

Speaker 3have and that's why it still has an eye line on that type of thing. Plus, it's got to be equivalent to tjg in and that's part of th jgn's construction, right. So anyway, hopefully that answers that question for you.

Speaker 2It's a great question.

Speaker 3I appreciate you sending it and sending it and you guys, you know that you can send any question you want to me by just going to our website fasttracksystem dot com and then all you've got to do is just put in your question, give your information, click that submit button, and again we do it much easier, believe it or not, it's much easier now than it.

Speaker 2Used to be on WIS.

Speaker 3Okay, but Wicks sponsored us for years and then we just kind of outgrew.

Speaker 2It a little bit. That type of thing Okay, let's see here. I got another question.

Speaker 3This is a long one, and I don't know if it's actually a question or not, but I'll read it. It says, I'm trying to pass my Texas Electrical Exam. I don't recall the Journeyman test being so cumbersome.

Speaker 1Ok.

Speaker 2I only have until May fourteenth to.

Speaker 3Pass it as it expires, and I kind of ft off for a year. That sucks, but I get it. Life does get in the way sometimes, so don't let it beat you up too bad. Says I took the last few years off as I was semi retired.

Speaker 2Okay, well that makes sense.

Speaker 3Your head's not in the code when you're kind of retired, It says, after some interesting times and a divorce, I'm looking to get my master's license and really dial in. I took the test and got a sixty one on the code theory portion, only finishing about fifty five of seventy five questions. And that's where you went wrong. That's where your problem is right there. For that one you ran out of time. That is where you got to learn the three wave method, man, and really optimize how

Speaker 3you manage your questions. That would have saved you a thing. But I'm going to tell you a lot of people and this is why we created the structured program. It doesn't matter who's we could have used any I could have used Mike Colt's book and created our fast Tracks program. It doesn't matter about The code is code. It's the method that we use to teach you. That's what separates us from everybody. And again, it sound like a commercial, but that is what it is. And so the way we hit you with a question, hit you with the chevron's, hit you with the competency review, and it's bam bam bam bam bam. And then we support you all the

Speaker 3way with fast Tracks Interact or the ability to ask questions and comments. And then of course if you get the enhanced program, you get to watch the videos as well extra videos over on fast Tracks too. Okay, it's not a video course, by the way, it's extra ancillary videos. Okay, So anyway, that's kind of a one two punch to help you. But I get it. So it looks like you had trouble. And folks, if you go into an exam and you find yourself having to look up every question on the exam, in an index.

Speaker 2You know, back and forth, back and forth. You're not going to pass.

Speaker 3I mean, you may get lucky, but statistically you're not going to pass. Why because you just you freaking run out of time? Okay, it says. Now, it says, I need to get quick and better, don't. I don't know how I get hung up on time, but I do. I got a sixty three on the calculations. Well you're close on the calcs. You're getting there. It says, I actually thought I did better than on that. But I digress. It says, what do you recommend? A I have to

Speaker 3cram and pass this thing I've been doing. He says, I've been doing the Tom Henry twenty twenty three Master Electrician Open Book and calculations. And I tell people all the time it's great stuff. But you cannot be successful, in my opinion, on an exam without a proper study plan. And I tell you young folk out there, you that are studying for your Journeyman or studying for your master, look, you have to give somebody three months of your life

Speaker 3twelve weeks to transform your ability to learn and absorb code. It's going to make you a better electrician in the field. But it's a proven science, folks. We didn't just start this the other day. So even though I got all these haters out there, look, we have proven it.

Speaker 2That is a proven science.

Speaker 3The data shows how you study does that doesn't mean you can't do it quicker. I'm just saying that's what the data shows. We've been keeping information on people in the testing and how they move through the course the analytics for years. There's a way that it works. Okay, so we're not making that up. We're not blowing smoke anywhere now, it says, But the past week it feels like I haven't made progress and even regressed. That can happen when you're really doing code questions only and you're

Speaker 3only as good as the question. How it's written so that I could see that it says, went from passing the open book five in a row in the seventies and eighty rerange. That is still passing. But that is not good, my friend, getting a seventy on a non pressurized test like that, when you know that the pressurized test when you're in exam room that seventies passing and you're just barely getting seventies or barely popping over the eighties in an environment where you shouldn't be as stressed

Speaker 3is not great. Okay, So I'm not saying that to be mean. I'm just saying it's not great. So there is work that we can do. There's work to be done. So it said I went from doing the seventy to eighty three range to falling failing the past four Master Open Book tests with an average of sixty to sixty eight, says in some cases finished as I have been focusing on being faster, and another case is feeling like giving up. I don't know, man, I'm trying to be optimistic, but I am wondering if I should just give up.

Speaker 2Okay, let's deal with the last sentence first. No, you should ever give up, ever, And don't let it creep into your head to give up. You can do this, you can get this. You're so close. You're so close.

Speaker 3I think what's happening is you're letting tests taking anxiety rule you. Because I can read it in your stress. I can read it in how you ask the question, and so you have to step back, and I would tell you you have to study the right way. Now here's the one unique thing about me that I will tell you, and people will attest to this.

Speaker 2If you hear me, If you ever hear if you're in the earshot of.

Speaker 3This podcast and you hear this, go on and leave me a comment and say, Paul's right, he did tell me this. I do not like to sell courses to somebody that only have about a month or a month and a half or so left before they test. Why, it's just way too much information to absorb. You waited too long.

Speaker 2Now.

Speaker 3The reason that people sometimes end up buying is because they realize, well, if they fail it, they'll just keep studying it, and they already have the program and they and it's better off to at least try and they may get lucky.

Speaker 2I agree with that one hundred percent.

Speaker 3But I don't push anything on anybody with that short amount of time because it's a lot of information to absorb.

Speaker 2It literally is. And you know, we have hundreds of videos you can watch on fast tracks too. The course is very detailed.

Speaker 3We have a database of over eight hundred exam style questions and there's even some videos in that database as.

Speaker 2Well, very extensive.

Speaker 3So it's just a lot and you'll get into what's called the brain fog, and this is what this gentleman's having, and your scores will start to get worse, and then and then you'll start to creep in this anxiety and it's not gonna help you when.

Speaker 2It comes to test day.

Speaker 3Okay, So my advice here is one, do you have to take it on that date?

Speaker 2Can you postpone it?

Speaker 3Do you have enough time or they cutting you off for some reason and you have to take it?

Speaker 2Well, that's a different thing.

Speaker 3If that's the case, then what my recommendation to you is if you do get a course, you get something that is structured, and you go through it. You know whether now if you have a month, sounds like you've got a month that you should spend at least three times a week five hours or so studying. When it starts to get jumblie in your head, take a break, step away, come back, but at least that amount of time and really focus. And it also mix in some

Speaker 3of our videos over on the fast tracks too, especially our calculation stuff. So maybe one night do the questions in the course, do the course. The next night, just chill out and watch some videos. The next night, kill the course again. Next night, take a little chill Friday, kill the course again Saturday. Sunday, relax, enjoy family, relaxation, build up your energy again, and tackle it again on Monday.

Speaker 2You've got this, You'll get it. It's just the way you've been studying.

Speaker 3And I tell people out there all the time, and people will tell me, Paul, you're wrong. No, that's your unique experience where you say, no, I didn't need all that, I didn't need to study. I didn't need need to this, picked up the codebook and I passed well, La di da. I taught over one hundred thousand students. I keep track of how students do I keep I get a lot of feedback from students.

Speaker 2When I tell you something.

Speaker 3It's based on my experience doing this nearly forty damn years, not because you went and took a test. Your ability to pass an exam is different than somebody else's. So don't post a comment thinking that you're you understand how it works, because you don't. You understand how you work, but you do not understand how other people work. And I have been blessed to be able to have to work with different people with all different types of learning disabilities, people that really don't comprehend things very well. People that

Speaker 3are super super smart, but they overanalyze everything and that causes them to go down these rabbit holes that are going to affect their ability to pass an exam.

Speaker 2I deal with them all. So it's just like when I hit comments.

Speaker 3On YouTube and TikTok and Facebook and Instagram and all this where they make comments. People that do that, who make comments in the comments sections about certain things they have, you have no clue.

Speaker 2I'm telling you.

Speaker 3I'm talking to you out there that do that. You have no clue. You only know your experience. I have the opportunity to know thousands and thousands and thousands of students, have conversations with them on the phone, interact with them, be a part of their success, and yes, be a part of their failure to ultimately help them succeed. So that's why I control my comments on my platforms. You want to know the reason why I don't let people go down a tie rate on my social media because

Speaker 3I am not about to let some of you taint the content by saying smart alec things in there, or matter of fact things or certain things that are going to derail somebody's focus. Okay, I'll do that, not you. Okay, I'm the Dave Ramsey of code. I'm going to do that, not gonna let you do it.

Speaker 2Okay.

Speaker 3So again, at the end of the day, that's where we're at with it. So for you, my friend, just need to get in a good program. Whether it's ours or somebody else's, it doesn't matter. But you need to remember it has to be structured, okay, very structured. It means you go from unit to unit to unit. You don't jump around, you don't skip around things like that.

Speaker 2You have to be very focused. Okay, all right, all.

Speaker 3Right, everybody. That's about it for this episode. Hopefully you got something out of that. Also mentioned if you have not tried out trade Hog, give it a shot. For those out there, some people are getting confused that have our subscription. There's three pages that are important if you're a subscriber. There's the trade hog page.

Speaker 2There's the Office Hog if you have the trade Hog premium. And then there's the Study Hog.

Speaker 3The page that comes when you type tradehog dot or dot com or dot org.

Speaker 2That's the demo.

Speaker 3That's the front page that's only going to give you a couple questions.

Speaker 2You maybe one or two that is not your account. I've had people reach out and say I can't get into my account.

Speaker 3That's because you're not on your account page. You need to log in and go to the actual trade hug page.

Speaker 2Okay.

Speaker 3And the big difference is you'll see demo on the one that's a demo for the general public to try it out. You can't be on the demo. You got to be on the regular page. So go to the navigation and make sure you follow it and follow instructions. Okay, and that'll help you out. But the lot of great feedback from trade hog. It's always getting smarter. It's using the latest mixtures of claud and Grock and the latest chat GTP, and it also is using information that Jeff

Speaker 3we upload ourself into the database, so it's got our own little flavor as well to help try to answer these questions. And for those that are using study hog while they're exams prepping, it's a great resource because you can post questions in there of something you get in the course and you don't understand it, You cut it and paste it, post it in there and it'll give you a detailed explanation.

Speaker 2But before it lets you leave.

Speaker 3It's going to ask you a code question so that you get an endless supply of code related questions. So it's awesome platform. So for those that are interested in it, check it out. All right, all right, folks, that's it. I hopefully got something out of the day's podcast. Until next time, Stay safe, God blessed, keep working hard out there, God bless America, and let's just keep it rolling. Great opportunities are on the horizon for all of you to get into trade. So I look forward to chatting with you again.

Speaker 2Take care.

Speaker 1Thanks for tuning into another electrifying episode of the Master THENP podcast. We hope you're feeling more powered up and ready to tackle the electrical world with the knowledge and confidence you need to succeed. Remember, in the electrical grade, knowledge is power. Here to make sure you stay plugged into the latest insights, tips.

Speaker 2And code updates.

Speaker 1If you enjoy today's episode, don't forget to subscribe, leave us a review, and share the podcast with your fellow electricians and industry pros. Until next time, keep your tools sharp, your circuits clear, and you're my focused because here at the Master of the NEC podcast, we're all about sparking your success, stay safe, stay smart, and keep mastering the trade. From all of us here at Electrical Code Academy, thank you for all your support and we will see you

Speaker 1on the next Amazing Master of the NEC podcast episode

Open the transcript file

Hosts and Guests

Nobody is credited on this episode yet.

Credit the people on this episode

Be the first to rate this episode

More episodes

All episodes
  1. NiteNerds™ — The Future of Permanent Outdoor & Landscape Lighting Is Here!

    Nov 12, 202631 minAudio

    NiteNerds™ - The Future of Permanent Outdoor & Landscape Lighting Is Here! What if your home could look absolutely stunning every night of the year - with the touch of a button? Welcome to the world of NiteNerds™, where...

    Credit the people on this episode

  2. MASTER THE NEC PODCAST | E81 | Electrical Code Knowledge and 2026 NEC Updates PT 3

    Oct 18, 202655 minAudio

    ⚡ MASTER THE NEC PODCAST 🎙️ Hosted by Paul Abernathy Master Electrician | National Electrical Code Expert | Electrical Educator ⏱️ Episode Length: 55 Minutes ⚡ ABOUT THIS EPISODEWelcome to Episode 81 of Master The NEC,...

    Credit the people on this episode

  3. MASTER THE NEC PODCAST | E80 | Electrical Code Knowledge and 2026 NEC Updates PT 2

    Oct 18, 20261 hr 23 minAudio

    ⚡ MASTER THE NEC PODCAST 🎙️ Hosted by Paul Abernathy Master Electrician | NEC Code Expert | Electrical Educator⏱️ Episode Length: 1 Hour, 23 Minutes ⚡ ABOUT THIS EPISODEWelcome to Episode 80 of Master The NEC, where...

    Credit the people on this episode

  4. MASTER THE NEC PODCAST | E79 | Electrical Code Knowledge and 2026 NEC Updates PT 1

    Oct 18, 20261 hr 4 minAudio

    ⚡ MASTER THE NEC PODCAST 🎙️ Hosted by Paul Abernathy Master Electrician | NEC Code Expert | Electrical Educator ⚡ ABOUT THIS EPISODEWelcome to another episode of Master The NEC, the podcast dedicated to helping...

    Credit the people on this episode

  5. What The HECK? Do you have a 2026 National Electrical Code Course?

    Oct 3, 202641 minAudio

    The National Electrical Code is a minimum standard - but what does that actually mean? In this episode of Master The NEC, Paul Abernathy takes a deeper look at one of the most misunderstood concepts in the electrical...

    Credit the people on this episode