This episode is powerful because it focuses on a question presented to NECA as a Question of the Day. Listen as Paul explains the use of PVC on a fuel dispensing pump, and its use of Rigid Metal Conduit, and the question is about the bonding rules. Let’s break it down and expand on the answer provided by NECA to the individual who submitted the question. Listen as Paul Abernathy, CEO and Founder of Electrical Code Academy, Inc., the leading electrical educator in the country, discusses electrical code, electrical trade, and electrical business-related topics to help electricians maximize their knowledge and industry investment. If you are looking to learn more about the National Electrical Code, for electrical exam preparation, or to better your knowledge of the NEC, then visit https://fasttraxsystem.com for all the electrical code training you will ever need by the leading electrical educator in the country with the best NEC learning program on the planet. Become a supporter of this podcast: https://www.spreaker.com/podcast/electrify-electrician-podcast--4131858/support.
Audio and video play straight from the show's own hosting. PodSubs stores and serves no media.
Transcript
From the show. Tap a time to play from there.
Speaker 1Welcome to the Master of the NEC podcast, the ultimate destination for anyone passionate about the electrical trade. Whether you're a season electrician, an eager apprentice, or just someone who wants to dive deep into the world of electrical work, you've come to the right place. Join your host, Paul Abernavi, a true authority in the industry with over thirty eight years of trade experience, as he electrifies your mind with in depth discussions, expertips, and valuable insights that will keep you ahead of the curve. Each episode, Paul will illuminate
Speaker 1the complexities of the trade de code, the National Electrical Code, and share the latest industry trends, all while empowering you to take your electrical career to the next level. So gar up, plug in, and get ready to supercharge your knowledge because with the Master of the NEEC podcast, the power is in your hands.
Speaker 2Now get ready.
Speaker 1Here is your host, Paul Abernathy.
Speaker 2What what Up? What Up? What up? Everybody? Welcome to another episode of Master the NEEC. My name is Paul Abernethy, your host as always for this podcast uh series. If you've never listened to the podcast before, please take the time to go to your favorite search engine or even go to Spotify, Spreaker, Deezer, iHeartRadio, Apple Podcasts, Google Podcasts, whatever it is, and just search for Master the NEC podcast, all separate words Master the n EC podcast. Amy surprised.
Speaker 2We have nearly I think it's over a thousand episodes that talk about all types of things in the electrical industry, from contracting to electrical inspections and all kinds of topics. So you're bound to find something you want to listen to there. Just kind of scroll through them and I'm sure you'll get some little nugget of wisdom in one of the episodes you listen to, So check that out. Just search for Master the NEEC podcast. All right, So on today's episode, we're gonna kind of answer a question.
Speaker 2I posted this on our TikTok channel. And by the way, my social media is always going to be at Master the NEEC. So Master th n e C all one word, no gaps in there, no space is in there. There's a lot of people that try to copy you and you know, play hate on you. But again, the only thing you see for me, if it's from me, it'll be at Master the Nec. Anything else it's not me. So somebody puts something on social media and it doesn't have at Master the NEC on it, then it ain't me, okay,
Speaker 2so and it is what it is. People like me are always a target. So anyway, so I posted a screenshot of a Nika Question of the Day. And by the way, Nica does a great job providing these questions for electricians. It really helps you learn and grow. Now, the other night, I did a trivia we're testing a new feature over on on our YouTube channel. Of course, it also goes out on our Facebook channels as well. Again all Master the NEC, and there was questions and
Speaker 2I left them in there because they came from an online database that had a lot of errors in there, and I wanted to show people how easy it is to get questions and you think you're really studying hard and you're putting the time in and then of course the questions are wrong and you don't know because there's nobody there to help you. There's nobody there to tell you that this question is wrong, and so you just take it for the face value. And the whole point behind that, again is always a method to the madness, was to show people that there is no substitute for a structured exam prep program. Yes you may be able
Speaker 2to pass. Yes you may fumble through and get a seventy one on a seventy's and that's enough for you. That's fine. But if you're investing in your future and you really want to learn the NEC, that's just going to keep you from making mistakes on the job. You most certainly want to get into our structured and once you buy it, do you own it. It doesn't expire. So again, it's an investment in you over on our website fastracksystem dot com and coming soon also over on the Electricalguru dot net dot com and dot org as well.
Speaker 2So anyway, so there was a question. It was presented up there by NIKA, and I was interested to see how they would answer this question because I know that Michael Johnson doesn't do these anymore. Johnston, he doesn't answer these anymore. And it used to be Charlie that used to answer these years ago, and I don't know who's answering him now, but the answers sometimes seem pretty generic. Now. That's not to throw a flag at him and say anything bad about Nika, because they again they do a wonderful job for the industry. I would in no way
Speaker 2imply otherwise, but I always like to discuss some of these questions. So, being that this is a podcast and I haven't yet turned my podcast into video versions of podcasts, I know everybody keeps telling me I need to do that, but again, I'm still a purist when it comes to the podcast. I love to do a podcast and then make it where I have to paint you a mental picture. It's just kind of that makes it fun for me. Otherwise it just becomes mundane. And you will notice that
Speaker 2when it comes to podcasts for electricians. My podcast is the only one that's been running for over a decade, and it's the only one that's still current, still puts out episodes. A lot of them come, they go, they do five or ten episodes, and then they disappear. I've been doing this for the industry for well over a decade, and so well over a decade, so a lot of episodes to listen to. So here was the question that was presented to Nika, and I'll read you their answer,
Speaker 2and it's again, it's not necessarily a bad answer, and it is accurate to the level that they're going to answer it, but I also like to take questions and elaborate a little more on it because sometimes I think more is better in some of these questions. Okay, so the question that was presented, and by the way, if you want to go look this up, it's Anica dot Nika neet dot org and it's the Question of the Day feature and this was the March twenty seventh, twenty
Speaker 2twenty sixth Question of the Day. So it's easy for you to go and do that. Also, you can just go on to Google and type in Nika n Eca Question of the Day and it'll pop up for you too. If you can't navigate through the website and find it. Typically you go to the homepage and you got to go to topics and then codes and standards and then you'll see question of the Day. And I'm in the in this course, now it's going to be in the archive because now we're what April third or something like that. All right, so this is from March. Now here was
Speaker 2the question. It said, good morning, question of the day. I'm right, I'm wiring a motor fuel dispenser brand circuit using RMC elbows and conduit at the panel board and we're entering the fuel dispenser. It says PVC conduit is being used between the RMC elbows. Do I still need to comply with the bonding requirements of five to ten dot thirty B? And I think they got that wrong. It's it's not really five to ten, but that happens.
Speaker 2You know, people submit questions and you know I do it. You know, we get the numbers transposed. But I think he meant five zero one. But anyway, he's got five to ten dot thirty B at each end of the raceway. Right. So it says thanks in advanced Corey K. Great question, Corey. It is one that people will run into when they're out doing fuel dispensing. So the first thing that we recognize that fuel dispensing is the rules. Specifically, the fuel dispensing is an article five fourteen, So that's the first
Speaker 2place that you think about when you look into this. So there are rules, and again we're look at five oh one, and of course it's kind of changed a little bit for the twenty twenty six edition of the National Electrical Code. Everything kind of got moved over into five hundred to cover general requirements for hazardous locations. But we're going to kind of dig into the question itself and see if we can't tailor it down a little bit, because sometimes the devil is actually in the detail. So the answer here that I'm going to give you is
Speaker 2not necessarily wrong. It's just I'm going to show you how we can go and help somebody be a little deeper. And I think that's the difference between somebody who just flips open the codebook and somebody who really digs into the codebook and really dabbles into it like I do and a lot of you do out there there. Listen. So the answer is for Corey was yes, the bonding requirements in section five zero one dot thirty B of the twenty twenty three a NEC still apply. Well, of course you know it would, right because it's a metal race way, it's gottors in it, so we have that
Speaker 2that type of scenario. But I am going to dig a little deeper here. It says the PVC sections does not eliminate the need for bonding the metal components at each end. Five fourteen dot sixteen covers grinding and bonding of motor fuel dispensing facilities and points us to five zero one dot thirty in the twenty twenty three or five hundred dot thirty in the twenty twenty six, which covers the means and methods to accomplish this bonding. It
Speaker 2says for the twenty twenty six a NEC, since the requirements of five zero one dot thirty, five zero two dot thirty and five zero three dot thirty were identical, they were moved to five hundred dot thirty, covering the general requirements for hazardous locations. Okay, so all of that is one hundred percent accurate. I have no problem with that, and I'm not here again to say that Niko was wrong in this one. That is not my goal. I'm not out here to the poke fingers at anybody. We're
Speaker 2all helping each other in this industry. I will say that sometimes when you see a question like this, it we as any C experts, if you want to call it that us. For example, I do any C witness work, so experts witness services are available through our company, and companies can hire us to do very detailed analysis of things, and I've done that for jurisdictions. For legal cases. We have to look at all the little details sometimes, so I probably Now, obviously a question of the day. You can't fire a question back at somebody and ask them
Speaker 2do you know to follow up? It'd be hard to do that. But my first question, I would say, you say that you're using PVC conduit is being used between the RMC elbows. But I guess my question would be, is we know that there is a requirement in the National Electrical Code to the fact that the PVC portion, the buried portion is fine. The portion that goes from the rigid metal conduit elbows, which you kind of the
Speaker 2question kind of pointed out, has to extend up into the fuel dispensing system. You can't bring PVC up into it. Now, Again, there's going to be people out there that say, well, no, dub Paul, that's obvious. But if you look at the question, all it talks about is RMC elbows and the PVC conduit is being used between those. So typically there you know Nico's question is one hundred percent accurate. I mean, because the between is the portion between each elbow, and
Speaker 2it's not talking about the portion that's stubbing up. So the only reason that I bring this question up is because I like to remind people that the requirements of the code also are going to stipulate that that portion that and that final run where it goes the last two feet are going to actually have to go up into the fuel dispensing that has to be rigid or intermediate. Okay. So if we were to look at the code and
Speaker 2you were to have your your your code book handy, and you were to go to five fourteen, one of the areas you're going to look at is five to fourteen dot eight, right, And so five to fourteen dot eight is talking about underground wiring, and a says metal conduit, and it says threaded rigid metal conduit or threaded intermediate metal conduit with listed threaded fittings shall be permitted any portion of the wiring method that is below the surface of a class one division one or division two location,
Speaker 2and again directly under the pump's Class one division one. The portion out from the pump is going to be around it and surrounding it is going to be typically division two. Okay, So you're going to be passing through what may be no classified location as it's underground, and then it's going that this raceway is going to pass into a Class one Division two, and then as it continues on and comes up into the fuel dispensing, then it's going to be changing into a Class one division one. Right, So,
Speaker 2and you have various tables for that, right, five fourteen dot five B one we have, you know, there's various tables that talk about that and even shows some various illustrations throughout the code. Okay, all right, So that last portion that sticks up, okay, and for those that are watching, you know, the figures that we're talking about is figure five fourteen dot five. So it kind of gives you a layout of some things. And so it's five fourteen
Speaker 2dot five and there's a figure there that shows some fuel dispensing pumps and all the area that extends out from that. Okay, all right, that just wanted to kind of point that out. So if we look at fourteen eight of your twenty twenty six edition of the National Electrical Code, you can see that it clearly is going to allow you to use PVC in the ground part that is underground, and that is going to be in five to fourteen dot eight C and it's called non
Speaker 2metallic conduit. It says rigid polyvinyl chloride PVC reinforce thermo setting resin conduit, which by the way, is what I see most of the time, and some of those harder to deal with, but it will see that. And well also it talks about high density polyethylene conduit HDPE, which is also very resilient in those locations, but you could use PVC. It says, it shall be permitted. We're buried under not less than two feet of cover, so we have to be at least down two feet, regardless by
Speaker 2the way of what it may say in three hundred dot five the table when it's a depth cover table. Regardless of that, So remembers chapters one, two, three, and four are general, five, six, seven, and eight. Can supplement or modify any things in chapters one through eight. So in this case, you're in chapter five, it's going to modify or supplement any supplement anything that would be let's say in chapter three. Okay, y'all, y'all know how that works. So it allows it as long as there is at least two feet of cover. Now it says where PVC conduit,
Speaker 2RTC conduit or HDPE conduit is used. It says threaded rigid metal conduit or threaded rigid medal conduit IMC or intermediate metal conduit shall be used for the last two feet of the underground run to emerge or to the point of connection to the above ground raceway. Okay, so an equipment ground of conductor EGC shall be included to
Speaker 2provide electric continuity of the raceway system and from grounding of non current caring metal parts. Okay. So at the end of the day, what you've really got is rigid metal conduit could be underground. That'd be fine as long as it's covered by at least two feet of cover. And then of course you would have an adapter a changeover that would change over to a RMC or IMC, and then it would go up into the fuel dispensing and of course you're going to have a seal that's
Speaker 2inside of the enclosure of the fuel dispensing. You have a ceiling there so you can seal it off and then it comes all the way up. And so, yes, they got the question absolutely right. And the easy way to think about this is it's still a raceway. There are rules in the code that say when you have certain wiring methods, let's say that are underground, like elbows that are metal, you don't have to bond them if they're eighteen inches below cover you know, underground eighteen inches. But here, Since this is a brand circuit going out the fuel dispensing pump, it's just like any brand circuit.
Speaker 2So theegorty of an effective ground fault current path has to be maintained. So without getting deep into the code with that, obviously, if you're going to be running a circuit, you're gonna have to have an equipment ground right, and so in doing so, at each end of this theoretical run, you're going to have to when you get it in, you're going to have to make sure that you do your bonding at each end. And typically the equipment ground and conductor also serves a bonding role in that as well,
Speaker 2which brings me to the point if you're not reading my blogs, I just put out a blog the other day over on our website fasttracksystem dot com. It'll be down in the description. And on that website, I wrote a blog about the difference between grounding and bonding, and so you understand things like bonding jumpers, main bonding jumpers, system bonding jumpers, supply side bonding jumpers, equipment bonding jumpers. They all have a specific name, right, and then of
Speaker 2course you have equipment grounding conductors, you have grinding electrode conductors, all the type of stuff, so they all have an actual name. And I encourage you to go check out that blog. It's free, doesn't cost you anything. We have dozens of blogs on all kinds of topics, so just kind of scroll through them. You may find one that you want to save, print out. Feel free to share my blogs on your website or with other people. I just want people to learn, that's all. That's all I care about is I want people to learn the code
Speaker 2a little bit better and maybe make our next generation a little bit better. Okay, all right, so yes, so obviously Nika got it right in a sense that yes, nothing takes away the requirement. They still have to bond the metal components at each end. You're still gonna have to bond that rigid metal condo at each in and obviously since that last two feet it stubs up, has to be metal, so it's going to be bonded. And that's obviously gonna bond the elbow if you want to use rigid elbows that's fine, And of course the PVC
Speaker 2portion in there, well, obviously there's no bonding PVC, but you still have to have an equipment ground and conductor located within the raceway, So that answers that question. So my only additional insight to a person that submits a question like this is that I just want to make sure that when I'm answering a question that I cover all of the possibilities. So because somebody asks me about the PVC between RMC elbows, I owe them the courtesy
Speaker 2of reminding them that that metal has to continue on up into the last two feet up into the actual fuel dispenser, okay, or as it emerges from grade up to let's say the point where it originates as well. Okay, where you're going to have a seal off at each end, right. I think that it's important for me to make sure that folks understand that when I'm answering some kind of question of the day. So again, and I do encourage you to check out Nika's Question of the Day because
Speaker 2they are amazing. There's an archive and there's literally goes on for years. So again I'm gonna encourage you to go check that out. But again, I just wanted to elaborate a little more on that Nika question because I think that it warranted a little more detail and a little more reference to the installer. Corey. Corey, if you're listening out there now, I have no doubt in my mind that you use rigid elbows, and you contended it with rigid on all the way up into the fuel dispensing.
Speaker 2I have no doubt you did that. Okay, I have no doubt at all, because at some point you're gonna have to be able to put in a clean out or seal, and I should clean out a seal, and the seals of those are typically designed to work and thread into rigid metal or intermediates. So I have no doubt that you did that. But I always feel like it's just a little extra to throw that out there and tell somebody, Okay, all right, folks, That's all I really wanted to do on this episode. We're gonna be cranking up a lot more podcast episodes. If you like what you hear, and you've got questions that you want
Speaker 2me to answer on upcoming episodes, just do me a favor. All you got to do is go to our website fasttrackssystem dot com, and I'll put a link in the description of this video as well that you can simply just click and it'll take you to the Let's Ask Paul feature. It's a way for you to be able to ask us questions directly and we will do our best to answer them in an email response or, if selected, on an upcoming podcast. All right, folks, till next time,
Speaker 2Stay safe, God blessed. We'll catch you on an upcoming episode a Master the NEC podcast. Take care.
Speaker 1Thanks for tuning into another electrifying episode of the Master the ANC podcast. You're feeling more powered up and ready to tackle the electrical world with the knowledge and confidence you need to succeed. Remember, in the electrical trade, knowledge is power, and we're here to make sure you stay plugged into the latest insights, tips.
Speaker 2And code updates.
Speaker 1If you enjoy today's episode, don't forget to subscribe, leave us a review, and share the podcast with your fellow electricians and industry pros. Until next time, keep your tools sharp, your circuits clear, and you're my focused because here at the Master of the ANEC podcast, we're all about sparking your success. Stay safe, stay smarked, and keep mastering the trade from all of us here at Electrical Code Academy. Thank you for all your support and we will see
Speaker 1you on the next Amazing Master of the NEC podcast episode
NiteNerds™ - The Future of Permanent Outdoor & Landscape Lighting Is Here! What if your home could look absolutely stunning every night of the year - with the touch of a button? Welcome to the world of NiteNerds™, where...
⚡ MASTER THE NEC PODCAST 🎙️ Hosted by Paul Abernathy Master Electrician | National Electrical Code Expert | Electrical Educator ⏱️ Episode Length: 55 Minutes ⚡ ABOUT THIS EPISODEWelcome to Episode 81 of Master The NEC,...
⚡ MASTER THE NEC PODCAST 🎙️ Hosted by Paul Abernathy Master Electrician | NEC Code Expert | Electrical Educator⏱️ Episode Length: 1 Hour, 23 Minutes ⚡ ABOUT THIS EPISODEWelcome to Episode 80 of Master The NEC, where...
⚡ MASTER THE NEC PODCAST 🎙️ Hosted by Paul Abernathy Master Electrician | NEC Code Expert | Electrical Educator ⚡ ABOUT THIS EPISODEWelcome to another episode of Master The NEC, the podcast dedicated to helping...
The National Electrical Code is a minimum standard - but what does that actually mean? In this episode of Master The NEC, Paul Abernathy takes a deeper look at one of the most misunderstood concepts in the electrical...