The Truth About GFCIs - UL 943, Floating Generators, Bonding & Current PathsThere may be more misconceptions about GFCIs than almost any other electrical safety device. Does a GFCI need an equipment grounding conductor to work? What does the toroidal sensing coil actually monitor? Why might a GFCI behave differently on a truly floating generator? And what happens when a bonded-neutral generator is connected to a dwelling through an interlock where the neutral is not switched? In this episode, Paul Abernathy breaks down the actual operating principles behind UL 943 Class A GFCIs and explains why understanding the current path is far more important than simply memorizing terms like “grounded,” “bonded,” or “floating.” We explore how a GFCI compares current leaving and returning through its monitored conductors, why an equipment grounding conductor is not required for differential-current sensing, and why a GFCI should never be thought of simply as a device that “detects current going to ground.” You'll also learn why a truly floating generator may have little or no first-fault current path, how a second fault can completely change that condition, and why connecting a generator to a dwelling can change its electrical relationship to ground. Then we tackle one of the most misunderstood generator issues in the trade: Bonded neutral vs. floating neutral. If a generator is connected through an interlock or transfer arrangement that does not switch the neutral, the generator neutral remains connected to the dwelling's grounded conductor system. Adding another neutral-to-ground bond at the generator can create parallel paths for normal neutral current through equipment grounding and bonding conductors. We also cover: How a GFCI's toroidal current transformer actually works The difference between GFCI protection and overcurrent protection Why a GFCI can work on a circuit with no EGC Why “GFCI protected” does not mean “equipment grounded” Why touching hot and neutral can still produce a dangerous shock without creating a GFCI-detectable imbalance Why some plug-in GFCI testers may not operate properly on an ungrounded circuit The difference between the integral TEST button and an external tester Floating generators and first-fault conditions Bonded-neutral generators Switched vs. unswitched neutrals Separately derived generator systems Parallel neutral-current paths Why a ground rod is not the normal branch-circuit fault-current return path How grounding, bonding, GFCI protection, and fault-current paths all work together The goal of this episode isn't to replace one electrical slogan with another. It's to teach you how to draw the circuit, follow the current, and understand what the protective device actually sees. Because when you understand the current path, the misconceptions surrounding GFCIs, generators, grounding, and bonding start disappearing. Current out. Current back. If they don't match, the GFCI becomes interested. Hosted by Paul Abernathy of Electrical Code Academy, Inc. #GFCI #UL943 #ElectricalCode #NEC #Electrician #ElectricalTraining #ElectricalSafety #Generator #PortableGenerator #Grounding #Bonding #GroundFault #ElectricalTheory #MasterElectrician #ElectricalEducation Become a supporter of this podcast: https://www.spreaker.com/podcast/electrify-electrician-podcast--4131858/support.
Audio and video play straight from the show's own hosting. PodSubs stores and serves no media.
Transcript
From the show. Tap a time to play from there.
Speaker 1Welcome to the Master of the NEC podcast, the ultimate destination for anyone passionate about the electrical trade. Whether you're a season electrician, an eager apprentice, or just someone who wants to dive deep into the world of electrical work, You've.
Speaker 2Come to the right place.
Speaker 1Join your host, Paul Abernavi, a true authority in the industry with over thirty eight years of trade experience, as he electrifies your mind with in depth discussions, expertips, and valuable insights that will keep you ahead of the curve.
Speaker 2Each episode, Paul.
Speaker 1Will illuminate the complexities of the trade de code, the National Electrical Code, and share the latest industry trends, all while empowering you to take your electrical career to the next level. So hear up, plug in, and get ready to supercharge your knowledge because with the Master of the NEEC podcast, the power is in your hands. Now get ready. Here is your host, Paul Abernavish.
Speaker 2What up, everybody? Welcome to another episode of Master the NEC, the podcast where I talk to you about anything electrical code theory, application, hiring, firing, marketing, promotion, whatever it is about the electrical industry. I'm here to help you and the answer questions for you. Of course, you can always submit me questions over on our website fastracksystem dot com. You go over there and you'll see in the navigation that so let's ask Paul link. Click that link and you could submit a question to me. I'm more than happy to answer those in podcasts, and in many cases
Speaker 2I will respond directly to you personally in an email answering your question. But it's been a great resource now for many years, and I'm going to thank everybody out there for participating in it. It really helps us get answer questions and to spill some myths out there or misconceptions that are obviously running rampant on all types of social media platforms today, and so we like to make an effort to kind of clear those things up when we get an opportunity. Today's episode is going to be a very impactful one, so I want you to really
Speaker 2understand it. This one could be about an hour long, so it's going to be long. I want to tell you that upfront, because we are going to unpack a lot of things today, talk about misconceptions. We're going to talk about GFCI function, We're going to talk about the misconceptions. We're going to talk about generators bonded versus unbonded or floating generators in the application, the hazards that it can be involved with both, how you would use each one of them properly. I'm going to explain certain concepts that
Speaker 2are going to be very elementary in how I explain them. So again, I'm hoping that you listen to our podcast, but I'm hoping that this one in particularly, you do listen to in its entirety, because again, there's so many things that we're going to unpack in this one. And I've been waiting to do this one because it's just it's one of those things where I do videos on generators in GFCIs and understanding their function, and so many
Speaker 2comments come in about the GFC. I will work regardless of this or that or this or that, and you're wrong, Paul, and I'm like, Okay, well today we're going to explain all of that so that when you walk away from listening to this podcast. And y'all all know I love podcasts versus doing videos because I believe that people should sit down with headphones on and just listen to a podcast or take your shower and have one of your devices in there that plays a Bluetooth. And I really think that people probably don't listen to podcasts because in
Speaker 2a podcast, I have to paint you a mental picture, and painting you a mental picture forces me to be as detailed in my verbiage as possible. And I think that's what ends up making better electricians, because you're able to listen, extract it, and apply it. And that's why I just love podcasts, and I love If I didn't do another video ever that you know, I wouldn't care. I just love podcasts, right, and because I think that it's a medium that is old school radios, radio old school.
Speaker 2I've been doing this well over probably close to two decades now when it comes to podcasting, and it's just a medium that makes you have to concentrate, and so I like doing it. So today we're going to talk about the truths about GFCIs. We're going to talk about UL nine forty three. We're going to talk about floating or unbonded generators. We're going to talk about current path, current flow, how they operate. We're going to get rid of some myths and try to give you some real fundamental knowledge that you can hopefully share this with other
Speaker 2people accurately rather than spreading misconception. Now, there are few electrical devices that electricians use every single day that are missingunderstood more than ground fault circuit interrupters, very few. There's a lot of people that just think they understand ground fault circuit interrupters GFCIs and how they function, and they really just take it for granted. In fact, I could probably ask ten electricians how a GFCI works, and you're probably going to get ten different answers. You might have
Speaker 2one say, well, Paul, its sense is current from the ground. Then you have another one that says, well, a GSCI doesn't even need a ground to work. Then you'll have another one that might say, well, then, how in the world can it be a ground fault circuit interrupter if there is no ground when the code allows you to use it, when there is no equipment ground present in certain applications of existing installations, they might say that. And so that's where the wheels start coming off of a conversation, because all three of these people's answers are focusing on
Speaker 2the term ground when we really need to talk about is current, and so I think the misconception is when you see ground fault circuit interrupter that they forget. This whole conversation needs to forget about the term ground that's just the name of the device. We need to understand how the current, where did the current leave, where did the current come back, and did all of it return through the conductors that the GFCI is actually monitoring. That's
Speaker 2the entire foundation of today's podcast. We're going to take it one step further. We're going to actually put that GFCI on a portable generator. We're going to use it and explain it. When there's a floating unbonded generator winding, which you know, you might get a generator that that is, you know, unbonded generator. It might have been previously connected to a dwelling and now you're taking it and use it as a work generator out on a project and it's been altered in some way. Or you may have a bonded generator that ultimately in a storm you end
Speaker 2up connecting it to your dwelling or something like that. So we're going to we have to unwrap all of that stuff. So not only are we going to explain the applications for generators and things like interlocked and transfer switches, because I think that's important topic today. But we're also going to understand the relationship of the GFCI device that how it interacts in these systems. Okay, So that's what we're going to kind of unpack today. Ok So, we're going to connect that generator to a dwelling through a
Speaker 2panel interlocked and it doesn't swits and virtual and then when we're finished, you're going to understand why no return path can create a problem, but too many return paths can also create a problem. And sitting right there in the middle of all of that is this simple GFCI device that's asking did the current that went out come back through me? And if it didn't, how in the world can I function properly if it all came back
Speaker 2through me and I didn't notice an imbalance. All of that's going to be talked about in today's episode and clear all of that stuff up for folks. Okay, So when we start into this, I just want to for a second, let's let's focus on something I want you to temporarily, Okay. And when I say temporarily, I want you to temporarily forget the name ground falt circuit interrupter. I know that sounds strange, but the word ground causes people to create this mental picture that isn't entirely accurate.
Speaker 2They picture a GFCI somehow monitoring the green or bear equipment ground and conductor. That's what they picture. That's what you see when you see the word ground. So I want you to forget the word ground. Okay, as we do this discussion, right, almost like there's a they think of the way that it monitors it. It thinks it's dedicated to that equipment. It thinks it's almost like there's this electronic policeman sitting inside this receptacle watching the ground
Speaker 2wire saying, hey, hey, I just saw electricity on that ground wire. I need you to trip. That's not fundamentally how a class AGFCI operates, Okay, So we want to make sure we're clear with that. So we're gonna we're gonna definitely hit some fundamentals for you under UL nine forty three, that is a standard for ground fault circuit and interrupters. If you're not aware of that, you will identifies a Class A, which is typically what you're going to be using, for example, in normal personal protection for kitchens and bathrooms whatever in your dwelling. Those are Class
Speaker 2A GFCIs and under UL nine forty three, they're they're called personal for Personnel Protection devices. And this is the receptacle type GFCIs portable gfcies used on construction sites. Circuit breaker type GFCIs. U L currently describes UL nine forty three class devices as intended for grounded neutral systems. That's the intended system that these things are supposed to be
Speaker 2used on. Fundamentally important, and when we're talking about typical class A circuit breakers, GFCI ULL identifies that Class A markings with a six MILLIONMP your maximum ground fault trip threshold. Now you've heard us all say nominal five millionamps, because the way it is, if it's four or less, it's not gonna detect it, and if it's six or more, it's gonna detect it. So we usually use five million amps as the nominal because six, right is the max.
Speaker 2Four is the men, So we always just say five millionamps. That's the that's the nominal, okay, now, but what is actually what is it actually sensing? That's what's I guess the most important thing. What is this GSCI really doing? And that's what's going to matter. So in order to do that, we need to crack it open. And when we crack it open and we start digging into this, you'll hear a lot of people talk about this little GFCI sensing transformer. Is the doughnut. Okay, it's inside the GFCI.
Speaker 2It's a sensing transformer. Electricians will commonly describe it as again a little doughnut or a toroidal current transformer, or you might hear somebody say it's a toroidal coil. Okay. So on a typical one hundred and twenty volt branch circuit or just to say one hundred and twenty volt circuit, in general, the unngrounded conductor and the ground to conductor, both of them actually pass through that sensing transformer, that doughnut. So let's keep this ridiculously simple. Okay. If I've got
Speaker 2five amps leaving through the ungrounded conductors going through that toroidal coil or that doughnut, and I've got five ampiers returning through the ground to conductor through that toroidal coil, that sensing transformer, and obviously alternating current. It's traveling in opposite directions, So the current's moving in opposite directions through that toroidal sensing coil. There, each conductor creates this magnetic effect, right and expanding and collapsing magnetic field. You probably learned
Speaker 2that back in when you were going through trade school, Right, expanding rapidly expanding contractions is the current changes directions and alternating current. Well, in this case, when you run the two conductors through it, then the magnetic effect is essentially canceled out. So the coil is not going to be picking and sensing anything in the circuitry. So from the perspective of the sensing circuit, current out equals current back. Everything is good. It's not picking up any not picking up any magnetic field. It's just canceling itself out. Okay,
Speaker 2So the GFCI doesn't care that five amps is flowing. That's important. Five amps doesn't bother it. Shoot, ten amps doesn't inherently bothered THEFCI sensing function. What the GFCI actually cares about is the difference between the currents passing through its sensing transformer. That doughnut. Okay, that's what it's sensing. So now let's create this fault condition. So I've got five amps that is going out through the breaker through
Speaker 2that torotal coil, leaving on an unngrounded conductor. Okay, but somewhere in the path, I've only got four point nine to nine five ampis coming back through the grounded conductor. I'm missing five millionampiers. Well, you have to ask yourself, now, where did that five million ampiers go? Here's the important part. The GFCI doesn't have to know where it went. It just knows it didn't come back through the monitored conductors.
Speaker 2Maybe it traveled through an equipment grounding conductor. Maybe it went through a metal bonded metal. Maybe it went through piping hell, maybe it went through concrete, maybe even through the earth sadly, maybe even through a person's body. But whatever path it took to get back to the source, that current bypassed the normal monitored return path. It did not fully come back on the neutral And now that
Speaker 2magnetic field doesn't completely cancel out because now there's a differential current, So it does create an imbalance that creates the magnetic field, and that's what gets the gfci's attention. Even Osha describes GFC operations similarly, they say in OSHA, it says the device compared compares current leaving on the ungrounded conductors with current returning through the neutral, and responds when an imbalance occurs. OSHA also makes it clear that
Speaker 2at GFCI monitors current leakage, it is not a device for verifying continuity of an equipment ground and conductor. That is not what its function is. It is looking for imbalance on the intended circuit path. So here's our first big takeaway before we dig even so deeper into this that you start going, Okay, this is getting deep. A GFCI is functionally a differential current device. It is not
Speaker 2a green wire or bear wire or equipment ground and conductor detector. That is not what it functions. So let's get rid of that right up front. Next, let's talk about GFCI versus circuit breakers. Now, let's clear up another misconception. A GFCI isn't simply a tiny circuit breaker. Y'all all know this. A normal fifteen or twenty eight brand circuit overcurrent protected device is concerned primarily with things such as overload short circuit things like that. Okay, that's its main
Speaker 2function overload short circuit ground fault. A GFCI has a completely different mission. So let's kind of picture ourselves here. Imagine I've got an appliance that's on this circuit. It draws eight amp years, that's normal, it's fine. Eight amps. Goes out to the load loads, drawing eight amps. Eight amps comes back through the same circuit through the neutral through the toroidal coil boom. No magnetic field is generated,
Speaker 2cancels each other out. GFCI doesn't care. It's like, I don't care. Everything's good on my end. Take that same circuit. Somewhere in that circuit path. Let's say we have insulation deterioration somewhere, and let's say we have five million amps leakage onto something else, some other composed it. It has another return path. Okay, well, my normal breaker still sees eight amps. That's all it's saying. As long as he
Speaker 2goes out and comes back. Far as the breaker's concerned, Dude, I'm continuing to run. I'm good, breaker says, I'm fine, let's go. It doesn't care. That's nowhere near the overcurrent operating region for that overcurrent device, so it does not care. But the GFCI sees eight ams out, but only seven point nine ninety five AMP years back. Now we have a difference. That's why GFCI protection and overcurrent protection should
Speaker 2never be taught as though they're doing the same job. They are not doing the same job and never have done the same job. Now, you may have a device that does all those things, like a typical GFCI circuit breaker is going to have integral overcurrent protection, but it's also going to have the GFCI protection built into it, and it still serves as a breaker obviously, but don't interconnect the two. That's also why equipment, ground fault protection, personnel, GFCI protection, AFCI protection, and ordinary brand circuit overcrip protecting
Speaker 2should not be thrown into that one bucket just because they can all cause a circuit breaker to actually open. Because they use different technologies, they're looking at different hazards, and they have varying operating criteria. They're all operating differently, so we don't lump them in the same basket. They all have their own purpose in their own role. Now, the next thing that we run into it's logical, is say, but wait a minute, wait a minute, wait wait wait
Speaker 2wait wait wait Paul, there's no equipment ground. Okay, So now we get to one of the biggest myths we have out there. Somebody finds an old two wire brand circuit. Okay, we've got an ungrounded conductor and we've got a ground to conductor, just the black and white to our system. But we don't have an equipment ground to conductor. And somebody will say you can't use a GFCI because a GFCI needs a ground to operate. Well, hopefully by now
Speaker 2you understand that that is not the case. It doesn't need a ground to operate. The GFCI doesn't require an equipment ground and conductor through its sensing transformer. It doesn't run through its toroidal coil. What it needs is a difference between the monitored conductors, the hot and the neutral. That's what it's looking for. So the GFCI is not taking the place of ground connection or the establishment of
Speaker 2the ground the lower Peden's effective ground for current path. That's not what it's replacing. Let's remember what the GFCI is doing. It's only looking for the differences between the monitored conductors when it comes to current flow. That's it. So now let's say a person contacts the energized conductive part. Now current leaves the young grounded conductor through the person, and let's say it finds some other conductive path back
Speaker 2to the grounded system and ultimately back to the source. This is why in a system like a bathroom, if it's an existing and it's a two wire system, you replace it with the GFCI. The concept is there is no equipment ground present, but we want to afford some type of safety because it could be where you become in contact with some other alternative path like metal piping system or something else that ultimately is maybe bonded back to the source. Now, maybe this path is the earth,
Speaker 2maybe it's a grounded pipe, maybe it's structural metal, maybe it's some other the conductive object in close proximity. The specific path isn't really the point. The point is that the current that left through the monitored ungrounded hot conductor, it actually doesn't return on the monitored grounded conductor. It may get back some other way, but it's not coming back on the intended path. Now, the GFCI sees this imbalance. That's why GFCI protection can still provide important personnel protection
Speaker 2on an otherwise ungrounded brand circuit. But let me be very clear, installing a GFCI does not magically create an equipment ground a conductor. Another falsehood that I see a lot of times on various home inspector channels and forums and platforms and electricians that say, oh, just throw a GFCI in THEAR, that'll replace the need for an equipment ground. That is not what it does. Okay, if the receptacle has no EGC equipment ground conductor, then guests what it
Speaker 2still has NOEGC. All you're adding is differential current protection. That is why you're adding the GFCI, and it's better than nothing, especially if something happens and the system deteriorates and it finds another path back and that path is through you, you definitely want to make sure that that GFCI is going to function. But as we saw earlier, if there's no return path and there's no current flow,
Speaker 2so it can't solve everything, but it does create a situation where if you did have that alternate path back to the source and you become in contact with that, it will protect you or make an effort to protect you. Right, So you are not magically grounding the enclosure grounding the appliance or installing a low impedance equipment grounding conductor back to the source. You're not doing that when you put that GFCI into a two wire ungrounded system or brand circuit.
Speaker 2That's unngrounded. Okay, just because you put that GFCI in there, you're not creating a magical grounded system at that location. That's not Those are totally different concepts. Now, I guess that leads us into understanding the return path is everything, and understanding current flow. So this is where I want to actually slow down a little bit because this concept takes us directly into generators, and we're going to start. We understood the basics the concepts, and we spent twenty
Speaker 2three minutes explaining this, so you truly should understand how a GFCI functions and how the current path has to flow, and what the GFCI is looking for, what it can do, and what it can do. But then we had to slow down a little bit because we have to think of this return path. Now, electricity needs a circuit to flow. I know this sounds elementary, but again that's why you have a switch. You flip the switch, you break the circuit. Path, you flip the switch back on, you close the path in a circuit and a current flows. Very simple concept, right,
Speaker 2But electricians sometimes becomes so focused on the grounding rules that we actually stop drawing the actual circuit in our head to understand that it has to be a complete system in order to function. For current to flow, remember, current does not simply disappear into the earth, doesn't dissipate out. Current does not leave a generator, go to the Earth and then all of a sudden just vanish. For sustained current to flow, we have to have that path back
Speaker 2to the source, a closed loop. So if circuits leaves circuits, current leaves the source through a person and travels into the earth. I want you to ask me something, Paul, how does it get from the Earth back to the source winding? That's an incredibly important question, and that brings us to floating generators or unbonded generators. So you have to always ask yourself, Paul, it could float through me,
Speaker 2and it could go through me to the earth, but doesn't it have to get back to the source. How does that happen? And so let's talk a little bit about a floating generator. An unbonded generator if it's a truly floating generator or an unbonded generator. So let's take this example. I have a portable generator completely by itself. You're used for you know, maybe work job sites, totally isolated. It's not hooking it up to a dwelling. It's just
Speaker 2just a generator you pull out to work on a job site. It isn't connected to a dwelling. It's just sitting there. You take it out, you use it for a project for purposes of this example, the winding is truly isolated, so it is a floating and neutral. There is no connection between the neutral, there is no connection to the frame. It's just a truly isolated generator. Neither circuit conductor has any intentional connection to the generator frame or the earth. Okay, none of that. No, So electrically,
Speaker 2what we've got here is a floating source, an unbonded floating source generator. Now you all makes an important point here. You on nine forty three Class A GFCIs are intended Okay you hear me, intended for use in grounded neutral systems. That's worth remembering. While we're discussing this hypothetical isolated source. Now, let's take one conductor from that generator winding and run
Speaker 2it through a GFCI. Okay, so we're we're creating this system in our head. I'm going to go from the generator winding out and I'm going to be supplying this GFCI receptacle out. Let's imagine somebody contacts that conductor while standing on the earth. Okay, so it's coming from the floating generator, from the winding through the GFCI, and it's maybe it's in a chord and I'm coming in contact with it and I'm standing on the earth barefoot. Let's
Speaker 2just say that, let's follow this circuit how it would flow from the generator winding through the conductor, through the person onto the earth. And then remember that important question we have to ask, and then what That's an important question, in't it? And then what happens? Where is the connection from Earth back to the other side of the generator winding to complete the circuit. If the winding is truly isolated,
Speaker 2there isn't an intentional one. So what we have is to person to Earth and one big ass question mark, we haven't completed the circuit back to the source. That means that the first conductor to Earth contact may result in very little current because we haven't intentionally provided a conductive return path to the source. It's not there. And now think about that GFCI. If little no current flows
Speaker 2outside of the monitored conductors, what differential current is the GFCI is supposed to be detecting Because there's potentially none, that doesn't necessarily mean the GFCI failed. That doesn't mean that it's no good. There may simply be insufficient differential current to actually make it operate. OSHA has historically recognized that electrical characteristics in certain isolated portable generator configurations. It's
Speaker 2construction rules and interpretations distinguish generator circuits whose conductors are insulated from the frame and grounded surfaces from grounded generator systems. Distinct difference in the different types from an isolated portable generator versus one that is actually bonded to the frame. Now, nobody is going to hear that and say, quote, so, well, yeah, actually,
Speaker 2I think somebody's gonna hear that statement. They're gonna actually hear that statement and say, wait a minute, wait minute, Paul, I'm in interpreting from that statement, now, is that a floating generator can't shock you. Absolutely not what we're saying. So don't make that leap. That's what I hear this all the time. They say, well, Paul, if it's not you know, if it's not bonded, then there's no way for crying to get back, there's no way that you can get shocked. That is not true. Now, let's do not make that leap. Real systems aren't perfect classroom drawings.
Speaker 2In reality, we've got capacitance, we've got insulation leakage, we've got connection loads, we've got electronic filtering damage that could take place between point a point B. We have multiple pieces of equipment that could be involved. Things that are plugged into the generator, moisture, water, rain, other contaminants, and possibly another fault somewhere else in this system. Any of those things could establish a reference or create another current path,
Speaker 2and once that happens, everything changes. So it gives you the false impression that the floating generator is safer. So the lesson isn't a floating generator is shock proof. The lesson really is the first conductor to ground contact on a truly truly isolated source may not establish the same fault current path that exists on a grounded system. Dude,
Speaker 2that's not myth, that's electrical theory. That's truth. And understanding that theory makes the rest of this discussion gonna be much easier for you to understand complete system, complete loops, and how it gets from point A to point B. Now, since we established it that first one may not cause the device to operate, we need to think about what about a second fault. So now let's leave that first fault in place. It's there, it's sitting there. It could
Speaker 2create live parts. It could be energizing something that's waiting, like a ticking time bomb. Now, somewhere in the floating generator system, let's say one conductor becomes unintentionally connected to the frame or some grounded conductive component. Maybe somebody didn't even know what happened. Maybe somebody contacts an opposite conductor. Okay, one side of the generator, winding through the person, through the grounded conductive through the grounded conductive system, through our
Speaker 2first fault, and then back to the opposite side of the generator, winding by the second fault. Well, guess what now, we have a complete circuit. Now significant current can flow on that generator that you thought was unbonded floating, and due to a series of events, can create this secondary condition. Now that current can flow, and if somebody, if some
Speaker 2of that current bypasses one of the conductors monitored by the GFCI, now we've created that differential current the gfc c I was designed to detect. So again, follow the current. Don't simply memorize it. Floating generators good, floating, bonded generators bad. This is not electrical education. That is not education by saying that. Don't simply say floating generators are good, bonded
Speaker 2generators are bad. It's much more detailed than that. That is not good electrical education to say that. You have to understand the circuit and understand when you would use one over the other. And we're going to get into that because now I'm going to go from that generator that's sitting out in a field that needs to be bonded so that if it comes back on the earth it can come through the frame. And that is truly a separator ive system. It's sitting there, it's not connected to a dwelling or any other system. Okay, that is
Speaker 2a situation where we could actually have the GFCI function giving it that proper path Okay, back to the from the from the ungrounded conductor out back through the winding to the opposite. So that's what we're establishing. Okay, not gonna work for a floating generator for use out in the job site. Now let's change it a little bit. Let's connect this generator to the house. This is where
Speaker 2things get really interesting. Take the same portable generator that we've been talking about. Now we're going to connect it to a dwelling using a proper generator inlet, and we're going to put a panel board interlock arrangement in it. We're gonna not switch the neutral so the interlock mechanically prevents the utility mean breakers and the generator backfed breaker from being one at the same time. We get that that's the whole purpose of the interlock. So we're preventing the generator from energizing to ustility supply conductors while normal source.
Speaker 2While the normal source is connected, we don't want the generator to be connected to it. Good, that's all done, But there's but here's the part that gets overlooked. A conventional circuit breaker interlock does not actually switch the neutral. We're transferring the two ungrounded conductors line one, line two, but the grounded conductor the neutral remains connected. So when the generator plugs into the dwelling, the generator neutral connects directly to the dwelling's neutral system, and somewhere upstream at
Speaker 2the service equipment, that grounded conductor is already bonded through a main bonding jumper to the equipment grounding system. Now think back to our floating generator scenario. When it was sitting out in the yard by itself, it's neutral could truly be floating. But once I connect that same generator connects its neutral to the dwelling through an unswitched neutral arrangement.
Speaker 2That generator winding is now now has a connection to the dwelling's grounded conductor system and ultimately to the service bonding point. So in this case, the situation or the electrical situation has totally changed. This is a major concept. So people will say, my generator has a floating neutral. Okay, floating when floating while standing alone or floating while you're connected.
Speaker 2If you connect it to the premise wiring system where it intentionally connects to the neutral and that neutral remains solidly connected to the service's bonding point. Those aren't necessarily the same electrical condition. It's vastly important that you understand the hazards involved with this, and of course I'm gonna break this down, but that is, you can't just take one generator that's used in one application and then magically use it as another application and say, dude, it's just a generator. It's fine. So Ocean and the NEC will
Speaker 2define separately drived systems as it is very distinctly, and it's clear a generator system is not separately derived when its grounded conductor remains sodidly interconnected to the service supplied grounded conductor. You're not switching the neutral. If you're not switching the neutral, then it is not separately a separately derived system. It's just another system, just like an oven, just like a range. Okay, so that brings up the
Speaker 2next giant misconceptions. Why don't I just bond the generator's neutral. So we started out with this floating generator, right, and we're used it out in the field, which was a wrong application because it needs to have a bonding jumper in it, and then we moved it over to the dwell and we use the same floating generator. Okay, well we're going to see where that would be right and where that why that would be right versus using a bonded one. So the question now people say, well, that's
Speaker 2majority of the generators that I buy out in the to use in the field, not on the house, but to use out on a job site that they typically are going to be a bonded generator. I know, I've got mine. I got a Westinghouse ninety five hundred. It had the bonding jumper in it. It's a portable generator. I use it for my house. I have an interlock system, so I had to move the bonding jumper out of it. And this is fundamentally so people ask yourself, well, why don't I just bond the generator's neutral. So somebody says, Paul,
Speaker 2you spent the past thirty eight minutes explaining how a floating source may not have a ground fault return path. Why don't I just bond the neutral to the generator's frame. Well, because you're connecting that generator to a dwelling with an unswitched neutral, the neutral is already connected back to the dwellings system bonding point. So you don't just take a floating generator that was improperly being used out in the
Speaker 2field and all of a sudden put a bonding jumper on it and use it on a dwelling, and people do this when it's exact opposite. You want to be a floating or unbonded generator if you're gonna look it to your dwelling and you're not switching the neutral. And then if it's a portable generator out in the field, then you want to have it be a bonded generator. So people ask us, well, why don't I just take my my generator, if it was a floating generator, why
Speaker 2don't I just bonded shit, I'll just run a connection from the neutral to the front. I'll just bond it. Well, because when you're connecting that generator to a dwelling with an unswitched neutral, the neutral is already connected back there. So if I add another neutral to frame connection at the generator, here's what I'm doing. I'm creating something that is potentially hazardous. I'm creating two neutral ground connections. And the code is very clear about not creating case to neutral connections downstream of the of the panel of the
Speaker 2main panel. So if I have two neutral ground connections, one at the dwelling service equipment, and I have another one at the generator because I put I used a bonded generator on a dwelling, or I took an unbonded or floating generator and I put this jumper in there, and now I created a bonded because some electrician told me to. Now I've got a problem. Because now if you follow the circuitry, you follow the path, here's what you've got. You've got this generator neutral is connected to
Speaker 2the dwelling's neutral. Okay, so the generator frame is connected through the equipment grounding conductor back to the dwelling equipment grounding system. Right, Because we're running the generator, it's a four wire system. We're gonna run a neutral, we're gonna run an equipment ground and we're gonna run two ungrounded conductors.
Speaker 1Right.
Speaker 2So if you do this bond a generator out at a dwelling and you've got this connection, now you've got the equipment ground a conductor which goes back and you've got the neutral that's connected together. They're both going back to the same location. Okay, you with me. So now the generator frame is connected through the equipment ground conductor back to the dwellings equipment ground and consystem, and at the service equipment, the equipment grounding system and grounded conductor are bonded together with the main bonding jumper. Then at
Speaker 2the generator I've bonded them together again because I wanted to create a bonded generator, which you know by now you should not do if you're connecting it to a dwelling, but somebody does it or they don't think about it. Now, the neutral conductor and equipment grounding path can form what's called parallel conductive path between those two bonding locations, and that is the problem. So you say, okay, well, Paul, I need you to illustrate how this creates a problem. Okay,
Speaker 2let's kind of let's break this down so it's so simple to understand where the hazards can happen. Normal load current now has another way home. Let's simply put one hundred and twenty volte load in the dwelling and it's being powered by this generator, and you use a bonded generator on a system where it does not switch to neutral, so you've got parallel paths. So current leaves one side of the generator windings on the ungrounded conductor. It goes
Speaker 2through the load, whatever that load may be because you're running generator now, it returns on the brand circuit neutral. Everything is fine so far. When that current reaches the dwelling neutral system, where should it go back to the generator winding through the neutral conductor. Well, that's our intended normal current path if you're powering this circuit through the generator into the into the dwelling. But I just gave
Speaker 2it another path because I'm using a bonded generator. That's creating parallel paths. Because the neutral is bonded to the equipment ground and conductor at the service, and I bonded the neutral to the generator's frame again to the equipment ground. I now potentially have neutral current flowing from the service bonding point through the equipment ground and system to the generator's equipment ground and conductor, through the generator's frame, generator's neutral bond, and then to the generator's winding. That's a
Speaker 2second conductive path, not the intended neutral path. And again remember current's gonna take all paths available proportional to the amount of impedance of that path. It's going to travel on all those parts. Now, some normal load current can divide between the grounded conductor and the equipment bonding path according to impedance, as we just said, on those parallel paths, and that's exactly what we don't want to happen. Equipment grounded conductor isn't supposed to become a second normal neutral conductor,
Speaker 2and you just created that. You just paralleled the neutral. Its job is not to routinely carry normal load current. Its job is to provide an effective path for fault current when something goes wrong. That's a completely different function than what you invertently did by using a bonded generator on a system with an interlock that you did not switch the neutral. Now, oceous generator rules specifically distinguished generator
Speaker 2frame bonding from the neutral bonding required when the generator forms part of a separately drived system. So this is why the statement that people make is a bonded generator is safer. That's actually incomplete. And some people say a floating generator is safer. That is also incomplete. The real question that we should be asking about the use of a generator is how is this particular generator connected to
Speaker 2the particular system? Am I using it is a standalone at a job site in a field, and am I going to connect it to the dwelling's premise wiring system. That's fundamentally what we have to decision, not whether one is safer over the other, because used in the improper condition, they are equally dangerous. Now that interlock, that interlock didn't do anything wrong, So let's make sure we're clear about something.
Speaker 2I'm not saying that a panner interlocks are inherently dangerous. That's not the lesson. That's not what we're talking about. The interlock is acc accomplishing its intended job right. It's preventing simultaneous connection of the generator power to the utility power. It's doing exactly what it's designed to do. So one's not on when the other's on. The issue we're discussing is how we're treating that neutral. A mechanical breaker interlock normally operates the breaker for the ungrounded conductors. It does not turn the service neutral owner off doesn't have anything
Speaker 2to do with that doesn't break, it doesn't change the situation. So if the generator is connected through an arrangement where the neutral remains solid, and that's what it's going to be on most all those interlock systems like that, you need a generator grounding and bonding configuration and appropriate for that unswitched neutral system. You cannot simply say, quote, this generator came from a factory with a new to frame bond, so I'll just plug it into anything and say, you
Speaker 2know what, it's just a generator. It'll work, because that's not accurate. That manufacturer may not have intended for that generator to be used in the application that you're trying to use it for. Nor should somebody randomly start removing a factory bonded connection without understanding the generators, listening the manufacturers instructions and transfer arrangement, understanding how you're actually using this generator. And that's the problem. When we have storms around the country, people sell generators, People just go grab generators,
Speaker 2they start hooking them up the systems. Electricians get involved. They don't understand these concepts and they don't understand the difference between a bonded and an unbonded generator. They get confused, and that's a problem. Each system has to be evaluated on their own to determine what we actually need. You got to look at the generator. You gotta look at the inlet. You gotta look at the cord. You got to determine how you're going to transfer it. You got to look at the neutral configuration. You have to understand the service bonding points, all of it. You got to
Speaker 2understand all of this. Now, conversely, somebody's gonna say, well, Paul, I like to use those little transfer switches that does switch the neutral, So how do you deal that? So what changes when we actually switch the neutral? Okay, now let's change this equipment out. We're not going to do an interlock. We're gonna put a transfer switch in. So, in spose, instead of leaving the neutral connected, the transfer equipment actually switches the neutral the same as it switches the ungrounded conductors. Perfect. So when we're on utility power,
Speaker 2we've got the normal utility connections. When we transfer to a generator, that that line one in line two from the utility disconnects and the utility neutral is disconnected from the generator supplied system, so it's isolated. Everything switched. Now the generator grounded conductor is no longer solidly interconnected with the utility supplied grounded conductor because it is switched. We've changed the entire grounding and bonding analysis at this point.
Speaker 2This is where the generator can truly be constituted as a separately derived system. It is not connected to the other system. It's being switched. OHSHA definition makes this distinction directly. It says, and I quote, a separately derived system has no direct electrical connection, including a solidly connected grounded connector to conductors originating in another system. It's totally separated. OHSHA
Speaker 2also requires the neutral to be bonded to the generator frame, where the generator is a component of a separately drived system. So that generator that's sitting out in the field that you're using portable generator, you're using it as a separately derived system. So the neutral is to be bonded to the frame because the ocean requires that. So here's a
Speaker 2simple way to understand that. If we have an unswitched neutral, we have line one, line two. There's are switches. The neutral's not switched this is what you do every day on an interlock. The generator neutral remains interconnected with the dwellings grounded conductor system do not establish a second neutral to ground bond at the generator. Thus, you need to use a floating or unbonded generator when you're connecting it directly to a dwelling. Makes sense, especially when you're not
Speaker 2switching the neutral. If you're switching the neutral, or you're using one of those transfer switches, or you're doing whole house transfer or whatever you're doing, then you have line one switches, line two switches and the neutral switches. Now we've electrically separated, okay, the grounded conductor from the normal supply, we're dealing with a different system configuration and the separately derived system bonding requirements become applicable at that point. And
Speaker 2that's why I never want an electrician to memorize something in their mind and simply quote generators should have bonded neutrals or generators should always have floating neutrals. Both statements can be wrong depending upon the installation. It really depends on what you're doing with the neutral, whether you're switching it or not. It's more deeper than just making generalized statements. Okay, so all of this ultimately is kind of circling us
Speaker 2back to GFCIs. Now watch how everything comes back together here now on our go back to our truly floating generator. We were concerned about having no effective return path for the first conductor default or conductor to ground contact. Okay, Now with an incorrectly duplicated neutral to ground bond on the unswitched neutral dwelling connection, we can create multiple return paths. Okay.
Speaker 2So if we thinking about the two concepts on a floating generator, we were originally concerned because there is no return path for that first, so how can the GFCI operate there's no return path. And then what we looked at as well, we said, well, wait a minute, what if we have a generator and we have a case to neutral connection at the generator, but we're using it on a dwelling. Now we're creating multiple return paths. That's
Speaker 2a violation. So we've taken it to the extremes. One of them we had no path or not enough path, and the other extreme we used the generator in properly and now we got too many paths. And then what's in the middle of all this The GFCI, Right, it's still doing the exact same things. It always looking for the imbalance. That's all it's doing. It doesn't care whether somebody call whether the conductors are called neutral, ground bond, grinding,
Speaker 2electro conductor, equipment, ground conductor, ground in front. It doesn't care about any of that. Its sensor transformer is simply asking how much current passed through me in any one direction and how much came back through me in the other direction. If those circuits don't balance within its operating characteristic, guess what the GFCI trips. This is why grounding and
Speaker 2bonding is not just definitions we make apprentices memorize. They determine current paths. The current paths determine what protective device sees. Now, a couple other misconceptions and things that we want to talk about or myths is does a GFCI protect me if I touch hot in neutral conductors. That's another major myth. Somebody will say, if there is a GFCI, I can't get electrocuted. That is absolutely not something you should rely upon.
Speaker 2Let's say a person simultaneously touches the ungrounded hot conductor and the grounded conductor at the same time. So current flows from the hot through the body back on the neutral. Now look at it from the gfci's point of view. Suppose your body and it passes through you. So suppose fifty million amps goes through the person's body as leaves through the ungrounded conductor being monitored by the GFCI, and ultimately, since you're touching the other side, fifty million a beer
Speaker 2returns through the grounded conductor being monitored by the GFCI. So what's the difference here, just because you're coming in contact within your touching it, what's the difference? Zero? The GFCI sees balanced current, What went out came back yep, potentially dangerous current is traveling through the person's body and the GFCI doesn't blink, an eye doesn't trip. This isn't
Speaker 2just theoretical wording. I'm making up ul's guidance for Class A circuit breakers. GFCI specifically says that in the instructions include information indicating that the user is not protected when contact is made with more than one circuit conductor. Literally says that that statement alone should just troy the misconception that a GFCI somehow recognizes that a human being is being shocked. It doesn't remember. It recognizes imbalance. That's it.
Speaker 2It doesn't care about anything else, doesn't get personal. It's all it's looking for is an imbalance. And if you're a part of the circuit and you're not creating an imbalance, then you're just part of the circuit. So this next one here is for all of my home inspectors and people out there that test circuits and people that put stuff on social media. They go, but my plug tester says that the GFCI doesn't work. Here's another myth people have.
Speaker 2Let's say you have an old two wire brand circuit with no equipment, ground and conductor. Somebody installs a GFCI protective device. Then somebody comes behind them with one of those inexpensive three light testers receptacle testers with the GFCI test button built into it. They plug it in, they press the little test button, and the GFCI doesn't trip, and immediately on their report it goes, see, I told you GFCIs don't work without a ground No. What you've
Speaker 2just demonstrated is that you don't truly understand how your tester works. In your hand. Many external GFCI tester manufacturers will tell you that it manufactures an imbalance by taking a small amount of current from the ungrounded conductor and shunting it to the equipment ground and conductor. That's why these devices are three prong devices. It has the ground prong. Now the GFCI sees current leave on the hot without
Speaker 2the same amount returning on the neutral. Obviously, because it's shunting it to the equipment ground, it trips. OSHA specifically describes this testing method as common. GFCI testers shunt a small amount of current from the hot to the grounding conductor to produce the imbalance. So what happens if there is no equipment grounding conductor in the circuit? The tester may have the path it needs to manufacture the fault
Speaker 2current or does it. Well, if there's no equipment ground it can't have that path. It can't shunt anything. Therefore, it can't function, So the external tester may fail to trip a perfectly functioning GFCI. In fact, OSHA tells its own compliance personnel not to rely solely on a negative result from the external GFCI tester because circumstances can't exist
Speaker 2where the external tester gives a negative indication even though a functioning GFCI is protecting the actual circuit. That's incredibly important point to understand. Don't confuse quote my tester couldn't create a test condition with quote the GFCI can't detect an actual differential current. Those are not the same statement. They are not the same statement. Now, how does the
Speaker 2gfs So the next question that people ask is, well, okay, but doesn't all these GFCI devices have their own internal test button. Yes they do, And somebody might ask me and says Paul, if there's no ground and you've explained how the external test devices work, how does the test button on a GFCI work. That's built into the GFCI. Well, because the integral test function isn't simply depending on your brand circuit equipment, ground a conductor the same way that
Speaker 2a common external plugin tester does. It doesn't do it the same way. The devices internal test circuitry deliver creates a condition that the GFCI sensing system recognizes a ground fault type in balance. Now, ul's Application Guidance for Circuit Breaker GFCIs says, depressing the test switch causes a current simulating a ground fault to flow, so the internal mechanism should trip. UILL also requires instructions on use of that
Speaker 2supervisory circuit to indicate that these devices should be tested at least monthly, and of course I know you all do. That's why understanding your test method matters. You should always know what exactly is my tester doing electrically, because a blinking light and a button don't replace electrical theory. Right now, a GSCI does not replace an EGC. Again, I will
Speaker 2say this, and I hear this on social media all the time. We have to destroy another misconception before somebody takes this podcast completely out of context. And I know you will because people do. If I say a GFCID doesn't require an equipment ground and conductor to perform differential current sensing, somebody online, somebody on social media is going to take that and shorten it and say, hey, Paul said, equipment grounding conductors don't matter if you have a GFCI.
Speaker 2That is not what I said. That's not even close. Nothing takes the place of an effective low imped its ground fault current path the EGC. What we're saying is that The GFCI doesn't require an equipment ground and conductor itself to perform its differential current sensing function. That's all we're saying. The equipment grounding and bonding system provide functions a GFCID does not provide. The EGC or equipment grounding
Speaker 2conductor establishes an intentional, low impedance conductive path for fault current. That path helped produce enough fault current for the appropriate overcurrent device to open fast very quickly. A GFCI is looking for a very small differential current associated with current escaping its intended current path. That's all it's doing. Yes, they work together. An equipment ground and conductor is vitally
Speaker 2important to the installation and new installations require it. But a GFCI also has its role in its functions and what it's trying to do as well, and they work perfectly together. One doesn't magically replace everything that the other does. Folks, remember that a GFCI protected receptacle installed where no equipment ground can doctor exists still doesn't suddenly have an equipment grounded conductor. It doesn't magically create an equipment ground and conductor.
Speaker 2Is it safer without having anything absolutely does the code allow existing to our ungrounded brand circuits to be able to add a GFCI in it? Yes, but it doesn't magically create an equipment ground for faults. Understand the concept GFCI protection does not mean grounded. Remember that grounding and bonding are not the same word. By the way, generators
Speaker 2also expose another problem in our industry. People use grounding and bonding interchangeably. They are not interchangeable concepts. When we connect conductive parts together to establish electrically continuity and it creates an effective fault current path, we're talking about bonding. When we intentionally establish a system's relationship to ground or to earth, we're talking about grounding. When somebody says, hey, Paul,
Speaker 2my generator is grounded because the neutral is connected to the frame. When they say that to me, I say, I immediately want to know exactly what they mean. I always follow with the question, I go, well, are we talking about the neutral to frame system bond? Are we talking about the generator frame to the EGC terminal being bonded? Are we talking about grounding electrodes? Are we talking about the dwelling grounding electrode system? Those terminology, Those questions are
Speaker 2not interchangeable. Precision does matter in this case, especially with grounding and bonding. It's probably one of again the vastly misunderstood concepts, and it's why in our program, our grounding and bonding course is so popular because we break these essentials down and understand it. There's some but different especially when we're trying to diagnose why current is flowing on paths that it's not supposed to. And the example we gave was using a bonded generator when we're not switching
Speaker 2the neutral on a dwelling, that can create that kind of condition and it's an unsafe condition. The next one that we get from people, I just want to get it out there is the ground rod myth. While we're on generators, we might as well clear this up because it's another misconception. Somebody sees a generator and immediately the first things that come out of their mouth, and cities are notorious for this. Municipalities you'll say you need to drive a ground rod, and they think that the ground rod is what makes a branch circuit ground fault cleary.
Speaker 2They think that that's what causes it to do that. That usually is a misunderstanding of fault current paths. Okay, our earth is generally not the intentional low impedance equipment fault current path we're depending upon to operate a circuit breakers over current protection device. That's that's not what we're doing with that. Y'all know that the impedance on the earth is way too high. That's why our bonding and equipment ground and conductors matter so freaking much. Driving electrode
Speaker 2into the earth doesn't magically solve an incorrect neutral to ground bonding arrangement, and removing the required bond isn't correcting an installation by installing a ground rod. Right again, follow the current back to the source. That's the question. It's not a question of does somebody install enough stuff called ground so that you have multiple, multiple, multiple connections that
Speaker 2that's going to make it better. Again, not what it is. So let's talk about why is bonded generators may appear to work perfectly on a system, and so you're installing in the system and that's not supposed to be. Let's just kind of figure out this real quick. So here's what makes the duplicate bond problem particularly deceptive. So this is where you mistakenly take a neutral that's not switched on a dwelling, and you install a bonded generator onto
Speaker 2that system and everything seems to work right. It just seems fine. So everything may appear to be completely normal. The generator starts, the lights come on, the refrigerators work, the well pump runs, televisions come on. Nobody gets shocked, and somebody says, see it's wired correctly. No operation is not proof of proper grounding and bonding. It could be a ticking time bomb. Parallel neutral current paths don't necessarily
Speaker 2stop equipment from functioning. That's a great thing about electricity is people do things wrong. It still tries to work. It still tries to function. The load can operate perfectly. While some normal grounded conductor current is traveling through paths that were never intended to carry current under normal load current conditions. Then that's the problem. That's what makes grounding and binding errors so deceptive. Because it still works. The system can work, and it's still wrong. That's what creates
Speaker 2a hazard, and that's where you end up having current traveling on parts that they're not supposed to and it's just waiting for you to come along and touch it and come in contact with it. So here's a little exercise just kind of puts you in a perspective. Every electrician, sit down and draw this. If you're ever confused about generator installations, stop arguing about terminologies and getting confused, and let's do this. Just take a piece of paper. Draw
Speaker 2a generator winding and you have line one, and draw line two, and draw a neutral, and draw the generator's frame, draw the equipment ground and conductor, draw the dwelling panel, draw the service bonding connection. Then ask yourself as you're starting to draw this up, is the neutral switched at your first question? If it's an interlock system, no, it's
Speaker 2not switched. So if that's the case, trace the neutral all the way from the generator back to the dwelling unit. Then locate every connection between the neutral and the equipment ground. If you got one at the service and another the generator, all the parallel paths, it becomes painfully obvious that if the neutral is switched, then you don't have the same
Speaker 2condition if the neutral is not switched, because current are going to be circulating on all those paths back and forth to the generator on the equipment. But if the neutral is switched. Draw what happens when the transfer switch moves the generator to the generator position where that neutral is disconnected. Now ask whether the generator system is electrically separated from the other systems, including the ground of conductors. Obviously,
Speaker 2if you're switching the neutral and you're switching all the ungranted, you are, so you're creating two separate systems. You won't have parallel paths. So this is why I tell electricians constantly draw the circuit. The code becomes a lot easier when you understand the electricity underneath it and how it flows. Now UL nine forty three isn't just an old five million amp standard. That's another thing worth understanding when it
Speaker 2comes to UL nine forty three, It isn't frozen in time. People talk about GFCIs like nothing has changed since the seventies. But modern electrical systems are full of electronics, variable speed motors and verters, power conversion equipment, switching, power supplies, vastly changing electronic equipment, smart technology. All those technologies can produce something called high frequency leakage components that older discussions of GFCIs rarely address. In August of twenty twenty five, UL
Speaker 2Standards and Engagement issued a revision to UL nine forty three, adding supplement SB for an optional high frequency or HF rating. UL says that the HF rating address this is compatibility with modern loads producing high frequency leakage current, including loads involving variable speed drives and inverters. UIL also notes that the twenty twenty six NEC recognizes this new class A HF mark GFCI application. So when we say UL nine
Speaker 2forty three GFCI, we're talking about safety standards that continue to evolve with the modern electrical components. This is why electricians need to understand both the fundamentals of how the circuit operates, the principles, and you also need to understand the product standard behind the device. So in a rapid succession here let's talk. Let's kill the miss one by one really quickly and wrap this thing up so you can have some real clean takeaways. Number one, GFCI needs
Speaker 2an equipment ground and conductor of the work. That's false. Its basic personnel protection sensing function is based upon differential current through the monitored circuit conductors, not the equipment ground and conductor. Totally different thing. Myth Number two a GFCI monitors the green or bare wire false as description of basic Class A operation. It's comparing monitored circuit conductors. The EGC or equipment ground and conductor may provide a path
Speaker 2that creates an imbalance, but that is different from saying that the GFCI is simply measuring current on the equipment grounded conductor, because it's not. It's actually sensing the imbalance between the neutral and the hot in those monitored circuit conductors. If current travels on the EGC, all that's doing is going outside of that troidal coil and that is giving it another path back that will cause the GFCI to function, But it could be other paths back to the source outside of that troidal cored as well. So it doesn't
Speaker 2mean that the GFCI is monitoring any equipment ground and conductor because it is not. We've established it. It doesn't even need it to function its intended role. Myth number three, GFCI makes an ungrounded receptacle grounded false. A GFCI protected and an equipment ground conductor are two different things. GFCI protection again looking for those imbalances, whereas an equipment grounded conductor is providing an effective, low imped its ground fault current path back to help facilitate the operation of an
Speaker 2overcurrent protected device. Vastly different concepts. One does not replace the other. Okay. Myth number four, A GFCI will always protect me if I get shocked. False. If current leads through one monitor conductor, travels through your body and returns completely through another monitored conductor, there may be no differential current. Again,
Speaker 2touching the hot in the neutral and both of them happen to go through that coil, there's no differential current, so in all cases, it will not protect you in all situations. Ul specifically warns that GFCI protection is not provided when contact is made with one or more with more than one of the circuit conductors that is running through the protective system. Very important to understand that number five.
Speaker 2If my plugin tester doesn't trip the GFCI, then GFCI is bad. Not necessarily. Many external testers need an equipment grounding conductor path to manufacture their test imbalance, and OSHA specifically says a negative external tester result alone isn't conclusive. Myth number six, A floating generator can never shock you. False.
Speaker 2The first conductor to ground contact on a truly isolated floating source may not establish a strong enough return path for real world capacitance leakage. Okay, but a real world capacitance leakage, connected equipment and additional faults can change the system. So the initial connection it may put enough current through you that is not enough to cause the device to function.
Speaker 2That does not mean in all cases that you can't get shocked, but again, in real world, various capacitants, leakage, connected equipment, or additional faults can change the system and provide a path back, an alternate path back where it doesn't go through the coil, and that it could protect you, but at would cost. Because it may be the initial shock that didn't cause the device to function properly because
Speaker 2it was floating and used in an improper application. Vastly important to understand the differences. Myth number seven. A GFCI doesn't work on a floating generator because the GFCI is defective, not necessarily if there isn't enough differential current. Because there isn't an effective return path as we just talked about, the device may simply have nothing substantial to detect. That
Speaker 2doesn't mean the GFCI is defective or bad, it's just not enough imbalance for it to go off. And remember you will identifies a Class AUL nine forty three GFCIs as intended for a grounded neutral system, not to be used on systems that don't have a grounded neutral Important to understand the application of a class A UL ninety three device. Myth number eight. A bonded neutral generator is
Speaker 2always safer. False. If you're connecting that generator to a dwelling right through an unswitched neutral arrangement, another neutral frame bond can be established and creates parallel neutrals and equipment grounding paths, and that could potentially energize metal parts that were not designed to carry current under normal operation. Only under a fault condition it creates a touch hazard. Myth
Speaker 2number nine. A floating neutral generator is always safer. Okay, so we went from a bonded neutral one. We explained why if you're using on a dwelling it's not safer. Then what about this again, A floating neutral generator is always safer. That is also false if the transfer equipment switches the neutral and it truly creates a separately derived system. The proper system bonding arrangement is different, and you need
Speaker 2to have that connection. So you have to evaluate each system's configuration separately. If it's switching the neutral, then we need that bond. If it's not switching the neutral, we do not want that case to bond to be done on that generator. Kind of understand these concepts, and if you don't get it, rewind this back and listen to that portion where I talked about it. Myth number ten.
Speaker 2If the generator powers the house, the installation must be wired correctly. Okay, let me read this again. If the generator powers the house, the installation must be wired correctly. So just somebody sees the generator hooked up to the house and asks soon that everybody did the right thing, And just because they plug a generator in and all of a sudden, everything gets powered on. Refrigerator works, TVs work everything. You assume, hey, everything's okay, generator works. That
Speaker 2it must be done correctly because everything's working. As you heard before. That is absolutely false. An improperly bonded system can operate loads perfectly while still allowing normal current on unintended conductive paths. Creates a hazard. So just because it works, doesn't make it right. So three questions that solve most generator arguments. When somebody asks you, should this generator be
Speaker 2bonded or floating? Before you answer these questions, these questions. Question number one is is this generator operating standalone or is it connected to a premise wiring system? Huge difference. That's the first question that you, as an electrician should always ask. Where is your intended use to this generator? Number two, does the transfer arrangement switch the neutral? That's one of the biggest questions in the entire analysis, and if you haven't figured out by now, that's going to dictate your generator connected to your dwelling on whether or
Speaker 2not you switch the neutral or not, on whether or not it's a bonded or unbonded generator. Got to ask that question. Question number three, where is the neutral ground system bonding connection for this operating configuration? Is it at the generator or is it at the panel service panel. If it's at the generator, then you need to transfer switch transfers the neutral. If it's not at the generator,
Speaker 2but the connection is neutral, the neutral to ground is made in the panel, then you want to make sure that the generator and you're not switching the neutral. That the generator does not have that bond connection between the neutral and the ground makes sense. Once you answer these, you've analyzed the circuit, you know where.
Speaker 1To go.
Speaker 2Together. So let's go all the way back to the beginning. Why can't a GFCI function without an equipment ground connector Because the GFCI isn't dependent upon the presence of an equipment ground conductor. For its basic differential current sensing principle, it compares current. That's it. Why might a first conductor to earth contact on a truly floating generator not cause the same GFCI response because there may not be an
Speaker 2effective current path back to the source, and so the GFCI device cannot detect the differential of current flow. That's why. Why does connecting that floating generator to a dwelling through an unswitched neutral change the picture? Well, because now the generator's neutral is connected to the dwellings grounded conductor system and its service bonding point. That creates what a situation
Speaker 2where you got parallel applications. So we have to understand that if we're going to switch the neutral, then we want the generator to be bonded. If we're not switching the neutral in the panel, then we want the generator to be unbonded or floating. Makes sense, Okay, you might ask yourself, why don't we use Why don't we just leave another neutral to frame bond at that generator? Why
Speaker 2does it matter? Because with the switch neutral again, we create a second neutral ground connection, and those parallel paths for normal neutral current traveling on conductors that never intended to making contact with parts that are bonded to the equipment ground that now have current flowing on it. That's a problem. That's a hazard. Doesn't mean it won't run. It just means you're creating a ticking time bomb and a potential lawsuit if you don't know what you're doing and you're an electrician, What if my transfer equipment actually
Speaker 2does switch the neutral? Paul, Now we change the system configuration again, and now you may have a separately drive system requiring an appropriate bonding arrangement. That means that you again want to that point, make sure that you if you are switching the neutral, and I keep doing this repetitively, so this hammer's in your head. If you're now switching the neutral and you have a separately drive system then the generator. It's treated as such, and that's when it
Speaker 2needs the bonding jumper in there between the case and neutral, because we're truly switching the neutral in the panel because of a transfer switch. Hopefully that that makes sense to everybody. What's you know, what's common through all this is the current path. There's no slogans, there's no folklore, there's not I've always done it this way and it's worked. We understand that current has to leave and it has to return,
Speaker 2and what conductive paths exist between the source and the load that allows for that. So if you remember one thing from this episode, and we've been an hour and thirty minutes approximately, if you remember only one thing from this podcast, remember this. A GFCI isn't really asking it's current going to ground. It's asking did all the current that left through my monitored conductors returned through my monitor conductors. If yes, the GFCI season of balanced. If not, it
Speaker 2sees differential current. Once you understand that, suddenly all of these issues start to make sense. Why a GFI operates without an equipment ground connector why an external GFI tester may not function. Why grabbing a hot neutral simultaneously is still incredibly dangerous. Why a floating source behaves differently. Why the first fault and second fault on an isolated system are different events. Why unswitched generator neutrals matter. Why a
Speaker 2duplicate neutral ground bond can create parallel current paths, and we just talked about why that's inherently dangerous, and why a switched neutral transfer arrangement completely changes the grounding and bonding analysis and means that it vital to whether or not you choose a bonded or unbonded generator vitally important. This is electrical theory meeting electrical safety. And this is exactly why we shouldn't teach electrician rules without teaching them
Speaker 2why these rules exist. Because if you all know is that bond, this ground that put GFCI here, you start memorizing instructions. But when you start to truly understand the source, the circuit, the current path, the bonding, the differential current, When you start really understanding that, you can analyze it. This is what it makes electricians true electricians, not just repetitive soldiers that simply do this from A to B. And this is why we teach people, because we really want you to understand it. So the next time somebody
Speaker 2tells you quote a GFCI needs a ground wire to work, don't just tell them they're wrong. Show them the touroidal transformer. Show them the current going out, show them the current coming back. Show them the floating generator in how it works. Do that little diagram. Then do the same one and show connect the generator to an unswitched neutral dwelling unit. Then show them what happens if you add a second neutral to ground bond with the generator. Because look, the
Speaker 2best way to eliminate misconception isn't to replace one slogan with another. It's to literally teach them how the circuits function. And that's why we should be teaching GFCIs grounding and binding and generator system. Understand the current path and the rest starts to make sense. Hopefully you got something out of that, folks. It was a long one today. Hopefully you made it through it. If you have any questions, you can always put it down in the comments. Feel free to yell out to me and let me know if you want me to clarify anything I try to give you everything I can in an episode, but those
Speaker 2are the fundamental concepts of how the device functions. If you disagree with that, you're going to have to bring the receipts because that is essentially what it says in ninety three, That's what essentially says in OSHA, and this is how they function. It's common sense, but sometimes it gets mixed up with folklore. Till next time, folks, Stay safe, God bless.
Speaker 1Thanks for tuning into another electrifying episode of the Master of the NEC podcast. We hope you're feeling more powered up and ready to tackle the electrical world with the knowledge and confidence you need to succeed. Remember, in the electrical trade, knowledge is power, and we're here to make sure you stay plugged into the latest insights, tips and code updates. If you enjoy today's episode, don't forget to subscribe, leave us a review, and share the podcast with your fellow electricians and industry pros. Until next time, keep your
Speaker 1tools sharp, your circuits clear, and you're my focused because here at the Master of the NEEC podcast, we're all about sparking your success. Stay safe, stay smarked, and keep mastering the trade. From all of us here at Electrical Code Academy. Thank you for all your support and we will see you on the next Amazing Master of the NEEC podcast episode
NiteNerds™ - The Future of Permanent Outdoor & Landscape Lighting Is Here! What if your home could look absolutely stunning every night of the year - with the touch of a button? Welcome to the world of NiteNerds™, where...
⚡ MASTER THE NEC PODCAST 🎙️ Hosted by Paul Abernathy Master Electrician | National Electrical Code Expert | Electrical Educator ⏱️ Episode Length: 55 Minutes ⚡ ABOUT THIS EPISODEWelcome to Episode 81 of Master The NEC,...
⚡ MASTER THE NEC PODCAST 🎙️ Hosted by Paul Abernathy Master Electrician | NEC Code Expert | Electrical Educator⏱️ Episode Length: 1 Hour, 23 Minutes ⚡ ABOUT THIS EPISODEWelcome to Episode 80 of Master The NEC, where...
⚡ MASTER THE NEC PODCAST 🎙️ Hosted by Paul Abernathy Master Electrician | NEC Code Expert | Electrical Educator ⚡ ABOUT THIS EPISODEWelcome to another episode of Master The NEC, the podcast dedicated to helping...
The National Electrical Code is a minimum standard - but what does that actually mean? In this episode of Master The NEC, Paul Abernathy takes a deeper look at one of the most misunderstood concepts in the electrical...