Discover Silent Sentinels, a groundbreaking exploration into the world of protective relays and the intricate schemes that safeguard the generation, transmission, and distribution of electric power. This book stands as one of the earliest comprehensive resources on the subject, revealing how, despite the rapid technological advancements over the past century, the core principles of protective relays remain steadfast. Join Rick Jay as he navigates through the historical and technical landscape of electrical protection systems, providing insights that are both timeless and essential for understanding modern power infrastructure. This episode includes AI-generated content.
Audio and video play straight from the show's own hosting. PodSubs stores and serves no media.
Transcript
From the show. Tap a time to play from there.
Speaker 1Chapter five of Silent Sentinels by Westinghouse Electric and Manufacturing Company. This LibriVox recording is in the public domain. Automatic control substations, depending on the method used in their operation, may be divided into three classes, manual, semi automatic, and automatic. Regardless
Speaker 1of its type, a station must be a highly reliable source of power supply. The necessary operations in a substation which serves the purpose of transforming alternating current into direct current by means of synchronous converters or motor generators are therefore the starting and stopping of such machines when the system demands it, and the provision of adequate protection against faulty action, either in case of some trouble out on
Speaker 1the system or in case of trouble within the substation equipment. The automatic substation today is more dependable than is the manually operated station. The design and development of relays with a high degree of accuracy, sensitivity, and reliability have made such an automatic substation a possibility. The characteristics of the automatic substation, which must be supplied by adequate relays, might
Speaker 1be roughly divided into two classes, namely control and protection. The control methods consist in the automatic starting of one or more of the machines in the station. This may be introduced in any one of several ways, depending on the conditions to be met, and is generally accomplished through some form of remote control or by means of a voltage relay which closes its contacts at some predetermined value
Speaker 1of reduced line voltage. Starting due to momentary drop in voltage or when the alternating current voltage conditions are incorrect is prevented by an induction type alternating current voltage relay. While many of the operations are common to both synchronous converters and motor generators, the following outline of system is especially applicable to synchronous converters. When conditions are favorable for starting,
Speaker 1a sequence of relay actions serves to perform the necessary functions such as lifting the converter brushes, connecting the converter to the starting tap of the power transformers, and other operations depending on the type of substation. After the converter has started to rotate. Synchronism and polarity are indicated by a polarized motor relay, which, in case of reversed polarity, causes the polarity of the machine to be corrected by
Speaker 1reversing the field. The armature of the relay motor is connected to the converter pilot brushes, and during the period of starting, the polarity of the relay becomes that of the machine. As the converter comes up to synchronous speed, alternating current of diminishing frequency flows through the motor armature until synchronism is reached without causing rotation. At that time,
Speaker 1the armature will revolve in drive a drum switch in the direction corresponding to the converter pole. If the polarity is incorrect, the drum switch causes the field connection to reverse by means of a double throw contactor switch. The reversed connection is maintained only long enough for the voltage default to zero and then to release the controlling relay, which causes the normal field connection to be re established.
Speaker 1By this operation, the converter has been caused to slip a pull and thus correct the polarity. The polarized motor relay continues to operate and causes a transfer relay to function. This relay in turn opens the starting contactor, causing operation of the direct current brush operating mechanism. Which lowers the brushes to the commutator. At this time, the main direct
Speaker 1current switches are closed and the machine is connected to the load. The final function of the control part of the substation equipment is to disconnect the machine from service. This operation is introduced by the action of a sequence of light load control relays. Protective equipment is provided not only in the automatic substations, but also in the manually operated or the semi automatic stations. It is provided by
Speaker 1induction type single and polyphase relays, which prevent the station from starting under abnormal conditions of alternating current line voltage, such as low voltage, open phase or reverse phase. The same type of relay causes the station to shut down on unbalanced phase conditions. If the trouble is within the station, a lock out relay prevents restarting, and if the unbalanced phase condition is outside the station, the automatic equipment functions
Speaker 1to the apparatus into service as soon as the line is restored to normal. Each bearing is equipped with a thermostat, which, in case of a hot bearing, locks the machine out of service until the contexts of the thermostat device has been reset by hand. A thermal relay also protects the winding of the machine from overheating due to continued overload. Other protective devices are the direct current directional relay, an
Speaker 1overspeed device, an inductive type alternating current overload relay, a thermostat preventing overheating of the current limiting resistors, and a lockout relay which locks the equipment out of service in case of failure of any part of the apparatus. The protection of the equipment is complete and responds immediately in case of trouble, thus eliminating the losses which often occur in man only operated substations because of the vary impossibility
Speaker 1of handling an emergency in the required time or the inability of the operator to do so. In addition to this automatic operation of the substation, a number of automatic selective relay equipments are in use for automatically cutting out a short circuited line, or for automatically reclosing and other types of necessary feeder operation. It can be seen from this description what a large part the relays play and
Speaker 1automatic substation equipment, and also how absolutely necessary it is to have relays which are not only highly reliable and accurate at the time of their installation, but also which will maintain this high degree of accuracy and reliability throughout continued service. Thus, success of the Westinghill Automatic substations and past experience have proved the induction types of relays, first
Speaker 1developed and manufactured by the Westinghouse Company, to be especially suitable for this type of service. By the use of the induction type relays, precision of operation is not only assured, but the exact calibration can be maintained throughout a long period of operation. Thus, the induction relay has solved many of the difficulties which were formally experienced when plunger type relays had to be depended on for various functions. Most
Speaker 1of the relays supplied with the present day automatic substation equipment are standard protective relays, as described elsewhere in this publication. In some cases it is necessary to somewhat modify the characteristics of the relay, but the fundamental principles of design and operation are maintained. The CV voltage relay is used throughout as a timing voltage relay to provide a definite
Speaker 1time delay where necessary. A slight modification of this relay consists in having the contacts geared to the disc shaft rather than mounted directly on it, which provides a relay with a much longer time delay characteristic than the standard. The GK time delay relay, also used largely in automatic substation equipment, is motor operated and is highly reliable. A recent addition to the relay family is the MF flash relay,
Speaker 1which is used in automatic substation protection to disconnect the rotary in case of a flashover occurring between the commutator and the frame and of Chapter five five
Report of the Inquiry into the Role and Oversight of Private Security Contractors in Afghanistan - United States Senate Committee on.... This episode includes AI-generated content.
"Silent Sentinels Protective Relays for A-C and D-C Systems" by the Westinghouse Electric and Manufacturing Company is a pivotal exploration of the technology that safeguards electrical systems. This book delves into...
"Silent Sentinels Protective Relays for A-C and D-C Systems" by the Westinghouse Electric and Manufacturing Company is a pivotal exploration of the technology that safeguards electrical systems. This book delves into...
"Twentieth Century Inventions: A Forecast" by George Sutherland presents a visionary exploration of technological advancements anticipated in the 20th century. This thought-provoking work delves into the possibilities...
"Seeking a Human Spaceflight Program Worthy of a Great Nation" is an insightful review of the U.S. Human Space Flight Plans Committee, examining the aspirations and strategies for America's human space exploration...