Discover Silent Sentinels, a groundbreaking exploration into the world of protective relays and the intricate schemes that safeguard the generation, transmission, and distribution of electric power. This book stands as one of the earliest comprehensive resources on the subject, revealing how, despite the rapid technological advancements over the past century, the core principles of protective relays remain steadfast. Join Rick Jay as he navigates through the historical and technical landscape of electrical protection systems, providing insights that are both timeless and essential for understanding modern power infrastructure. This episode includes AI-generated content.
Audio and video play straight from the show's own hosting. PodSubs stores and serves no media.
Transcript
From the show. Tap a time to play from there.
Speaker 1Chapter seven of Silent Sentinels by Westinghouse Electric and Manufacturing Company. This LibriVox recording is in the public domain. Typical relay application. When it is desired to relay a power transmission system, there are many factors which enter into the problem, all of which must be given consideration. In most systems, so many complications are present that it is almost impossible to
Speaker 1secure an ideal application of relay protection. However, in most cases it is possible to arrange the relay setting so that certain lines in case of a fault may be disconnected without disturbing the service, and the disconnecting of these lines leaves conditions such that ideal selective action is secure. You're on the rest of the system where distance between stations is great enough to give the necessary three percent drop,
Speaker 1and it is convenient to use the type c Z relay, these complications may be eliminated. Figure sixty four shows a schematic sketch of a typical network system which will be used as the basis for illustrating one method of making an initial relay application. Figure sixty four is described here in order to facilitate understanding the remainder of the chapter.
Speaker 1It is suggested to copy this down to paper to facilitate understanding. The Crichton Generating Station is connected via a loop system to seven substations. Line one connects Relay twenty two at Kryme Generating Station with relay one at Woodward Sub. Line two connects Relay twenty one at Crichton Generating Station
Speaker 1with relay two at Woodward Sub. The distance is three miles. Fault location A is located on line one. Line three connects relay three at Woodward Sub two Relay four at Parsons Sub over a distance of three miles. Fault location B is on this line. Line four connects Relay six
Speaker 1at Parsons Sub with relay seven at bryce Ki Sub. Fault location C is on this line. The distance is six. Line five connects relay eight at brice Key Sub with relay nine at Feldman Sub. Fault location D is on this line. Line six connects Relay ten at Feldman Sub
Speaker 1with relay eleven at Goldsboro Sub. Fault location E is on this line. The distance is one mile. Line seven connects relay twelve at Goldsboro Sub with relay thirteen at Kubiak Sub. Fault location F is on this line, the distance is three miles. Tie Line eight connects relay five
Speaker 1at Parsons Sub with relay fourteen at Kubiak Sub. Fault location G is on this line, the distance is five miles. Tie Line nine connects relay fifteen at Kubiak Sub with relay twenty at Crichton Generating Station. Fault location H is
Speaker 1on this line, the distance is five miles. Line ten connects relay sixteen at Kubiak sub with relay seventeen at Anderson's Sub. Fault location I is on this line, the distance is four miles. Line eleven connects relay eighteen at Anderson Sub with relay nineteen at Crichton Generating Station. Fault
Speaker 1location J is on this line. The distance is two miles end of figure sixty four description. Upon analysis, the network is found to be really a loop system, with tie line number eight connecting Parsons and Kubiak substations, and number nine connecting the generating station with the Kubiak sub. This loop, without these ties connects seven substations with a
Speaker 1generating station. Either the co CR or the CZ relay scheme will be the typical one to use. Therefore, the COOCR scheme will be chosen with the CZ scheme S an alternative. Standard CO overcurrent relays are therefore allotted to each outgoing line numbers one qu nine eleven at the generating station, and standard CR directional overcurrent relays on each
Speaker 1line of the loop. At each substation. The type CR relays are connected so that the directional element contacts will close only when power is flowing away from the substation bus s bars. It should be remembered throughout this discussion that access current flowing in this direction is necessary to complete the tripping circuit. After assigning relays to the various lines,
Speaker 1the next problem is to assign time settings to the relays and then check out to determine if the proper time intervals necessary for selective action can be allowed without having excessive type settings on any of the relays. A five tenths second interval between relay settings is commonly used in present day press. This value allowing zero point three five second for the breaker to open after the trip circuit has been made, and zero point one five second margin.
Speaker 1The maximum allowable setting, of course depends on the system, but three point one seconds is considered the highest time setting, which it is safe to use, and a maximum of two point six seconds is adhere to whenever possible. Referring to the system in question, there are seven substations in the loop which would require a maximum time setting of three point six seconds for the relays at the generating station. This value is rather high, therefore some way must be
Speaker 1found to lower it. When checking the distance between stations, it is found that line six is comparatively short. Hence a pilot wire scheme may be used to protect this secondction. That makes one less section to be counted in adding the successive time intervals, but three point one seconds is still higher than is desirable. Trying to find some means of eliminating one more section, it is observed that the
Speaker 1Anderson sub might be eliminated from the loop for the first trial application, making tie line number nine a part of the loop. This will make it possible to obtain the proper intervals between successive relays with a maximum setting of approximately two point six seconds. Definite time settings may now be assigned to the successive relays in the following manner. Beginning at the Woodward sub, the cr relays numbers one
Speaker 1and two on lines one and two set to trip with power flowing from the sub to the generating station may be set to trip almost instantly, because a fault online number one or two is the only circumstance to cause excess current to flow in this direction, and therefore the relays may be set to clear as soon as possible. It is customary to make this setting zero point one second. Going on to the next sub persons, we find that
Speaker 1Relay four online number three at this sub is set to trip with power flow in the same direction, namely away from the bus bars towards woodward sub. This relay must accordingly be given a higher time setting because a fault online one or two will draw current through Relay four, and therefore it is essential to have Relay one trip first. A definite setting of zero point six second is therefore assigned to it. In like manner, each successive relay connected
Speaker 1to trip with the power flow in this direction is given a setting of zero point five second higher than the next preceding one, which leads to a setting of two point six seconds on Relay twenty at the generating station. Relay number eleven at Goldsborough's sub may be ignored because it can be set to trip almost instantly when a fault occurs in line six, but a fault on any other part of the system will not affect it. A similar procedure is followed out for the relays set to
Speaker 1trip with the power flow in the other direction, or clockwise as it might be considered. Beginning at Kubiak sub relay fifteen is assigned to zero point one second, setting Reulay twelve zero point six second, Relay eight one point one second, and so on until relays twenty one and twenty two at the generating station are reached. The next problem which must be met and solved is the time
Speaker 1setting for relays five and fourteen on line eight and relays six, sixteen, seventeen, eighteen, nineteen on lines ten and eleven. No definite rule can be followed for making the settings on relays five and fourteen. Very often the relays on a tie line are set to trip in a short time whenever excess current flows, because this action makes the relay operation on the rest of the system simpler and
Speaker 1does not injure the service. In this case, however, by assigning a setting of one point six seconds to relay five and two point one seconds on relay fourteen. Comparatively good protection is secured for line eight, and neither relay will trip with a fault elsewhere on the system, except in one or two cases as well be shown later. The lines ten and eleven may be considered as completing the loop from substation Kubiak rather than line nine, and
Speaker 1the settings a de signed to fit in with the rest of the loop as already described. A check can now be made assuming a fault in each line in turn, and then determining whether the proper relay operation will take place. Assuming a fault on line one at a current will flow to the fault from the generator station and from woodward sub Thus Relay one will clear within zero point one second, cutting off all flow from that direction, and
Speaker 1Relay twenty two will clear within two point six seconds. Assuming a fault at B on line three, current will flow in from both directions, tending to trip relay's seven at brice Ski fourteen at Kubiak in twenty one and twenty two in addition to three and four at the immediate ends of the line. Relay three will be twenty two and twenty one out, thus clearing the fault inn in that direction. And relay four will trip in zero
Speaker 1point six second, which is a shorter period than that of any of the others that will be likely to trip. Assuming fault sets C on line four, D on five, G on eight, E on line six, H on line nine, J on line eleven, and I online ten, the action may be checked out in the same way. Assuming of fault online seven et F. We find that current may be drawn from both directions that coming from sub kubiak
Speaker 1being possibly drawn from lines eight, nine, and ten. In case enough current is drawn from line eight to give relay five its definite minimum time of tripping, it may trip before relay thirteen clears. However, relay thirteen will trip before any other relays in the system. Therefore the opening of the tie line is not serious. There is also a possibility of setting the current taps on relay five so that it will be operating on the inverse part
Speaker 1of the curve under such a condition, and thus increase its time of tripping to the extent that Relay thirteen will trip first if it is desired. And an analysis of short circuit current values shows that sufficient unbalanced will exist between lines one and two with a fault in either one. Additional current balance CD relays may be installed at each end. These will provide a means for clearing either line almost instantly when they are both in service
Speaker 1and one develops a fault. Type CO relays should be used on each outgoing feeder from the several substations. TYPEZA relays should be used for the differential protection of the three banks of transformers in the generating station. The transformers in the substations elseh may be supplied with differential protection if their size and location justify it. In most cases, however,
Speaker 1where the transformers are relatively small less than two thousand kilovote ampiers, and where the overload relays may be given a low time setting, the overload relays serve also as sufficient transformer fault protection. On complicated systems employing COO and CR relays for protection, the time required to trip sometimes becomes excessive in some parts of the system. This subjectionable
Speaker 1feature is entirely absent in a CZ installation, as all lines have their relays set to clear the line in a maximum time of zero point seven five second with a short at the far end. If the short takes place add or near the relay, the short is cleared almost instantaneously since the voltage restrained action is zero. The other relays on the system are restrained in proportion to their distance from the short and accordingly do not open
Speaker 1their breakers. Type CA relays should be used for the differential protection of the three generators. It should be understood that definite current in time settings and final checks on the relay operation can be made only after a short circuit study of the system has been made, thus determining the actual currents which will flow in different lines with faults at the different locations. After this information is available,
Speaker 1the proper current transformer ratios in current taps on the relays may be specified, and with the time setting assumed, the exact time of operation may be found from the relay time current curve. End of Chapter seven
Report of the Inquiry into the Role and Oversight of Private Security Contractors in Afghanistan - United States Senate Committee on.... This episode includes AI-generated content.
"Silent Sentinels Protective Relays for A-C and D-C Systems" by the Westinghouse Electric and Manufacturing Company is a pivotal exploration of the technology that safeguards electrical systems. This book delves into...
"Silent Sentinels Protective Relays for A-C and D-C Systems" by the Westinghouse Electric and Manufacturing Company is a pivotal exploration of the technology that safeguards electrical systems. This book delves into...
"Twentieth Century Inventions: A Forecast" by George Sutherland presents a visionary exploration of technological advancements anticipated in the 20th century. This thought-provoking work delves into the possibilities...
"Seeking a Human Spaceflight Program Worthy of a Great Nation" is an insightful review of the U.S. Human Space Flight Plans Committee, examining the aspirations and strategies for America's human space exploration...