Discover Silent Sentinels, a groundbreaking exploration into the world of protective relays and the intricate schemes that safeguard the generation, transmission, and distribution of electric power. This book stands as one of the earliest comprehensive resources on the subject, revealing how, despite the rapid technological advancements over the past century, the core principles of protective relays remain steadfast. Join Rick Jay as he navigates through the historical and technical landscape of electrical protection systems, providing insights that are both timeless and essential for understanding modern power infrastructure. This episode includes AI-generated content.
Audio and video play straight from the show's own hosting. PodSubs stores and serves no media.
Transcript
From the show. Tap a time to play from there.
Speaker 1Chapter three, Part two of Silent Sentinels by Westinghouse Electric and Manufacturing Company. This LibriVox recording is in the public domain. Section three Methods of clearing ground faults solidly in low resistance grounded neutral systems. These systems, when protected by types CO, CR and CD relays, require no additional relays. For wired to ground faults, three current transformers and three relays are
Speaker 1necessary for the complete protection of each circuit breaker. However, where type CZ impedance relays are used in order to obtain the minimum time for clearing faults, two sets of impedance elements are required for phase to phase and phase to ground faults. The reason for this is that a ground fault on one wire results in fifty seven point seven percent voltage being maintained across two sides of the voltage triangle and one hundred percent voltage across the third side. The voltage between the grounded wires and neutral is, of course zero or nearly so. If only three elements having
Speaker 1their directional element potential coils connected in STAR are used, a wired to wire short circuit will reduce the voltage across each relay coil from fifty seven point seven per cent of the line voltage to twenty eight point eight percent line voltage, so that each relay still has fifty percent normal voltage impressed across it. With fifty percent normal voltage acting on the potential coil of the CZ relay, The time required to close the contacts is entirely too long for satisfactory operation, and two sets of elements must
Speaker 1be employed for complete protection, medium resistance, grounded neutral systems. Relay equipment, and additional to that required for line short circuits, is required to care for phase to ground failures. For those installations where the magnitude of the ground current in the circuit and the ratios of the current transformers are such as to produce a single phase curve cur of at least two ampers in the secondary of one current transformer for a fault from that wired to ground, a type co relay having a low current winding is inserted
Speaker 1in the neutral connection between the neutral point of the line relays and the neutral point of the current transformer secondaries. The low current type COO relay has taps for operation at zero point five, zero point six, zero point eight, one point zero, one point five, two point zero, and two point five ampers. It can generally be operated on the zero point five amper tap without danger of tripping improperly. As under normal operation, there is no current flowing in the neutral connection. Fig. Forty one shows the connections for
Speaker 1the ground relay. When the circuit breaker is controlled by type CO over current relays, it will be observed that the tripping contacts of the ground relay parallel to the tripping contacts of the line relays. The same scheme of current and tripping connections is employed when non directional single impedance element type CZ impedance relay are used to protect the feeder against line faults. When the circuit breaker is controlled by type CR directional overcurrent or type CZ single impedance element relays for phase to phase faults, the low
Speaker 1current relay is inserted in the neutral circuit. For ground fault protection. The tripping contacts do not, however, go directly to the circuit breaker trip coil, but are connected in series with the directional contacts of the line relays. To secure proper directional indication on ground faults as well as line faults, a tap must therefore be provided on the line relays between the directional element contacts and the overcurrent or impedance element contacts. Fig. Forty two shows the connections using three type CR line relays and one type CO
Speaker 1low energy ground relay. The same tripping circuit connections hold when Type CZ impedance relays are used for line faults. This arrangement should be used with care. It has been found that a high resistance at the point point where an accidental ground occurs will limit the current to such a small value that the load current flowing through the CR relays will be greater than the ground current and the CR relays will not operate in the proper direction. A low current Type CD selective differential current relay is available for ground protection at those locations protected against line
Speaker 1faults by type CD relays. Each winding is provided with taps for zero point five, zero point six, one point two and two point zero ampers operating current. One winding is connected in each neutral connection of the balance pair of lines. Fig. Forty three shows the complete connections for line and ground protection on two balanced lines for both balanced and single line operation. High resistance grounded neutral system protection against wired to ground faults on high resistance grounded
Speaker 1neutral systems cannot be readily provided in less the magnitude of the ground current in the circuit and the ratio of the current transformers are such says to provide one and a half to two ampers in the secondary of one current transformer with a ground fault on that wire. Since the ground current is less than the load current in the circuit to be protected, a directional element which shall be independent of load is required. Fig. Forty four shows complete line and ground protection for two parallel lines on a high resistance grounded neutral system. The line potential
Speaker 1transformers are connected star star with the star points grounded. The line relay potential coils are energized by the delta voltages of this bank. If the potential transformers are chosen as to give one hundred and fifteen volt single phase secondary when energized by a single phase voltage of line to line value, the line relay should be provided with one hundred and twenty five vault potential coils. The secondaries of the line potential transformers also energize an auxiliary bank of three two hundred to one hundred voult potential transformers
Speaker 1connected star on the primary side. The star point being can acted to the two star points to the line potential transformers. The secondaries of the auxiliary bank of transformers form a closed delta through the potential coil of the ground relay. A low current low energy directional type CR relay having the same current winding as the low current type co previously mentioned, is required for ground protection. The current coil of this relay is connected between the neutral point of the current transformer secondaries and the neutral point
Speaker 1of the line relays. When a fault from one wire to ground occurs, the distortion of the voltage triangle caused by a current being fed to the ground fault by the potential transformer develops sufficient voltage across the potential coil of the directional relay to obtain in conjunction with the residual current in the relay the proper directional indication. The proper time of operation for the relay is secured by an adjustment of the time index lever of the over current element. When power transformer banks are can connected star
Speaker 1delta and the star point is grounded through a resistor, the potential for the directional ground relays can be secured by connecting the primary of a two hundred to one hundred volt potential transformer between ground and a point on the resistor which is two hundred volts above ground. When carrying the maximum ground current. The secondary of the potential transformer energizes the potential coil of the relay. Section four. Calculation of short circuit current. In applying any protective scheme,
Speaker 1it is necessary to determine the short circuit currents which may develop under all conditions. It is unfortunate that the term overload has ever come into use in connection with sectionalizing distribution systems, because it implies that the relays should be set to operate at a value determined by the normal load on the feeder. Such a setting is possible if definite time limit relays are used, but where a relay having inverse time characteristics is used, is necessary to consider the current that occurs during times of trouble, and
Speaker 1that may be tens or even hundreds of times greater than the normal current. An approximate method of determining the possible short circuit current is to observe the voltage drop between two stations at normal load. Short circuit current equals normal voltage divided by voltage drop times load current. For example, if a certain load current causes a drop of five percent in voltage between the generating station and the substation, the maximum short circuit current would be twenty times the load current. Results obtained in this way are likely to
Speaker 1be too large, particularly in lines having high inductance. In order to determine more accurately the RMS current, an analysis of short circuit phenomena on an alternating current network is necessary, and it may be desirable to call attention to some of the conditions under which relays may be called upon to function. A short circuit is a transient condition, and this current at any point in an electrical system is a variable depending on the resistance, inductance, electrostatic capacity, magnetic capacity,
Speaker 1point on the voltage wave at which the disturbance takes place, and current conditions of the circuit immediately preceding any change in the steady condition of that circuit. It represents a readjustment of the stored electromagnetic and electrostatic energy in the system from an initial steady state condition until a final steady condition is reached. It is manifested during every change in the condition of the circuit, although its effects on the circuit are usually not appreciable under certain conditions, such as short circuits. The effects of the transient current, however,
Speaker 1are of prime importance. Short circuiting a system at any point immediately causes an abnormal current rush to occur on that system. During the first complete cycle following the short circuit, the current usually rises to maximum value. If now the generator field circuit is assumed to remain unchanged by automatic generator voltage regulators or similar devices than during succeeding cycles, the current will rise to lesser and lesser values until a steady condition again exists on the system. The current
Speaker 1wave during the transient period, as shown by assilograms, may be symmetrical or asymmetrical with respect to the line representing zero current, depending on the point on the voltage pressure wave at which the short circuit occurred. The transient current is said to be symmetrical when the assumed line connecting points on the current wave midway between the peaks coincides with the line of zero current. Similarly, a transient current is said to be symmetrical when the assumed line connecting
Speaker 1points on the current wave midway between the peaks does not coincide with the line of the zero current. The value of the current at any point on the current wave during the transient condition, if referred to the line representing zero current, is a measure of the effects produced by the current at that point. Some of these effects are indicated by the breaking of insulators supporting buses, the displacing of windings of transformers and generators, the distortion of oil circuit breaker connections, and the fusing of conductors. In
Speaker 1various parts of electrical systems, the value of the current at any point on the current wave during the transient condition is frequently referred to an assumed zero line between the peaks. This values used to calculate the electrical constants of a circuit, such as impedance, reactants, etc. The maximum asymmetrical value of a transient current in RMS ampers during a short circuit on an ordinary alternating current generator is approximately equal to one point eight times the generated voltage pressure of the generator in volts immediately preceding the short circuit,
Speaker 1divided by the impedance of the circuit in omes between the point of power supply and the point of short circuit. The maximum symmetrical value of the transient current is a proximately equal to zero point five to five times the maximum asymmetrical value. The transient of an electrical system at a point remote from the source of power supply will be different from that at the terminals of an alternating current generator. Its amplitude and duration will depend upon the electrical constants of the system and the distance between the
Speaker 1point of short circuit and the source of power supply. In general, the greater the distance between the source of power and the point of short circuit, the less the amplitude of the transient, and the shorter its duration. Automatic generator voltage regulators introduce system transients differing from those which occur in systems not so equipped. They tend to maintain constant the system pressure, but on account of the inherent time lag of the iron portions of the generator and exciter armatures and fields, their effect is not felt immediately.
Speaker 1The effect of automatic voltage regulators on system transience may be predicted for any known set of conditions, and account taken as such effects in the application of relays. Fig. Forty five is a typical acilogram showing the current flowing in one phase of the external circuit when a system is short circuited under ordinary operating conditions. In this diagram, O is the origin of the coordinates and is taken at the instant at which the short circuit occurs. Ox is the axis of absissa, and the absissa represent time.
Speaker 1O Y is the axis of ordinates and the ordinance represent current. CD is a curve passing through the maxima of the wave of total current, and EF is a current passing through the minima. AB is a curve which cuts the vertical everywhere midway between CD and EF. The wave of total current, which the crests lie along curve CD and EF, and of which ordinates are measured from the axis OX, may be regarded as having two components,
Speaker 1namely one a direct component, two an alternating component. The direct component is represented at any time by the ordinate to the curve AB, or at the time X by the coordinate GH. The alternating component is a wave whose cress value at any time is the difference between the ordinance to the curve CD and AB. This difference at the time X has the value HJ. The RMS values
Speaker 1of this alternating component are shown on curve st At any instant, this component is considered to have the same RMS value as an alternating wave of constant amplitude whose CRESS value is represented by one half the distance between curve CD and EF at that instant. The RMS value of the total current wave under short circuit at any instant is the square root of the sum of the squares of the value of the direct component and the effective value of the alternating component at that instant. The
Speaker 1correct application of relays to an electrical system requires that certain characteristics of the system be known or assumed. These system characteristics are one normal voltage, two maximum current carried by the circuit in which the relay is connected, three normal frequency section, four maximum CAVIA capacity of synchronous apparatus, transformers, reactors, and lines. Five transind current characteristics during short circuit or overload.
Speaker 1The RMS current at any point of a system under short circuit conditions is affected by the following factors. One the total CAVA, reactants and transient characteristics of the synchronous machines connected to the system. Two number reactance, resistance, capacitance, and arrangement of all circuits over which power can be supplied to the point of short circuit. Three CAVA arrangement
Speaker 1resistance reactants and capacitance of all reactors and transformers through which power can be supplied to the point of short circuit. Four, contact resistance at the short circuit. Five, the nature of the short circuit, whether single phase or polyphase. Six, the CAVA and power factor of the load being carried at the time of short circuit. Seven, the point of the voltage pressure wave at which the short circuit was established.
Speaker 1Eight the use of automatic voltage regulators. The short circuit transient for systems may be determined by tests, by calculation, or less closely by assumption. Obviously, the determination by test for all circuits of a large system is expensive and involves considerable time and interruption to service. This will be practical in but a few cases. The determination by calculation is also a matter of considerable labour, but is feasible
Speaker 1if only the important factors listed above are considered practical. Approximate selection sufficiently accurate for most cases can be made by using only reactants and an accepted group of time. Current decrement curves table IE gives decrement factors for three phase short circuits. These factors are intended primarily for use in relay application and setting where minimum short circuit values are important. The effect of using RMS values instead of peak values is to appreciably reduce the ratio between short
Speaker 1circuit and rated ampers. For example, assuming ten per cent reactants and a short circuit current containing the maximum possible direct component, the ratio of the peak value of the first alternation of the short circuit current to the peak value of rated current is roughly twenty. Under the same condition, the ratio of the RMS value of the first alternation of the short circuit current to the RMS value of the sinusoidal rated current is roughly seventeen. The effect of
Speaker 1using the flux at rated voltage and the assumed load instead of at rated voltage and no load is to increase the short circuit current by a somewhat lower percentage than the alternator reactance percentage. This effect in alternating current generators of low reactants is relatively unimportant, but becomes of increasing importance as the generator reactants increases. The characteristic shapes of the time current decrement curves have been reached by analysis of generator tests, including a celigraph studies of short
Speaker 1circuits occurring when the generators were excited to full voltage and were carrying various loads at various power factors. In the curse or total reactancies up to including fifteen percent, the reactance is assumed to be wholly within the alternating current generators, and for higher values of reactants, the generators were taken at fifteen percent, and due allowance was made by calculation for the effect of the external reactancies. In the latter case, if alternating current generators of the other
Speaker 1reactants had been used, the results would have been somewhat different, but the error is not large enough to be of practical importance. The final values of current ie the sustained short circuit current have been assumed in accordance with experience and tests, and are based on the behavior of machines of predominating design. The study of representative assilograms of short circuit tests showed that in most cases, the direct component disappeared within zero point five second and that the transient portion of the alternating component disappeared within three seconds. These
Speaker 1time values have therefore been used in constructing the characteristic decrement curves. Several alternating current generators with the same reactants and synchronous impedance will not necessarily they have the same rate of RMS current decay. This has been considered in constructing the characteristic curves, and the decrement curves may therefore safely be taken as representing the greatest RMS current that will be given by modern alternating current generators of normal design. The percentage reactance in any leg of a circuit is
Speaker 1a reactance drop in that leg of the circuit at normal rated current, expressed as a percent of the voltage to neutral of that circuit. For single and two phase systems, this is the voltage between phase wires divided by two. For three phase systems, this is the voltage between phase wires divided by one point seventy three. The percentage values in Table I are initial values based on a symmetrical sin wave and on the maximum rating of the machines connected to the bus. The percentage of reactants of generators
Speaker 1varies from about eight percent to thirty percent. The percentage reactance of transformers varies from about three percent to fifteen percent. Nature of short circuits. When making current calculations, it should always be assumed that a short circuit is due to a metallic connection between the conductors In a high voltage aerial line using wooden pins and cross arms. It sometimes happens that an insulator is broken, with the result that the wood is gradually heated by the passage of the current through it, until it finally bursts into flame, thus
Speaker 1causing an arc between conductors. A little consideration shows that the flow of current is small until the arc is established, and that it is wrong to speak of automatically disconnecting a section of line which has such a high resistance short circuit. It has sometimes been assumed that an arc has a high resistance, but this is not the case, and in general the presence of an arc at the point of short circuit will not decrease the short circuit current by more than a few percent. Incidentally, it may be of interest to note that on a high voltage
Speaker 1ungrounded neutral system, the capacity current to ground through an arc is greater than it is through a direct ground. There is only one case where a short circuit is likely to increase in intensity as it develops, and that is on a system where the neutral is grounded through a resistance A cable breakdown, for instance, frequently occurs first between one conductor and the sheath, and the current flow may be limited by the neutral resistance. The trouble will quickly involve all the conductors in the cable, resulting in
Speaker 1a heavy short circuit, but it is possible that it will require an appreciable time to do this, in which case the relay operation may be unsatisfactory. This is particularly liable to happen if the neutral is not grounded at every substation. Section five. The protection of AC apparatus overload protection. Overload protection of the larger type of electrical apparatus, as a general rule, receives little special attention inasmuch as the
Speaker 1relays provided for short circuit protection serve also for overload protection of the apparatus of the system in addition to this, in generating. In substations where there are operators in attendance, the load on the apparatus is usually under their supervision and is governed by them accordingly, except in cases of short circuit trouble on the system. In small installations where some scheme of overcurrent protection is necessary, the CO overcurrent relay or CW overpower relay can generally be used to give satisfactory protection protection against internal faults. Protection against internal
Speaker 1faults in the windings of electrical apparatus is receiving much attention. In present day practice, these internal faults might be roughly classified as phase to phase short circuits, short circuited turns, open circuits, and grounds. Experience has shown that most of the internal faults developed in larger types of rotating electrical apparatus develop originally as a ground from the phase windings to the frame. If the neutral is not grounded, a fault of this sort will not unbalance the phase current, and it is therefore rather difficult to locate until it
Speaker 1is developed into a phase to phase short circuit. Thus, from the consideration of protection, it is best, wherever possible to have the neutral grounded. Grounds are more likely to occur near the line end rather than the neutral end of a winding, but in the event of the latter, the current which flows may be relatively small, especially if a high resistance ground is used. The fact that the fault current is often very small at the beginning, and that it is highly desirable to detect such a fault and disconnect the apparatus from the line before a phase
Speaker 1to phase short circuit can develop, makes the protection of apparatus against internal faults rather a difficult problem. A differential scheme of protection, making use of either standard over current relays or special over current relays operating on very small current, is the most general scheme for protection against internal faults. This form of protection consists of balancing the current entering the apparatus against the current flowing from it. This scheme of protection is usually accomplished by connecting a current transformer
Speaker 1at each end of each phase winding, connecting their secondaries in series, and then connecting a current relay across these secondaries. As long as the secondary currents are equal, no current will flow through the relay windings. Any leakage of current, however, to other phases or to ground, will upset this balance and send current through the relay. The relay, in turn operates to trip the circuit breaker and disconnect the faulty apparatus. The principle of operation used in this scheme allows relatively
Speaker 1low current settings on the over current relays because obviously no current will flow under normal conditions. It is also free from trouble due to circulating current when synchronizing or switching on any part of the system is taking place, inasmuch as such current should be balanced in each phase. This scheme is very flexible in its application and might be applied to machines of any size either star or delta connection, provided that both ends of each phase winding are capable of being brought out and connected to current transformers.
Speaker 1No definite rule can be set down in regard to the size of apparatus to which relay protective scheme should be applied. It is largely a question to be decided from a consideration of the importance of limiting the amount of damage that can be done to the machine. In other words, it resolves into an economic consideration in which the cost of relay protection must be balanced against the value of service rendered and then compared with the cost of possible damage to the apparatus. In the case of large generators and sometimes motors, where the neutral is grounded
Speaker 1directly or through resistance, and the faulty currents may or may not be of any great value, a relay sensitive to very small current is required. The low energy COO relay is especially adapted for the differential protection of such applications. An improvement on this method has been made by designing a relay the type CAA that trips on a percentage of the line current rather than on a given value of current. This makes it possible to get more sensitive protection without danger of having the relay operate due to
Speaker 1the circulating currents which usually occur at times of through short circuits. In the differential protection of transformers, highly sensitive settings are not so necessary and in many cases are undesirable, as they would only serve to disconnect the transformers upon some transient condition which accompanies a momentary unbalance but not a fault. The standard over current co relay is therefore applicable for the differential protection of transformers. A special form
Speaker 1of the type caa relay with taps provided so that unequal currents can be balanced without the use of auto transformers, has been developed for transformer protection. This tap arrangement, combined with its adaptability to cases where circulating current appears under transient conditions, makes it of particular value, especially when bushing type transformers are to be used. Open or reverse phase protection. In many installations of polyphase motors and rotary converters of any size, it is becoming a common practice to provide
Speaker 1protection against running in case of an open phase or in case of reversal phases. A reversal of two phases, of course, reverses the direction of rotation of any motors on the line, and so it is especially desirable to have this condition protected against. In cases where a reversal of the direction of rotation of any driving motors, such as one in an elevator service, may be disastrous, the CQ phase balance current relay gives ample protection against the occurrence of such conditions on a system. Temperature protection of
Speaker 1windings inasmuch as the overheating of the windings and electrical apparatus is closely realid to the overcurrent protection, the overcurrent protection is often adequate to provide the necessary temperature protection. In some cases, however, it is more desirable to furnish protective apparatus which will include in its operation not only the load on the apparatus, but also the existing temperature of the windings. In other cases, the temperature of the winding alone is taken as the determining factor in the
Speaker 1operation of a temperature protective scheme. In most of the larger generating stations or substations, where constant supervision of the operation of the various machines as possible, temperature indicating devices are used to show the attendant when the temperature of the windings in questions becomes such that some means should be used to reduce it. Such indications are usually provided by means of exploring coils embedded in the windings of the apparatus, serving either to actuate a signal when the temperature reaches some predetermined point or to operate some temperature
Speaker 1indicating instrument. Thus, when the critical degree of heat is indicated, the operator may relieve the condition, either by reducing the load on the apparatus or by increasing any existing cooling means, such as the flow of air or water, as the case may be oil filled thermal relays where manual supervision is not possible, such as in automatic substation equipment and in plants using numerous motors, it is necessary to have temperature protection that will disconnect the apparatus when any predetermined
Speaker 1conditions exist. A common scheme for providing such protection is to apply in a protective relay a heating element with thermal characteristics similar to those of the machine. To be protected, a current proportional to the load current in the apparatus itself flows through the heating element of the relay. The characteristics of this element are such that its temperature will be approximately the same as that of the protected apparatus under all loads and at all times. When the temperature of this element reaches the critical points, it serves to
Speaker 1trip the apparatus offline. The Westinghouse BA and BD oil filled thermal relays serve to provide this class of protection type CT temperature relay. Another scheme used for the temperature protection of windings is to have the protective apparatus depended on the current flowing at any given time, and also at the same time, on the temperature within the windings of the apparatus to be protected. In such a scheme, the temperature is usually determined by means of copper exploring
Speaker 1coils buried in the windings and connected in some sort of bridge arrangement, so that the change in resistance of the exploring coils due to any change in the temperature of the windings will give the proper temperature indication to the protective relay by using the change in the resistance values to cause a flow of current. In addition to this, a current proportional to the current flowing in the apparatus flows through another winding of the relay, and thus the following three conditions are necessary before the apparatus is disconnected from the source of power. First, the temperature of the
Speaker 1windings of the apparatus must be above the value for which the relay is set to operate. Second, the current flowing in the apparatus must be above the normal value, and third, these two conditions must have existed for a given period of time. Thus, the liability of the machines being disconnected upon the occurrence of a transient overload is guarded against. The CT temperature relay provides such protection and embodies the necessary characteristics to assure maximum continuity as service.
Speaker 1The simplest form of over temperature protection is that in which the temperature of the surrounding material is alone used as an indication of the temperature of the winding and is taken as the determining factor in the operation of any protective relays used. Such a scheme is used largely in the protection of transformers, where the exploring coils, expansion bulbs, or whatever means are used for measuring the temperature of the surrounding material may be embedded between the coils of the transformers in such a way that an approximate indication of the temperature of the windings is secured. The HM
Speaker 1thermostat relay is sometimes used for this purpose. Temperature protection of bearings. In the case of rotating machinery, it is often necessary to provide some scheme of protection whereby any overheating in the bearings will either cause a signal to operate or else cause the machine to be disconnected entirely. Where actual supervision is possible, such protection may provide only for the operation of a signal to call the attendant's attention to the fact that all is not well with this machinery. In cases such as automatic substations, it is
Speaker 1usually necessary to have the protective apparatus disconnect the machine entirely, either shutting down the station or else disconnecting the individual piece of apparatus. The HM thermostat relay is used largely for this application. End of Chapter three, Parts two
Report of the Inquiry into the Role and Oversight of Private Security Contractors in Afghanistan - United States Senate Committee on.... This episode includes AI-generated content.
"Silent Sentinels Protective Relays for A-C and D-C Systems" by the Westinghouse Electric and Manufacturing Company is a pivotal exploration of the technology that safeguards electrical systems. This book delves into...