Discover Silent Sentinels, a groundbreaking exploration into the world of protective relays and the intricate schemes that safeguard the generation, transmission, and distribution of electric power. This book stands as one of the earliest comprehensive resources on the subject, revealing how, despite the rapid technological advancements over the past century, the core principles of protective relays remain steadfast. Join Rick Jay as he navigates through the historical and technical landscape of electrical protection systems, providing insights that are both timeless and essential for understanding modern power infrastructure. This episode includes AI-generated content.
Audio and video play straight from the show's own hosting. PodSubs stores and serves no media.
Transcript
From the show. Tap a time to play from there.
Speaker 1Chapter ten of Silent Sentinels by Westinghouse Electric and Manufacturing Company. This LibriVox recording is in the public domain. Instrument transformers. Instrument transformers are used for two reasons, first to protect station operators from contact with high voltage circuits, and second
Speaker 1to permit the use of instruments with a reasonable amount of insulation and a reasonable current carrying capacity. The function of instrument transformers is to deliver to the instruments a current or voltage which shall be always proportional to the primary current or voltage, and which shall not exceed as safe potential above ground. Generally, the secondary of a voltage
Speaker 1transformer is designed for about one hundred and fifteen vaults, and the secondary of a current transformer for five ampiers, and both these secondary circuits are grounded together with the cases of the relays, instruments or meters to which they are connected. Types and ratings. There are two general classes of instrument transformers, dry and oil insulated. Dry type voltage
Speaker 1transformers are listed for primary voltages up to the six nine hundred volt class, and the oil insulated type up to the sixty six thousand vult class. Current transformers are listed for primary currents up to ten thousand ampiers voltage classes up to twenty three thousand volts, the dry type of current transformer is used, and for the higher voltage is the oil insulated type. The demand for transformers of
Speaker 1higher ratings than those given is so small that they are not listed, although they can be built on special order. Oil is used in oil insulated instrument transformers, chiefly for its insulating properties. It is extremely important, therefore, that it be of the proper quality and that it be kept free from dirt and moisture polarity. In connecting instrument transformers
Speaker 1to watt meters, what hour meters, power factor meters, et cetera, it is necessary to know the relative instantaneous direction of currents in the leads. For this reason, one primary and one secondary lead of each Westinghouse transformer are marked with a white polarity marker. The relation of the marked leads is such that the instantaneous direction of the current in them is the same that is toward the transformer in
Speaker 1the marked primary lead and from the transformer in the marked secondary lead, or vice versa. This marking of the leads is carefully checked by a polarity test grounding of secondary. All instrument transformers should be grounded on the secondary side as an extra precaution against danger from the high voltage in case the insulation should be punctured by lightning or
Speaker 1other abnormal process. In polyphase groups, any point of the secondary may be grounded, but it is prof to use a neutral point or a common wire between two transformers. Insulation. The insulation of instrument transformers protects the meters and control apparatus, as well as the power station operators from the high voltage circuits. It is highly important, therefore, that it be
Speaker 1able to withstand the strains of service. For this reason, the insulation of Westinghouse instrument transformers is designed with special care. Dry type transformer coils are impregnated with a compound impervious to moisture. Coils. For oil insulated transformers are dipped in, varnished or impregnated to seal them against moisture insulation tests.
Speaker 1The insulation tests conform to the standardization rules of the American Institute of Electrical Engineers. Voltage transformers uses. Voltage transformers are used with volt meters, what meters, what hour meters, power factor meters, frequency meters, synchronoscopes, and synchronizing apparatus, protective and regulating relays, and the no voltage in over voltage
Speaker 1trip coils of automatic circuit breakers. One transformer can be used for a number of instruments at the same time if the total current taken by the instruments does not exceed that for which the transformer is designed and compensated. Voltage transformers have a capacity of two hundred volt ampiers, but are compensated to give correct ratio at forty volt ampiers, as this is the average blow demanded by a voltage transformer.
Speaker 1Special transformers may be compensated for correct ratio at any load up to the full capacity of two hundred volt ampiers. The standard secondary voltage is one hundred and fifteen volts nominal to suit standard instruments. Instrument transformers with special secondary voltages can be made if necessary. Principle of operation, the voltage transformer is in principle an ordinary constant potential transformer,
Speaker 1especially designed for close regulation, so that the secondary voltage under any condition will be as nearly as possible a fixed percentage of the primary voltage. The secondary voltage can never be exactly proportional to the primary voltage or exactly opposite in phase to the primary voltage on account of the losses in the transformer and the magnetic leakage between coils.
Speaker 1There are two classes of errors inherent in voltage transformers, ratio error and phase angle error. The part of these errors due to the exciting current is constant for any particular voltage. It can be reduced to a minimum by choosing the best quality of iron and working it at a low magnetic density. The part of the errors due to the load current varies directly with the load and
Speaker 1can be minimized by making the resistance and reactance of the windings very low. Current transformers general, the current transformer is a special development of the transformer principle. The object is to maintain a constant ratio between the currents in the primary and secondary windings, instead of a constant ratio between the voltages, which is the usual requirement. Uses. Current
Speaker 1transformers are used with ammeters, watt meters, power factor meters wt hour meters, compensators, protective and regulating relays, and the trip coils of circuit breakers. One current transformer can be used to operate several instruments, provided that the combined burden does not exceed that for which the transformer is designed and compensated. Principle of operation. The ordinary voltage transformer or
Speaker 1distribution transformer is connected across the line, and the magnetic flux in the core depends upon the primary voltage. For a given voltage, the flux is therefore fixed, while a current crent in the winding rises and falls as the load of the secondary winding changes. The current transformer is connected directly in series with the line for a fixed number of instruments in the secondary, which is the usual condition.
Speaker 1A rise or fall in the line current requires a corresponding rise or fall in the secondary voltage to force the secondary current through the impedance of the meter load. The magnetic flux in the iron which supplies this voltage thus follows the rise and fall of the primary or line current. In any transformer, the primary ampere turns may be considered as made up of two parts, one small
Speaker 1element which supplies the magnetizing and core loss current, and another element which supplies the working current. The working current ampier turns are always exactly equal to the secondary ampire urns. End of Chapter ten and of silent sentinels by Westinghouse Electric and Manufacturing Company,
Report of the Inquiry into the Role and Oversight of Private Security Contractors in Afghanistan - United States Senate Committee on.... This episode includes AI-generated content.
"Silent Sentinels Protective Relays for A-C and D-C Systems" by the Westinghouse Electric and Manufacturing Company is a pivotal exploration of the technology that safeguards electrical systems. This book delves into...
"Silent Sentinels Protective Relays for A-C and D-C Systems" by the Westinghouse Electric and Manufacturing Company is a pivotal exploration of the technology that safeguards electrical systems. This book delves into...
"Twentieth Century Inventions: A Forecast" by George Sutherland presents a visionary exploration of technological advancements anticipated in the 20th century. This thought-provoking work delves into the possibilities...
"Seeking a Human Spaceflight Program Worthy of a Great Nation" is an insightful review of the U.S. Human Space Flight Plans Committee, examining the aspirations and strategies for America's human space exploration...