Discover Silent Sentinels, a groundbreaking exploration into the world of protective relays and the intricate schemes that safeguard the generation, transmission, and distribution of electric power. This book stands as one of the earliest comprehensive resources on the subject, revealing how, despite the rapid technological advancements over the past century, the core principles of protective relays remain steadfast. Join Rick Jay as he navigates through the historical and technical landscape of electrical protection systems, providing insights that are both timeless and essential for understanding modern power infrastructure. This episode includes AI-generated content.
Audio and video play straight from the show's own hosting. PodSubs stores and serves no media.
Transcript
From the show. Tap a time to play from there.
Speaker 1Chapter six of Silent Sentinels by Westinghouse Electric and Manufacturing Company. This LibriVox recording is in the public domain. Relay settings, the selection of the proper current tap in time index, lever setting, or induction type over current relays demands a knowledge of the load conditions in the circuit or portion of the circuit to be protected, and the amount of
Speaker 1short circuit current available under minimum generating capacity conditions. It is also desirable to know the amount of short circuit current available under maximum generating conditions, but in case the data is not available, the interrupting ability of the oil circuit breaker will service a first approximation. While there are minor modifications in the actual set of the relays dependent on the particular type of protection employed. The following remarks
Speaker 1will outline the general considerations with reference to the simpler cases current tap settings on radio and loop feeders, the proper current tap is determined largely by the current transformer ratio and the full load current in the feeder. In general, the current tap is so chosen to be at least two hundred percent of the secondary current from the current transformers when carrying full load in the line. In cases
Speaker 1where the load is subject to violent fluctuations, it may be necessary to make normal operating current for the relay three hundred percent of the secondary current corresponding to normal full load. The current tap should not, however, be chosen so high that the wheels delay winding receives less than three hundred percent of its current setting under short circuit with minimum generating capacity on the system, as otherwise, the
Speaker 1time of operation will be so long as to completely disrupt service. Time settings on radial feeders, the proper time of operation of the relay is determined by its location with respect to the source of power and other relays on the same circuit. For a radio feeder system, the outermost relay is set for the shortest time, and the relays towards the generating station for successively longer times. The
Speaker 1relays at the source of power must be set sufficiently long to allow any outlying faulty section to be cleared. With induction type relays and direct current operated circuit breakers, it is common practice to set successive relays for time intervals zero point five seconds apart, with the outermost relay set for zero point one second, adopting a maximum of two point one seconds, as the longest time of fault
Speaker 1should remain on this system. We therefore find that five sections is about the most that should be protected by selective timing alone. Although some systems are operating satisfactorily with relays set zero point three or zero point four seconds apart, such systems achieve success only by extreme care in the maintenance of the oil circuit breaker mechanism and careful adjustment of relays in trip circuit mechanisms. Time intervals closer together
Speaker 1than zero point five second are not to be recommended for average systems. The time of operation should be that required when the relay is operating on the flat or minimum time interval of the time current curve i e. When the second current is five hundred percent or more of the relay current tap setting time settings on loop feeders for the simple loop system involving only one source
Speaker 1of power, the relay time settings are described in the paragraph on time settings on radio feeders. The loop is opened at one of the generating station breakers and the relays on the outgoing sides of the substations set for successively higher times of operation from the outermost substation. Considering the feeder as straight radio to the generating station. The loop is then closed up and the other generating station
Speaker 1breaker opened. The time settings on the remaining relays being determined is already outlined. Starting on the loop at any point and approaching the generating station, it will then be observed that the relays set to trip for power flowing from the generating station will be set for increasingly longer times of operation, whereas the relays set to trip for power flowing towards the generating station will be set for
Speaker 1increasingly shorter times of operation. The loop system, which receives power at two or more points in the ring, is especially difficult to relay. If the various substation relays are timed for one source of power, as outlined in the preceding paragraph, the timing is wrong when considering the other source or sources of power. Parallel lines between any two points can of course use some form of balanced protection
Speaker 1for parallel operation, but this is not a place likable when the lines are operating singly. In applying a series of time settings to such a system, it is generally necessary to consider both the amountain source of short circuit current available. Selection usually can be obtained by working on the inverse portion of the time current curve of the relay. Parallel feeders protected by type CD relays four lines protected
Speaker 1by Type CD relays, It is usual to set the relay to operate on a differential current of three ampers. For through short circuits, the current in the two equal lines will be balanced so that there will be a very slight amount of differential current tending to trip the relays. For the somewhat infrequent case where type CD relays protect two parallel lines of unequal impedance, but equipped with current
Speaker 1transformers of the same ratio type, a current balance auto transformers should be used to make equal the currents flowing through the relay windings. The time setting is generally on the order of zero point one or zero point two second settings for ground relays. Ground relays are set the same as line relays, except that ground current flow differs in magnitude from the current flow for a line to
Report of the Inquiry into the Role and Oversight of Private Security Contractors in Afghanistan - United States Senate Committee on.... This episode includes AI-generated content.
"Silent Sentinels Protective Relays for A-C and D-C Systems" by the Westinghouse Electric and Manufacturing Company is a pivotal exploration of the technology that safeguards electrical systems. This book delves into...
"Silent Sentinels Protective Relays for A-C and D-C Systems" by the Westinghouse Electric and Manufacturing Company is a pivotal exploration of the technology that safeguards electrical systems. This book delves into...
"Twentieth Century Inventions: A Forecast" by George Sutherland presents a visionary exploration of technological advancements anticipated in the 20th century. This thought-provoking work delves into the possibilities...
"Seeking a Human Spaceflight Program Worthy of a Great Nation" is an insightful review of the U.S. Human Space Flight Plans Committee, examining the aspirations and strategies for America's human space exploration...