Discover Silent Sentinels, a groundbreaking exploration into the world of protective relays and the intricate schemes that safeguard the generation, transmission, and distribution of electric power. This book stands as one of the earliest comprehensive resources on the subject, revealing how, despite the rapid technological advancements over the past century, the core principles of protective relays remain steadfast. Join Rick Jay as he navigates through the historical and technical landscape of electrical protection systems, providing insights that are both timeless and essential for understanding modern power infrastructure. This episode includes AI-generated content.
Audio and video play straight from the show's own hosting. PodSubs stores and serves no media.
Transcript
From the show. Tap a time to play from there.
Speaker 1Chapter nine, Part one of Silent Sentinels by Westinghouse Electric and Manufacturing Company. This LibriVox recording is in the public domain. Westinghouse Protective and Control Relays, Part one one. Alternating current Relays type COO over current relay. The protective relay now
Speaker 1having the most universal application, is one that may be used to disconnect circuits or apparatus when the current flowing in the circuits or apparatus succeeds any given value. Such a relay has a wide variety of uses. The most common uses are applications to outgoing feeders, transmission lines generating the substations, distribution feeders at substations, and to motor and
Speaker 1transformer circuits. A relay designed for such a diversity of applications must have very reliable characteristics which will allow a flexible adjustment for operation under all circumstances and conditions. In verse time characteristics, the co over current relay embodies characteristics which make it applicable to the widest variety of uses.
Speaker 1For over current protection. The relay is similar in operation to thea watt hour meter. It operates on the induction principle, the contacts being closed by the rotation of a disc. It is necessary to have a certain quantity of current flowing in the relay winding before the disc will begin to rotate. After it once has been started. The speed of rotation is proportional to the current flowing in the
Speaker 1winding until such current reaches an excessively high value. This gives the relay an inverse time characteristic, or in other words, the greater the current flowing in the relay winding, the sooner the relay contexts will close. The design of the relay and the action of the damping magnet are such that the time of action is definite for any given current value. Definite minimum time characteristics conditions arise in over
Speaker 1current protection, which demand that a relay used for such a purpose should never close its contacts instantaneously. Because of the inverse characteristics of the COO relay, it is evident that upon excessive overcurrent, the action of the relay would become almost instantaneous. A small torque compensator is added in the relay winding for the purpose of placing a definite
Speaker 1limit to the inverse time characteristic. This compensator becomes saturated at excessively high currents and acts upon the relay in such a way that a definite minimum time must elapse before the context will close, regardless of the value of current flowing in the winding. This is termed the definite minimum time characteristic of the relay current settings. Conditions very
Speaker 1often arise where the current supply uses for operating an overcurrent relay varies widely due to different current transformer ratios, different conditions under which the relay is desired to act, and different degrees of sensitivity required in the relay. Such an adjustment of operating current is obtained in the co relay by varying the number of active terms in the
Speaker 1main coil winding. This is accomplished by means of a screw in the terminal block at the top of the relay element. The numbers on this terminal block represent the minimum current which will operate the relay time settings. It is also very often desired to vary the time in which the contexts will close when any given amount of current is flowing in the relay winding. This adjustment is
Speaker 1accomplished in the co relay by varying the distance through which the disc must rotate before the contacts are closed. This distance through which the disc must travel is adjusted by means of the scale and hand lever located directly above the disc. The time current curve shown on the name plate of each relay gives the time required for the context to close with different values of current flowing
Speaker 1in the relay winding with the time lever set on the number ten graduation. It will be noted from this curve that two seconds is the minimum time in which the relay will close its contexts for any given value of current, regardless of how great it may be. This definite minimum time may be reduced, of course, by placing the time lever on a smaller setting. For instance, if
Speaker 1the lever is placed on the number one graduation, the action of the relay will be almost instantaneous, because the disc has practically no distance through which it must rotate before the contacts are closed. Contact troubles have always been plentiful in relay operation. This source of trouble has been largely eliminated from the co relay by introducing an auxiliary
Speaker 1contactor switch interconnected with the tripping contacts so that it closes the instant the main relay contacts close. This arrangement relieves the relay main contacts from carrying the tripping current, and also assures good contact even though barely enough current is flowing in the relay. Winding to close the main contacts. The action of the contexts responsible for making the tripping
Speaker 1circuit is therefore made positive, and a tripping current of its high as thirty ampiers may be safely handled without fear of contact trouble type ca over current relay. In many power plants and substations, the space for mounting instruments and other switchboard apparatus is limited. In such stations, it
Speaker 1is often very essential also to have supervision over the current flowing in each circuit leading out from the station. A means of providing this current supervision and also relay protection for each circuit without the necessity of supplying and providing room for mounting both ammeters and relays, is provided by the CoA relay. This relay consists of the co
Speaker 1relay with the addition of a current indicator, which serves to show at all times the value of the current flowing in the circuit. The current indicator consists of a thin copper segment mounted on a separate shaft directly above the main disc of the relay in such a way that it is actuated by the same flux that passes through the relay disc. As the relay winding is connected directly in the circuit to be protected by means of
Speaker 1a current transformer, the current indicating element shows at all times the quantity of current flowing in the line. The current indicating element also gives a double protective assurance, inasmuch as any accident which a curves either within or without the relay to prevent the main electromagnet from operating the relay disc will also keep the indicating disk from operating.
Speaker 1Low energy type COO relay. Certain relay applications are such that only very little energy is available for operating the relay. This is especially the case on high voltage lines, where low ratio bushing type current transformers are the only convenient means for supplying energy for the operation of relays or instruments. A modification of the COO relay has been designed to
Speaker 1fit such conditions. This low energy co relay requires approximately two volt ampiers for tripping. In construction and operation, it is very similar to the standard COO relay, except that the contacts are not closed directly by the action of the disk, but through a train of gears. This train of gears also supplies the definite minimum time characteristics, thus
Speaker 1eliminating the torque compensator. Due to the construction of the relay, it is somewhat more sensitive than the other COO relays and is therefore suitable for use on applications requiring great sensitivity. The differential protection of generators is an example of this type of application. Type c R directional relay. All relays dependent on current alone for their operation function when sufficient
Speaker 1current is flowing in the winding regardless of the direction of the flaw. In protecting transmission lines and in making possible the sectionalizing of such lines on the occurrence of trouble, it is often necessary to have protective relays which will close their contacts only when current is flowing in one certain direction. The CR relay has been developed to fill these requirements. The CR directional relay is a combination of
Speaker 1the COO overcurrent relay and a watt element. The current element is the same as that of the standard COO overcurrent relay and has identical operating characteristics. The watt element is similar to the CW power relay, except that it operates on a very small percentage of normal voltage. The contexts of the overcurrent element are connected in series with the contexts of the watt element, and as this element
Speaker 1will close its contacts only when the power flows in one direction, the relay as a unit operates only when current is flowing in any given direction. As the relay has all the characteristics of the COO relay, the following conditions must exist before the tripping circuit is completed. One access current must be flowing. Two current must be flowing away from the bus bars or in the direction for
Speaker 1which the relay is connected. Three current must be flowing for a sufficient length of time. Thus, the directional element may close its contacts upon momentary surges of current in the reverse direction, or the overcurrent element may close its contacts on the flow of access current in the normal direction, But the tripping circuit is completed only when both elements
Speaker 1close their contacts. Low energy type CR directional relay. The low energy CR directional relay has been developed to be used in the same way as the standard CR relay, except that it is suitable where only a small quantity of energy is available for the operation of the relay. The low energy characteristic of the relay has been obtained
Speaker 1by substituting the low energy CO overcurrent element for the standard CO overcurrent element. Thus, the low energy CR relay has over current characteristics similar to those of the low energy CO relay and directional element characteristics similar to those of the standard CR relay type CRA relay. In cases where it is desired to have an indication of the
Speaker 1current flowing in the circuit, the CoA overcurrent element has been used in the CR relay in place of the standard COO element. This makes a compact, convenient arrangement serving the purpose of an AM meter without adding greatly to the expense of installation or detracting it all from the operating characteristics of the relay. Type c Z impedance distance relay.
Speaker 1On large complicated transmission systems, the method of sectionalizing by means of overcurrent and directional relays is often difficult to apply and sometimes even impossible. This is due to the necessity have enpoint such a large number of relays that it is impossible to keep the timing sequence within safe limits. At times, it is impossible to secure proper discrimination at all,
Speaker 1especially in the case of a complicated loop which is fed at several points and where the points of feed change with load conditions. The Westinghouse Company has recently developed a relay which overcomes all such difficulties experienced on large and complicated systems. Its application does not supplant that of the standard COO and CR relays, but makes protection possible
Speaker 1where otherwise it would be difficult or even impossible. The only requisite is that with a short at the far end of the line, the headen's drop in the line should be at least three point zero percent of the normal voltage. That is, the line must be of sufficient length to give this drop. The c Z relay consists of an overcurrent element and a voltage element. The overcurrent
Speaker 1element is similar to that of the CO relay. The special feature of this relay is the construction of the voltage element. The voltage element is so constructed that its action in relation to the closing of the relay contexts depends on the distance the relay is away from the fault. In other words, the voltage element acts in opposition to the overcurrent element, and when the relay is a considerable
Speaker 1distance from the fault, the voltage on the element is comparatively high, thus lengthening the time required for the relay to close its contacts. On the other hand, the relays near the fault will have a very low voltage imposed on the voltage element, thus causing the relay to operate in much less time due to less opposition being offered to the action of the overload element by the voltage element. Thus,
Speaker 1the relay that is nearest to the fault operates first, and at no time does the time exceed zero point seven five to one point zero second. For some applications, it is necessary to restrain the relay from operating unless the power is flowing in a given direction. To fill such needs, a directional element similar to that of the CR relay is added to the c Z relay. Type
Speaker 1CA ratio differential relay. The type CA ratio differential relay is a current operated induction relay similar in appearance to the type CO relay. As the name implies, it operates differentially, but it differs from the relays usually used in that the tripping current varies with the load. The current required to trip the relay increases in proportion to the line
Speaker 1current instead of remaining constant for all load conditions. This feature of the relay provides against faulty tripping due to a combination of through short circuits and variations of current transformer ratio, and allows the relay to be set for close protection at normal loads. Other methods of differential protection generally act on a difference of two currents, so that
Speaker 1a slight difference in current transformer ratios increased by heavy loads or by through short circuits is often sufficient to cause enough circulating current to operate the relay. The CA relay is designed to avoid this trouble and will trip out generators and motors on a trouble circuit as slow as two point five percent of the line current without danger of tripping them out on system troubles. For protection
Speaker 1of star delta transformer banks, Scott connected banks, or in any case where the currents in the circuits to be balanced are unequal, the relay is provided with taps so that balancing auto transformers are unnecessary, as saving any expense and in one switchboard space is made possible by the provision of these taps. This relay is less sensitive than
Speaker 1that used for generator protection in order to get the ratio feature of the relay. Both of the secondary currents to be balanced, as well as the differential current are used in the relay. A field proportional to the sum of the currents reacts with the field proportional to their difference, and the resultant field acts to produce rotation. The quadrature flux is supplied to the upper poles by transformer windings
Speaker 1on each of the lower poles. Figure eighty seven show schematically the connections of the CAA relay for the protection of a generator. The arrows show the relative instantaneous directions of current flow under normal conditions. If the currents supplied by each tree transformer are equal, there will be no current flowing Coil A. If the current transformers supply unequal currents, the difference flows through coil A. The direction of current
Speaker 1in Coil A with respect to coil B does not affect the tripping direction of the relay. The flux produced by coil B tends to hold the relay open, and that due to Coil A tends to trip the relay. As the line currents increase, the torque holding the relay open increases, and more torque and consequently, more current is required to close it. The relay for generator protection is provided with a tapped difference coil winding so that the
Speaker 1sensitivity may be varied readily. On the transformer relay, the conditions are very similar, except that both the sum coil and the difference coil windings are tapped in order to compensate for the effect of unbalanced currents. The sensitivity cannot be varied on this relay. The energy required to operate the relays, particularly the transformer relay, is very small. This,
Speaker 1combined with the fact that the operating current increases in proportion to the line currents, makes the relays very adaptable to conditions requiring the use of bushing type current transformers. When greater sensitivity is required, as in the case of the generator relay, the burden of the relay is somewhat greater, but under these conditions the current transformers used are of higher grade and the load is well within the capacity
Speaker 1of the current transformers. The relay is very rugged. There are no adjustments to get out of order and no delicateche panical parts to give trouble. The contexts are set well out in front where they can be seen through the glass cover and where they are easily accessible for adjustments or repair. All the relays are provided with two trip circuits and an operation indicator and contact or switch. As in the CO relay type C B over current relays.
Speaker 1The cost of the current transformers used with relays often forms a considerable part of the entire cost. Where the current transformers must be connected to high voltage circuits, they must be insulated for the high voltages and their cost is high. The CB relay has been designed for use on high voltage installations. It is a combination of the CO overcurrent relay and the BT transfer relay with the
Speaker 1addition of a special contactor switch. A standard transformer is used without regard to insulation for the high voltage line, and the CO relay element is connected in the usual manner. The COO and BT relays, however, with the current transformer are mounted on a slate base which is mounted on an insulator. The contactor switch is separate from this assembly and is connected to the BT relay by means of
Speaker 1a Makarta chain. Thus, the tripping circuit is insulated from the high voltage circuit, which is to be protected when the CO relay contacts close they serve to operate the BT transfer relay. This relay, in turn, by means of the Macarta chain, closes the tripping circuit contactor switch. The operating characteristics of the CB relay are the same as those of the standard CO relay type CD selective differential relay.
Speaker 1Balanced current protection is very often desired where two or more similar transmission lines are used to connect two stations or two different points in a system. Balance current protection on such lines means that each line normally carries approximately the same current, and if this condition does not exist, the line carrying the greater current must be in fault. The CD relay furnishes a simple method of securing such protection.
Speaker 1It avoids the necessity for any special apparatus such as split conductor cable, and as it operates on current alone, potential connections or potential transformers are not required. The relay operates on the induction principle and is in reality two overload elements so located that they act in opposition upon a common disc through a common magnetic circuit. Each element
Speaker 1is connected separately to its own current transformer and to corresponding phases of the two lines that are to be protected. These two elements are electrically opposed and under conditions a balanced line load, which will give approximately the same current in each element. The fluxes in the magnetic circuit of the relay are equal and opposite, giving a resultant zero torque in the relay disc. When a fault occurs in
Speaker 1either line, however, the current in that line will become greater, and the unbalanced will cause the relay to operate, tripping out the line in which the greater current is flowing. The CD relay has inverse time time characteristics and also a definite minimum time of operation with excessive overcurrent. The inherent characteristics of the relay are such that when one line of a pair is tripped out, double the normal
Speaker 1current is required in the other line before it will be tripped out, thus making it possible for one of a pair of protected lines to be open and the other line to carry its load without interference from the relay. Any number of lines may be balanced against one another, but the tripping out of certain lines in a group will necessarily destroy the balance connection between the remaining lines. The CD relay has the same current adjustment and time
Speaker 1adjustment as that of the CO relay. The time adjustment is, however, seldom of importance inasmuch as the relays usually are designed to operate almost instantaneous. Yes type CW power relay. In many instances, a motor is so connected to its load that, under certain conditions, the load may drive the motor, causing it to act as a generator. A mine hoist driven by an induction motor is a good example of such
Speaker 1an installation. In such cases, it is sometimes necessary to provide some sort of protection to ensure against having the motor return too much power to the line when it is being driven as a generator. The CW power relay serves this purpose. It is also often used to prevent undesirable or excessive interchange of power between parts of a system, as in the case of a small plant connected in
Speaker 1parallel with a larger plant, where some means must be provided to prevent the small plant from being subjected to the entire load of the system should the larger plant be suddenly disconnected. The CW relay is essentially a contact making watt meter. It operates on the induction principle and is similar to the CO relay, except that it requires both current and potential connections. It closes its context in
Speaker 1but one direction and only after a predetermined time when a predetermined quantity of power is flowing in a predetermined direction. Which direction may be either the normal or the reverse according to the way the relay is connected. The relay has a standard time adjustment in also taps for changing the wattage values necessary to trip the relay type CV voltage relay. The CV relay is designed for general use
Speaker 1when it is desired to have circuits or apparatus protected against voltage changes of any predetermined value. It operates to close a circuit, either for the purpose of disconnecting the apparatus or of actuating a signal. The time delay characteristic of the relay is used also in many applications where a timing device is desired. In these applications, the relay is used to close the circuit after a predetermined interval
Speaker 1when the relay winding is energized. This relay is similar in appearance to the CO relay and operates on the same principle. The chief difference between the two types is that the CVE relay operates on voltage, whereas the CO relay operates on current. The latest design of the CVE relay is provided with a voltage adjustment by means of which the operating voltage can be adjusted over a wide range.
Speaker 1Justment consists of a slide wire resistor connected in the upper pole circuit of the relay. The resistor is provided with a calibrated scale so that the relay can be readily set to close its contexts at the desired voltage value. The time adjustment of the relay is identical with that of the CO relay. One form of the CV relay closes its context only when the voltage is raised to
Speaker 1the operating point or above, and another form closes its context only when the voltage is lowered to the operating point or below that value. These two forms are called over voltage and under voltage relays, respectively. A third form is equipped with the front and rear contexts, the front context closed when the voltage is raised above the operating value, and the rear context close when the voltage is lowered
Speaker 1somewhat below that point. When a relay having a long time delay is desired, it is possible to supply a CV relay with a geared element similar to that of the low energy CO relay. With this relay, a time delay of as much as sixty seconds can be obtained type CP reverse phase relay. In many motor installations, it is very essential that the direction of rotation of the
Speaker 1motor always be in a given direction. This applies particularly to motors used in connection with control equipment, or for motors used for operating elevators, pulleys, conveyors, cranes, machine tools, et cetera. The reversal of phase rotation in a polyphase system caused by the reversal of two wires, although not of frequent occurrence yet, is liable to happen at any time when lines are being changed or repaired. Such a
Speaker 1reversal a phase rotation means a reversal in the direction of rotation of all polyphase motors connected to the line. The CP reverse phase relay serves to protect against such occurrences. It operates upon phase reversal or when any one phase of a polyphase circuit opens. In case of a phase reversal, the relay may serve to disconnect the motors from the circuit. However,
Speaker 1in case of one phase opening, with polyphase motors operating on the system, the relay will not operate until the motors have been stopped. Due to the fact that practically normal voltage is maintained on all phases by the motor. The relay will operate, however, as soon as the machines are stopped, thus prem from being again started. The CP relay operates on the induction principle and has two windings,
Speaker 1each of which is energized from a separate phase. The construction of the moving element is such that the disc is maintained in its normal position, with the contexts opened by the torque produced by the two windings. In case either winding is deenergized or the direction of current in one winding is reversed, the torque becomes zero or is reversed, and the context are closed by the reversed torque or the action of a spring. As the relay operates on
Speaker 1the induction principle and the closing of the context depends on the rotation of the disc, a time delay action is produced when the relay operates on low or unbalanced voltage. This time delay action is a very important characteristic of the relay because it prevents the relay from tripping upon the occurrence of momentary voltage disturbances in the line to which the relay is connected. Type C M phase balance
Speaker 1current relay. In installations where polyphase machinery such as rotary converters and motors, is used, it is necessary to have some protective means available whereby the machine will be disconnected from the source of power in case of an unbalanced condition of the current flowing in the phases, or in case of a phase failure where the apparatus would be compelled to operate on single phase. This protection is necessary
Speaker 1because a polyphase machine operating on a system with unbalanced faces or on single phase draws excessive current and may over heat. The CM phase balance current relay is used to prevent such occurrences. The CM relay operates on the induction principle and consists of four single phase current elements mounted in a single case. The four elements are mounted
Speaker 1in pairs, one pair being in the upper part of the case with its own disc, and the other pair in the lower part of the case with its disc. Each disk carries its own set of contacts, the two sets being connected in parallel in order that either disc may close the tripping circuit. The two current elements in each pair are mounted on opposite sides of the disk and are so connected that the torque produced by one bus that produced by the other. Therefore, when balanced conditions
Speaker 1exist on the system, there is no movement of the disc, but with an unbalanced or opened phase, the balanced condition of the disc is destroyed and the tripping circuit is closed. The relay has inverse and definite minimum time characteristics, and it gives protection for each phase because all phases are represented in the winding. The value of the unbalanced current necessary to trip the relay may be adjusted by means
Speaker 1of current taps, as in the CO relay type CQ phase balance relay. The CQ relay is designed to protect polyphase motors and rotary converters against running in case of an open phase, the reversal of phases, or in case of a three phase unbalanced such as is caused by a single phase short circuit. This is necessary because operation
Speaker 1with any of these conditions existing for considerable time will cause serious overheating. It is generally desirable to have machines disconnected from the line on as small and unbalanced condition as possible, and they should not operate on single phase currents at all with machines in isolated locations. However, it is sometimes desirable to have the machines kept on the line running on single phase or unbalanced current if the
Speaker 1load to be carried is not high enough to cause serious overheating or vibration in the machine. The CQ relay has current and time adjustments which make this operation possible wherever it is desired. The relay operates on the induction principle, the operating element being very similar to that of the CO relay. The winding of this element is so connected that under normal conditions of operation, no current is flowing
Speaker 1in it. However, with any unbalanced condition, current will flow through the winding, operate the element and close the contact, which may either actuate an alarm or disconnect the protected machine from its source of power. The CQ relay has an inverse time characteristic. Its construction is such that it is extremely sensitive to small quantities of unbalanced current. The
Speaker 1current necessary for operation may be adjusted, and the time required for the contact to close may also be changed. Its application is practically the same as that of the CM, but it is a much more sensitive and a later designed relay and should be used unless the CM is desired for some good reason. Type r F frequency relay. Sometimes it is desired to have the frequency of a
Speaker 1circuit or system maintained at a given value, or to have some means whereby a signal is given if the frequency varies from the given value. The F frequency relay is designed to take care of such applications and may be used either to disconnect the circuit or to simply actuate a signal when the frequency changes above or below the normal value. The relay consists of two coils operating
Speaker 1on a balanced lever. The coils are connected across the same source, one with a reactance and the other with a resistance in series. As long as normal conditions exist, a balance is maintained on the lever and the contacts remain open. A change in the frequency causes a change in the current flowing in the coil that has the reactance in series, whereas the current flowing in the other and resistance coil remains practically the same. This condition causes
Speaker 1an unbalance, which closes the contacts and serves to perform the required operation. The relay can be made very sensitive and is adaptable to a variety of applications. Type C operation indicator. In many installations where a number of relays are in service, a circuit breaker may be tripped by one of several protective relays. As each relay affords protection
Speaker 1against some special kind of fault in the line, it is highly desirable to know which relay has tripped the breaker in order to be able more easily to locate the trouble. As most protective relay is reset automatically as soon as the circuit breaker opens, it is difficult to determine which relay has operated without some auxiliary means. The operation indicator is the small coil serving to attract a
Speaker 1semaphore into a visible position when the coil is energized. This operation indicator may be installed within the case of all the standard types of protective relays and is connected in series with the tripping circuit. As soon as the relay closes its contacts, thereby closing the tripping circuit, the operation indicator is energized and attracts the indicator to the operated position. The indicator remains in this position until reset.
Speaker 1The hand reset of the indicator is so arranged that it may be actuated without removing the cover of the relay Chapter nine, Part one
Report of the Inquiry into the Role and Oversight of Private Security Contractors in Afghanistan - United States Senate Committee on.... This episode includes AI-generated content.
"Silent Sentinels Protective Relays for A-C and D-C Systems" by the Westinghouse Electric and Manufacturing Company is a pivotal exploration of the technology that safeguards electrical systems. This book delves into...
"Silent Sentinels Protective Relays for A-C and D-C Systems" by the Westinghouse Electric and Manufacturing Company is a pivotal exploration of the technology that safeguards electrical systems. This book delves into...
"Twentieth Century Inventions: A Forecast" by George Sutherland presents a visionary exploration of technological advancements anticipated in the 20th century. This thought-provoking work delves into the possibilities...
"Seeking a Human Spaceflight Program Worthy of a Great Nation" is an insightful review of the U.S. Human Space Flight Plans Committee, examining the aspirations and strategies for America's human space exploration...