Silent Sentinels- Protective Relays for A-C and D-C Systems

Silent Sentinels- Protective Relays for A-C and D-C Systems artwork

012 - Westinghouse Protective and Control Relays Part 2

Mar 5, 202633 minAudio
ShareXLinkedInFacebookWhatsAppEmail

Discover Silent Sentinels, a groundbreaking exploration into the world of protective relays and the intricate schemes that safeguard the generation, transmission, and distribution of electric power. This book stands as one of the earliest comprehensive resources on the subject, revealing how, despite the rapid technological advancements over the past century, the core principles of protective relays remain steadfast. Join Rick Jay as he navigates through the historical and technical landscape of electrical protection systems, providing insights that are both timeless and essential for understanding modern power infrastructure. This episode includes AI-generated content.

Audio and video play straight from the show's own hosting. PodSubs stores and serves no media.

Transcript

From the show. Tap a time to play from there.

Speaker 1Chapter nine, Part two of Silent Sentinels by Westinghouse Electric and Manufacturing Company. This lipribox recording is in the public domain Westinghouse Protective and Control Relays two direct current relays. Installations where direct current is employed are so few and

Speaker 1small in size as compared with the present day alternating current installations that their importance is sometimes overlooked. It must be remembered that there are still many applications where alternating current cannot be used, or at least where no means have yet been devised for using it instead of direct current. On such installations. Therefore, it is important to have depend relay service as protection against overcurrent, reverse current, and other

Speaker 1sources of trouble. Type D overcurrent relay. This type serves to furnish protection against overcurrent in direct current circuits. The relay is of the moving coil type with an electro magnet energized by a voltage winding. The winding on the moving coil is connected across a shunt in series with the line, and in this way receives a current proportional to the current flowing in the circuit to be protected.

Speaker 1The moving contact is carried by the moving coil and is held open by the action of a spring. The torque produced by current flowing in the coil opposes the action of this spring, and when the current reaches any predetermined value, the opposing action of the spring is overcome and the contacts are closed. The electromagnet field is highly saturated, and thus the action of the relay is unaffected by

Speaker 1voltage changes. The overcurrent relay may be adjusted to operate over a range with from forty to eighty millivolts impressed upon the winding type D reverse current relay conditions are often such that a reversal in the direction of current flow may prove very disastrous. For example, it requires a very small percentage of normal folow current to cause a

Speaker 1rotary converter to run away when running inverted. A slight modification of the D overcurrent relay makes its service a highly sensitive reverse current relay applicable for protection against such conditions. The moving coil used in the D reverse current relay is such that approximately two millivolts will cause the contacts to close. This tripping value may be adjusted to a

Speaker 1smaller amount by changing the relative position of the moving and stationary contacts. By using shunts of different capacities in series with the line to be protected, Almost any sensitivity required can be obtained. For example, suppose the relay is set to operate on one milli volt drop in a given direction and is connected to one hundred millivolte shunt. It will then trip when approximately one percent of bull

Speaker 1load current is flowing in the reverse direction. Type TO overcurrent relay. The TO relay serves practically the same purpose as the T over current relay, except that its action is not as sensitive and its construction is such that it can be supplied at a lower price. The relay consists of a two pole electromagnet serving to attract a

Speaker 1pivoted armature against the pool of a pelical spring. The tension of the spring determines the tripping point of the relay. The relay is suitable for use with a fifty millible shunt and may be adjusted to close contacts on from forty to eighty millivals Type m F flash relay. The flashing over of commutators on rotary converters has been the source of much trouble in the past, and although the

Speaker 1improvement of modern design has eliminated the possibility of such occurrences, to some extent, the trouble still exists. The MF relay has been developed for the purpose of instantly disconnecting a machine upon the occurrence of a flash over. The MF relay operates by having an armature attraction close its contacts. The coil serving to attract the armature is connected directly

Speaker 1between the frame of the machine and the ground. As flashovers usually occur between insulated circuits and the frame of the machine, this arrangement will give immediately a flow of current to ground through the relay coil, which acts almost instantaneously to disconnect the machine from the line. The action of the MF relay is so fast that with the ordinary flashover, the machine will be disconnected before other protective

Speaker 1relays farther back on the system have time to operate, thus cutting out on the machine without disturbing the rest of the system. Its speed also aids in disconnecting the machine before any great damage has been done, type a polarity directional relay. In many electrochemical processes, a current reversal, even of small magnitude is serious, in many cases, serious

Speaker 1enough to cause considerable damage. Such conditions give reasons for the development of a relay to prevent any reversal of polarity. The type A polarity directional relay fills the requirements for such protection and is applicable also to other uses where a check on the direction of polarity is desired. The relay consists of a polarized electromagnet serving to attract the

Speaker 1soft iron armature the one polar The permanent magnet consists of two steps, upon which are placed the two coils of the relay. The relative action of the current flowing in these coils with respect to the pole of the permanent magnet on the soft armature determines the operation of the relay. Its sensitivity and design are such that the context will be closed upon any reversal polarity of the

Speaker 1circuit to which it is connected, and upon the fall of the voltage to below twenty percent of normal upon the occurrence of an open circuit in the relay winding itself. Action of the relay is assured before any voltage has built up in the reverse direction. Type t V voltage relay, wherever it is desired to protect direct current circuits against excessive over voltage or under voltage a slight modification to

Speaker 1the t V overcurrent relay may be used. The too overcurrent relay with the coils wound for voltage constitutes the TV voltage relay and is applicable for such voltage protection. Three temperature relays type h M bearing thermostat relays type HM relays are designed for use in protecting the bearings

Speaker 1of rotating machinery from the disastrous effects of overheating. With this relay installed, it is unnecessary to have constant supervision of the bearings of rotating machinery. This relay is particularly valuable in automatic substation work. The action of the thermostat is largely mechanical. It consists of the operation of a toggle switch by means of the ex expansion of a bellos.

Speaker 1The thermostat unit consists of a bulb which is to be embedded in the bearing, the connecting tube, and the expansion bellos. As the temperature of the material in which the bulb is embedded rises, the liquid enclosed in the bulb and bellows moollatizes and thus creates a pressure, causing the bellows to expand lengthwise. This expansion serves, in turn to operate the toggle switch thereby closing the contexts of

Speaker 1the relay. The relay usually is made to operate at one hundred degrees, but different thermal elements having the temperature of operation seventy degrees, ninety degrees or one hundred degrees centigrade may be supplied Type H N grid thermostat. A slight modification of the HM thermostat is used for the protection of grid resistors from damage due to overload or

Speaker 1to sustain short circuits on the system. The construction of this relay is largely the same as the HM, with the exception of the manner of resetting. This HN relay resets automatically, whereas the HM relay has to be reset by hand. The thermal element supplied with the HN relay is also somewhat different, giving operation at either one hundred and fifty degrees centigrade or three hundred degrees centigrade Type

Speaker 1CT temperature relay. The problem of protecting electrical apparatus against over temperature presents many difficulties. The object in any such protective apparatus is to allow the protected machine to remain in service as long as it is safe to do so, and yet to disconnect it from the source of power as soon as the temperature becomes unsafe for further operation. In order to obtain the most efficient protection, a relay

Speaker 1used for this purpose must take into consideration the ambient temperature, the speed with which the windings of the apparatus heat up when subjected to overload, and the conditions existing when the temperature of the machine becomes dangerously high. The CT temperature relay is applicable on alternating current circuits where the apparatus is so arranged that exploring coils can be installed

Speaker 1in the windings. It operates on the wheatstone bridge principle, the moving part operating on the induction principle. The relay in its appearance is similar to the type co over current relay. The lower coil is directly connected to a current transformer in one lead of the machine which is to be protected. The upper coils are connected across the two points of the bridge arrangement to which the galvanometer

Speaker 1is ordinarily connected. Two permanent resistance units mounted in the relay case serve for two arms of the bridge, while two copper exploring coils embedded in the winding of the apparatus to be protected served for the other two arms. The points of the bridge opposite those connected to the upper coils, are connected to the current transformer in parallel with the lower coil of the relay. The resistances of

Speaker 1the different arms of the bridge are so arranged that at normal operating temperature, no current flows through the upper winding of the relay. When the apparatus becomes heated, however, the resist distance of the arm formed by the exploring coil changes, thus destroying the balance and causing current to flow through the upper coils of the relay. This produces a torque tending to rotate the disks and to close the contexts. As it is necessary to have a certain

Speaker 1quantity of current flowing in both the upper and lower coils of the relay before the disc will rotate to close the contexts. The operation of the relay depends upon three conditions. One, the temperature of the material surrounding the coils must be such as to cause an unbalanced sufficient to send current through the upper coils of the relay. Two, the current flowing in the line at that time must be such as to give a sufficient current value in

Speaker 1the lower coil of the relay. Three, heat that has been generated in previous overload but then has not yet been dissipated, tends to influence the temperature of the exploring coil type DT temperature relay. The DT temperature relay is simply a modification of the D over current relay used in connection with a wheatstone bridge. Its use is similar

Speaker 1to that of the CT relay, except that the DT depends altogether on direct current for its operation and does not take into consideration the current flowing at the time when a critical temperature is attained, as in the case of the CT relay. The operating coil replaces the governometer connection in the bridge circuit. The two opposite points of the bridge are connected across the constant direct current source

Speaker 1of voltage. The two opposite points of the bridge are connected across a constant direct current source of voltage. Three arms of the bridge are made up of fixed resistance, while a fourth arm consists of a copper exploring coil embedded in the winding of the apparatus to be protected. The resistance values of the arms of the bridge are so proportioned that when the temperature of the apparatus reaches

Speaker 1a safe operating point, there is no appreciable current flowing through the relay moving coil winding. With a low temperature in the winding of the apparatus, current will flow through the relay coil in one direction, and with a high temperature current will flow in the other direction. Thus, with low temperature contact is made in one direction, while with high temperature contact is made in the opposite direction. From this,

Speaker 1it is evident that the operation the relay depends solely on the temperature of the windings in the apparatus, leaving out the consideration of the current drawn by the apparatus at the time the critical temperature is reached. This relay, therefore is applicable wherever a constant source of direct current voltage is available and where the load conditions may be disregarded. Type B A and B D oil filled thermal relays.

Speaker 1Another type of temperature relay which does not require the use of exploring coils embedded in the windings of the apparatus to be protected, has been developed. This type depends upon the expansion of a bimetal element. The element has characteristics such that it heats up at the same rate as the windings of the apparatus to be protected. In order to further duplicate take the temperature rise of the protected apparatus. The bimetallic element is immersed in oil, and

Speaker 1the walls of the container are such that the dissipation of heat will be approximately the same as in the case of the apparatus to be protected. The operation of the relay is simple. When the bimetallic element heats to a certain temperature, it expands sufficiently to operate the relay, closing its contexts. The BA relay is suitable for use on alternating current circuits. The BD relay is suitable for

Speaker 1use on direct current circuits. It is similar to the BA relay in construction and operation. A cartridge type of relay, which is not oil filled, is made suitable for either alternating current or direct current application where high precision is unnecess The operation of the cartridge type relay is dependent on the expansion of a bimetallic element in the same way as that of the BA and BD relays, except

Speaker 1that precautions are not taken in the relay to have its temperature rise identical in degree with that of the rise in the protected apparatus. Four auxiliary relays. In the design of relays, as with any other line of apparatus, it is desirable to adhere to the simplest plan possible. Many relay applications require only a single simple contact arrangement, while others require a more or less complex scheme of

Speaker 1interconnected contexts. Rather than complicate the design of any one type of relay to take care of these more complex applications, several different relays are sometimes used to accomplish the purpose designed. In such applications, one relay is usually responsible for starting a sequence of contact operations. This is termed the main or primary relay of the application. The other relays simply

Speaker 1service contactors, their coil or coils being energized by the action of the primary relay. These relays are termed auxiliary control relays type BT transfer relay. In most relay applications, where the relay serves to energize the trip coil of a circuit breaker, direct current is used as the source of energy for the trip coil. In some cases, however,

Speaker 1it is desired to use alternating current taken from the current transformer to which the relay windings are connected. In such cases, it is necessary to provide some contact arrangement whereby the secondary circuit of the current transformer will be closed at all times, and whereby the trip coil of the circuit breaker will be simply inserted in series with the transformer secondary when the relay operates. To energize the trip coil, the BT transfer relay is used in connection

Speaker 1with the primary protective relays to accomplish this purpose. The main winding of the relay is connected in series with the secondary of the current transformer and the winding of the primary relay and serves to hold the contacts in the normal position. When the primary relay closes, its contacts, the short circuit and auxiliary winding on the BT relay and cause the contacts to operate and thereby cut the trip coil of the breaker into the circuit. The design

Speaker 1of the contacts is such that when they are in the normal position, the trip coil of the circuit breaker is mechanically and electrically isolated from the current transformer circuit. The windings of the relay are designed to carry five ampiers continuously, but during times of short circuit they may be required to handle as much as one hundred or two hundred ampiers. This can be done satisfactorily for a

Speaker 1short period of time type m C multi contact relay. In the application of protective relays, it is often desirable to have several circuits energized at the time the primary relay operates. As most of the standard protective relays close only one or two circuits when they operate, auxiliary relays are necessary when it is essential to have more than

Speaker 1the two circuits closed. Another case one auxiliary relay is needed is when the current required in the control circuit which is to be closed by the action of the primary relay is greater than the context of the primary relay can safely handle, as in the case of the multiple circuit requirements. Auxiliary relays are used to accomplish this purpose, the relay winding being energized by the closure of the primary relay contacts. The MC multiple contact relay fills either

Speaker 1of the purposes just described and is used also in many other control installations where a simple multiple contactor is required. Its design is simple and such that it is suitable for operation either on alternating current or direct current circuits, and may be allowed to remain energized continuously. The action of the relay is positive and windings may be supplied which are suitable for various values of alternating current or

Speaker 1direct current voltage. There are also a variety of contact arrangements which may be supplied. Thus, standard contact arrangements are first four independent makes second three makes one break all independent, third two makes two breaks all independent, fourth one make three breaks all independent, fifth five makes one brake all parallel,

Speaker 1sixth one independent, make five parallel brakes, seventh four parallel and one independent makes eighth six parallel makes Type M multiple contact relay. The Type M relay is similar to them, but is simpler. It is suitable for use only on direct current and is intended only for intermitted service. This

Speaker 1relay is furnished with either two, four or six contacts, the first having the independent and the last two the parallel arrangement. Type MS banked Multi contact relay. The MS relay consists of a group of ten different and distinct contactors, similar to the MC assemblies, except that each contactor operates only two contacts, or in other words, makes only two

Speaker 1complete circuits. The ten units are mounted in a neat case, and the complete assembly is used on supervisory control systems wherever it is necessary to insulate the low voltage telephone equipment from the higher voltage power control circuit. The coils of these contactors may be supplied for various values of voltage. In the entire group of relays may be applied to various applications wherever it is desirable to have a number

Speaker 1of contactors in as compact an arrangement as possible. Type O line of auxiliary relays. The O line of auxiliary relays is intended for miscellaneous switchboard and control use. Arrangement usually is such that the auxiliary relays are energized by protective or other primary relays, and they in turn energize or deenergize any desired combination of circuits. They have instantaneous

Speaker 1time characteristics. The O relays are so designed that when placed in a normal position and with the main coil deenergized, they make a set of four contacts, and when in the operated position, a second set of four contacts. The interconnection between the four sets of contexts may be changed so that a large number of circuit combinations are obtainable, thus making the relay adaptable to a variety of applications.

Speaker 1There are four types of the O line of relays, classified according to the method of resetting. Type OA. The OA relay has a main operating coil only and resets itself automatically as soon as the excitation is removed from the main coil. Type OL. The OL relay has only the main coil, but it has a latching mechanism which latches the context in the operated position as soon as

Speaker 1the coil has been energized and holds them until the latch mechanism is tripped by hand. Type OS. The OS relay is equipped with a main coil to operate the relay, and also an auxiliary coil which serves when energized, to hold the context in the operated position after the main coil has been deenergized. This type of relay resets automatically

Speaker 1if the holding coil is not energized, and otherwise resets when the holding coil is deenergized. Type O X. The OX relay is equipped with a maine coil and also an auxiliary coil which is located similarly to that of the OS relay. It has the latching mechanism so arranged that when the relay operates, the contacts are locked in

Speaker 1the energized position until the latch is tripped either by means of energizing the auxiliary coil or by hand coils, which are suitable for operation on various alternating current and direct current voltages may be supplied for the various types of relays. On account of vibration, only the latching types are satisfactory. On AC The contexts are of sturdy construction

Speaker 1and will carry ten ampiers continuously or will break five ampiers at five hundred volts satisfactorily. Type g K long time limit relay. It often is desirable to introduce a time interval of considerable length between control switch operation, mechanical operation, or factory process is where a series of operations occur in sequence. A specific example of such application is in

Speaker 1the case of automatic railway substations, where various operations must be correctly timed. The GK relay is used for this purpose. It consists of a small motor driving a contact assembly through a train of gears. The contacts of this relay are carried on a drum connected to a worm gear. This worm gear is engaged with the driving gear by an electromagnet, either simultaneously with the starting of the motor

Speaker 1or at a certain definite interval after the motor has been started. The GK relays may be supplied with a time limit as high as forty minutes. Relays whose time can be adjusted to from one to ten minutes can be supplied on special orders. Type j M group nunciator. Many features in electric service stations require operation indicators. To

Speaker 1satisfy this need, the Westinghouse Company has developed the Type JM group annunciator, which comprises a group of twelve operation indicators assembled in a glass covered case similar to that of the Type MC relay. The twelve indicators are mounted in four rows of three each and are all connected in parallel. That is, each has one terminal stud for one side of the line, and all the indicators are

Speaker 1connected to a thirteenth stud which goes on the other side of the line. The indicators of this annunciator are similar in appearance to the Type C operation indicators described elsewhere in this book, but they differ for somewhat from theasing construction. The target, which is made of non magnetic material, is latched in place behind the front plate. When the indicator coil is energized, the latch is pulled back, allowing

Speaker 1the operating spring to pull the target into view. All indicators can be seen readily through the glass cover of the relay. They are reset without removing the relay cover by pulling a small knob which protrudes from the right side front view of the relay case. There is a separate reset knob for each roll of indicators, or four for the relay. Portable phase indicator for use in making

Speaker 1relay connections in order to obtain correct operation. When connecting a relay which requires both current and voltage connections to a poly phase circuit, it is necessary to select the current and voltage having a proper phase relation to each other. One of the most convenient methods of checking such relay connections is to use a Westinghouse phase indicator. The phase indicator is a portable instrument built on the same principle

Speaker 1as is a power factor meter. However, the phase indicator is calibrated to indicate degrees from zero to three hundred and sixty instead of power factor percentages. It readily shows the exact phase relation between any current and voltage to which it may be connected. The phase indicator can also be used to check the phase relation between two or more currents. An example of such an application is the

Speaker 1checking of relay connections for differential protection. To select the two current transformers, the secondaries of which should be connected together, it is necessary only to select some voltage for uses of reference, and then to measure the phase relation of the different currents with respect to this reference voltage. End of Chapter nine, Part two,

Open the transcript file

Hosts and Guests

Nobody is credited on this episode yet.

Credit the people on this episode

Be the first to rate this episode

More episodes

All episodes
  1. Report of the Inquiry into the Role and Oversight of Private Security Contractors in Afghanistan - United States Senate Committee on...

    Nov 21, 20265 hr 54 minAudio

    Report of the Inquiry into the Role and Oversight of Private Security Contractors in Afghanistan - United States Senate Committee on.... This episode includes AI-generated content.

    Credit the people on this episode

  2. Silent Sentinels Protective Relays for A-C and D-C Systems-Westinghouse Electric and Manufacturing Company

    Nov 14, 20264 hr 27 minAudio

    "Silent Sentinels Protective Relays for A-C and D-C Systems" by the Westinghouse Electric and Manufacturing Company is a pivotal exploration of the technology that safeguards electrical systems. This book delves into...

    Credit the people on this episode

  3. Silent Sentinels Protective Relays for A-C and D-C Systems-Westinghouse Electric and Manufacturing Company

    Oct 31, 20264 hr 27 minAudio

    "Silent Sentinels Protective Relays for A-C and D-C Systems" by the Westinghouse Electric and Manufacturing Company is a pivotal exploration of the technology that safeguards electrical systems. This book delves into...

    Credit the people on this episode

  4. Twentieth Century Inventions A Forecast-George Sutherland

    Oct 30, 20266 hr 42 minAudio

    "Twentieth Century Inventions: A Forecast" by George Sutherland presents a visionary exploration of technological advancements anticipated in the 20th century. This thought-provoking work delves into the possibilities...

    Credit the people on this episode

  5. Seeking a Human Spaceflight Program Worthy of a Great Nation-Review of U.S. Human Space Flight Plans Committee

    Oct 29, 20269 hr 8 minAudio

    "Seeking a Human Spaceflight Program Worthy of a Great Nation" is an insightful review of the U.S. Human Space Flight Plans Committee, examining the aspirations and strategies for America's human space exploration...

    Credit the people on this episode