Software can find, sort and check only what someone has described in terms it can recognise. I am Dr Sepehr Abrishami, this is Reimagining AEC and its season on the ISO standards, and my doctoral research, completed in 2015, joined building information modelling to artificial intelligence, where an algorithm is only ever as good as the descriptions it is given. This episode is about classification and structured data, as ISO 12006-2 sets out a framework for classifying construction information, with Uniclass as the system UK practice builds on that framework. Beside it sit ISO 23386, a method for defining and governing properties, and ISO 23387, a structure for data templates.
The case is a school campus, and it is hypothetical. A council is building it. The campus has a teaching block, a science laboratory inside that block, external walls with curtain walling on the main elevation, and an air handling unit serving the laboratory. The council's appointment documents carry one sentence on the subject. All information shall be classified to Uniclass, and objects shall carry sufficient information for their intended purpose. The mechanical tender comes back. Three bidders have each returned a performance figure for the air handling unit, and the figures cannot be compared, because each bidder measured at a different operating point and none said which. On the design side, the architect has coded the curtain walling as an element and the facade contractor as a product, one to two levels of detail and the other to four. Everything is digital. Nothing can be selected, compared or checked by software. The council must now choose between picking a bid on a guess and sending the tender back, which costs weeks. Nobody broke the requirement. It asked for almost nothing, and it looked complete enough that nobody asked what was missing.
So the question for this episode is what it takes for information to be machine readable rather than merely digital. By the end you will be able to take a one-line requirement like the council's, say what is missing and which standard supplies it, and write a classification requirement and a structured data requirement that a supplier can price, answer and be tested against.
We will get there in six steps. The three jobs machine readable information needs, and the standards behind them. The classification framework and where it stops. Uniclass, including how to read a code aloud. Properties and their data dictionaries. Data templates, and who supplies their content. And the two requirements, written so that someone can test them. The campus stays with us throughout.
The first step is diagnosis. Four failures will be familiar to anyone who has received information on a project, and they sound like one complaint about bad data. You cannot find something, because there is no agreed way of saying, in terms software can select on, that an object is an external wall. You cannot filter, because the replacement cycles a maintenance team needs are spread across twenty spreadsheets whose column headings all mean slightly different things. You cannot check, because fire performance data arrived as a sentence that a person can read and nobody can test for completeness. And you cannot carry information forward, because six months after handover the operator cannot match an asset in the maintenance system to an object in the design.
Those failures do not share one missing piece. A machine needs three different things before it can act. It needs a name for the thing, a code from a system everyone uses in the same way, so that selecting all the external walls returns all of them and nothing else. That is classification. It needs a statement of how much information is required, for a stated purpose, at a stated point in the work, or nobody can say whether what arrived is enough. That is the level of information need. And it needs a structure for the answer, a defined set of properties, each with a name, a data type and a unit, so the answer comes back in a shape software can read. That is the data template.
Cannot find is a classification failure. Cannot check is usually a level of information need failure. Cannot filter and cannot carry forward are usually structure failures. And the fix for one does not fix the others.
Each need has its own standard. Classification is governed by ISO 12006-2, the framework, and in the UK the implementation of that framework is Uniclass, a different document with a different life. The level of information need is governed by ISO 7817-1 of 2024, which has its own episode, Level of Information Need in ISO 7817-1. This episode touches it at one point only. ISO 7817-1 divides alphanumerical information into identification and information content, and gives classification as an example of identification. So classification sits inside the level of information need rather than competing with it. The data template is governed by ISO 23387, whose second edition was published in 2025, and the properties inside a template are governed by ISO 23386.
Run the campus through that diagnosis. The curtain walling coded two ways is a classification failure. The three air handling unit figures are a structure failure, because the property had no stated measurement conditions. And the second half of the council's sentence, the part about sufficient information, is a level of information need requirement, written badly and placed in a classification clause, which can never be met because nobody knows what sufficient means.
A word of care about the argument often used to justify all this. In England the golden thread duties for higher-risk buildings are real and specific. Regulation thirty-one of the Building (Higher-Risk Buildings Procedures) (England) Regulations 2023 requires the information to be kept electronically, transferable without loss or corruption, accurate and up to date, intelligible to its intended readers, secure from unauthorised access, and changed only under procedures that record who made the change. It does not use the words structured, machine readable or interoperable, and it names no information standard. The Building Regulations Advisory Committee's golden thread report of July 2021 did say the information should be stored as structured digital information, but that is advice to government, not the operative law. So a supplier who calls structured data a legal requirement is overstating the law. The honest case is commercial and operational, and it is strong enough.
That settles the diagnosis. Machine readable means a shared name, a stated quantity and a defined structure, supplied by three different standards. A requirement that names one of them is answered on that axis and left open on the other two.
The second step is the framework itself, because knowing it lets you appraise any classification system, not only the one you were given. Start with what ISO 12006-2 refuses to do. It gives a structure for building a classification system, with recommended table titles and informative examples. It does not give an operational system, and says so in its scope, so a project that promises to classify to the international standard has promised something that cannot be done. It does not give the content of the tables. And it expects local variation, because the benefit of following it is not that systems become identical. It is that they can be mapped to one another.
The framework hangs off a model one sentence long. Construction resources are used in construction processes, and the output of those processes is construction results. The resources are products, aids, agents and information, where agents are people and organisations. The processes run from pre-design, through design and production, to maintenance, so the whole life cycle is covered. The results are complexes, entities, built spaces, elements and work results. The difference between a resource and a result lies in its relation to a process, not in the object. A reinforcement bar in a warehouse is a resource. The same bar, installed, is a result. Nothing about the bar changed.
The classes fall into groups related to resources, processes and results, with property standing on its own. At clause four point six the standard says that a property can define and subdivide a class, and that a property has an identity of its own rather than existing only as an attribute of something else. That is why properties later get their own standard and their own dictionaries. Annex A recommends twelve tables in all.
Four definitions settle most arguments. A construction entity, at clause three point four point two, is one physically independent construction serving at least one function or activity. A construction complex is a group of neighbouring entities that together serve a function, so two buildings a mile apart are not a complex. A construction element, at clause three point four point three, is a part of an entity picked out by its function, form or position, and for purposes such as cost analysis elements must be mutually exclusive, so nothing is counted twice. And a built space, at clause three point four point four, is a space bounded by construction or natural surroundings and there to be occupied.
Now the campus, from definition to class. The campus is several neighbouring entities serving education, so it is a complex. The teaching block is physically independent, so it is an entity. The science laboratory is a bounded space for occupation, so it is a built space, not an element, even though it sits inside a building. The external wall is a part of the entity with a characteristic function, form and position, so it is an element. The definition decides the class, the class decides the table, and only then does the table decide the code. The commonest error is to open a table, find something that looks close and take its code.
Each class is divided by what the standard calls a principle of specialisation, and the result is a table. Where a second principle matters for the same class, the standard does not blend the two. It produces another table, so that every table has one logic and can be queried. Complexes, entities and built spaces divide by form, function or user activity. Elements divide by function, form or position. And work results divide by the work done and the resources used.
Then comes the rule, stated as a shall. An object shall only be of one class, and within a table an object shall only have one classification. That does not mean one code in total. Our external wall takes a code from the elements table, and may also carry a systems code, product codes for the products in it, and a code for the work that creates it. What the rule forbids is two codes from one table on one object, or one object in two classes, because both make queries unanswerable. No single table serves every purpose, which is why there are twelve.
One more distinction decides whether a query works. The type-of relation is classification proper, in which a framed roof structure system is a kind of roof structure system, and going down makes the kind narrower. The part-of relation is composition, in which a wall is part of the teaching block, and going down makes the thing smaller. A cost manager rolling up quantities uses composition. A specifier selecting every object of a kind uses classification. Mix the two in one table set and both get wrong answers without knowing why. The standard also leans, where there is a choice, towards keeping an object stable and adding a property, so that a load bearing wall stays a wall that carries a load bearing property. The more is handled by property, the more properties need governing.
Conformity is specific but not restrictive. A conforming system uses the framework's classes and definitions and states the principle dividing each table. It may add tables outside the recommended set, and clause four point five gives the route, building such a table to the guidelines in ISO 22274, but only with a supporting document stating the sorting criteria and the scheme. Departing from the recommended set is permitted. Departing silently is not, because the supporting document is what lets someone map to the system after its authors have moved on. Systems that do not align can still be mapped, the UK National Foreword says, but with greater variance, so budget for verifying the mapping as well.
So the second step resolves on the framework's limits. A table set cannot say how much information is required, cannot define a property, cannot carry the answer, and cannot classify user activity, which the standard puts outside its scope. It says what a thing is, and it says that well.
The third step is Uniclass, held against that framework. Uniclass is a unified set of classification tables for the built environment, maintained by NBS and free to use on personal and commercial projects under a Creative Commons Attribution NoDerivatives licence. NBS states that its tables were developed in accordance with the framework, so everything in the second step applies directly. And it is a rolling release, updated quarterly, with each table versioned and dated independently. At the July 2026 release, published on the twenty-first of that month, four tables changed, Products, Systems, Activities and Spaces and locations.
Uniclass is not an International Standard and not a British Standard. What BSI publishes is the UK adoption of the framework, BS EN ISO 12006-2. Uniclass has no editions in the way a standard does. And you may not modify it, because the licence lets you use and share the tables but not adapt them or add codes. A project that invents three codes to fill a gap has produced something that is no longer Uniclass and will break at the next release. The route for a missing code is a change request to NBS.
There are fifteen tables, and the useful way to hold them is by how they line up with the framework. Ten correspond cleanly. Complexes, Entities, Spaces and locations, and Elements and functions match the result classes. Products, Roles, Tools and equipment, and Form of information match the resource classes. Project management matches management, and Properties and characteristics matches property. Five do not correspond. Systems and Activities have no direct counterpart in the recommended set, and Materials, Risk and the table for computer aided design sit beyond it. None is a defect, because the framework anticipates extra tables. Notice what is missing too. There is no construction process table and no work result table, so a UK project uses something else for those, most often a cost breakdown structure.
The Systems table is the case worth understanding, and the campus curtain walling shows why. It is a part of the teaching block with a characteristic function, so arguably an element. It is manufactured, so arguably a product. It is really neither. It is an assembly of products working together, specified, procured and installed as one. The framework defines a construction system in its terms but recommends no table for systems, and Uniclass publishes one. That is why both the architect and the facade contractor in the hook could defend their codes, and why a requirement naming only elements and products leaves the systems layer unspecified, which is where most performance requirements attach.
There is also a live conflict worth knowing. The UK National Foreword printed in the framework maps its classes onto Uniclass tables, and it is out of date. It maps construction elements to a table it calls E e, where the published table is Elements and functions, coded E F. It maps construction aids to a table called C A, which does not exist, where the equivalent is Tools and equipment, coded T E. The foreword was accurate when printed, and the tables moved on. So the framework wins on the framework, meaning classes, principles and conformity, and the current release wins on the table set, meaning which tables exist and what they are called. A document citing table E e or table C A tells you roughly how old it is.
Now a code, read aloud. The first two letters identify the table. Then come up to four pairs of digits, separated by underscores, standing for group, sub-group, section and object, each one narrowing the kind. The letters are read one by one, each pair of digits is read as a whole number, the underscore is not spoken, and a leading zero is read as oh. Take a code from the Systems table, current at the July 2026 release. S S, thirty, ten, thirty, twenty-five. S S is the Systems table. Thirty is the group, roof, floor and paving systems. Ten is the sub-group, roof structure systems. The next thirty is the section, framed roof structure systems. And twenty-five is the object, heavy steel roof framing systems. It is a type-of hierarchy, so rolling it up gives totals by kind, not by assembly.
Reading an unfamiliar code takes four questions, in order. Which table, from the two letters, because the commonest coding error is a code from the wrong table. How many levels, because a code with three pairs of digits is complete in one table and a level short in another, and the code alone will not tell you which. What each level means, remembering that levels mean nothing outside their own table. And whether it is current against the release the project named, which is the step everybody skips. A code tells you the kind, and how narrowly. It does not say how much information is required, and it carries no values, no fire rating and no thermal transmittance.
The most misread table is Properties and characteristics. It sorts kinds of property into families, such as what identifies an object and how it performs, which helps check that a property set covers the ground. But it holds no data type, no unit and no permitted values. It classifies properties. It does not define them. If someone says the project's properties are sorted because it uses that table, ask for the data type and unit of any one of them.
The UK requirements sit in two National Annexes doing two jobs. Clause N A five point two of the UK National Annex to ISO 19650-2 covers classification within information containers, meaning the objects inside, and says it should follow Uniclass. Clause N A two point one point one of the UK National Annex to ISO 19650-4 covers classification of the containers themselves, using the Uniclass Project management table. Classifying the external wall falls under the first annex. Classifying the Stage 3 spatial coordination report as a container falls under the second, which lets a reviewer find everything issued for a review. The Part 4 annex reads almost like a ready-made requirement, and it asks for four things. Classify to Uniclass and identify the scheme as Uniclass, so it is recorded rather than assumed. Version the classification, either by the date of the snapshot or download in the international date format, or by the table version identifiers. Align with breakdown structures such as cost or maintenance where a purpose needs one. And hold code and description as a pair, preferably in separate properties, because a machine reading a joined string has to parse it.
Last in this step is where classification is held. The UK expectation, set out in the transition guidance PD 19650-0 of 2019, which BSI has since withdrawn and which I cite here as history, was that classification lives in metadata and not in the container naming convention, and the National Annex keeps the identifier and the metadata apart in the same way. The identifier names a container, and classification sits as an attribute beside status and revision. There is one qualification. When a container is exported from the common data environment, metadata may be appended to the identifier, but only as far as the project's information standard defines which fields, in what order and with the same delimiter. The episode The Common Data Environment: Process Before Platform covers naming and attributes in full.
Here is where Uniclass leaves us. It implements the framework closely, goes beyond it deliberately with Systems, and changes every quarter. A requirement that names Uniclass without a release, without tables and without saying where codes are held has pinned nothing down.
The fourth step crosses a boundary. Everything so far identifies things. From here on we deal with what is known about them. Begin by separating three things often treated as one. A classification table says what a thing is. A data dictionary is, in the standard's own spare definition, a database that contains metadata, which here means the definitions. Properties, groups of properties, object types and templates live in a dictionary and are governed there. A data template is a structure for describing the characteristics of objects, a view assembled from the dictionary for a purpose. The dictionary is the place, and the template is the view. Confuse them and nobody can say where a definition lives or who may change it.
ISO 23386 of 2020, confirmed on review in 2025, sets the attributes with which a property is defined and the method by which properties are authored and maintained. It refuses the content. That is the second time we have met this shape, and the template standard will make it three. Each gives structure and leaves content to someone else, fixing only what has to be the same everywhere for exchange to work.
The reasoning behind ISO 23386 assumes there will never be one central authority for every property in construction. There will be a network of independent dictionaries, each with its own committees, held together because they describe their content with the same attributes, so a property in one can be mapped to a property in another. The aim is not that everyone uses the same properties. It is that everyone describes them the same way.
The attribute list is long, and what organises it is who supplies each attribute. The dictionary supplies identity and life cycle, a globally unique identifier, an active or inactive status, and the dates of creation, change and deactivation. The standard calls these calculated. An obsolete property is deactivated and kept, not deleted, because information recorded against it still has to mean something. The author supplies meaning, measurement, relationships and context. Measurement uses the international system of units, and a property with no physical quantity, such as text, is marked as having none rather than left blank, so a machine can tell not applicable from not yet answered. Three mandatory attributes fall to the author. A definition in international English and in the creator's own language. The group or groups the property belongs to. And the country or region where it applies, because a fire classification means different things under different regimes.
Groups of properties carry a mandatory category from a closed list, and the list shows that a group is more than a folder. It can stand for a class, but it can also hold the parts of one composed property, or every property drawn from one reference document. Groups nest, and sub-groups inherit every property on their parent, so requiring a sub-group requires its parent's properties too, which is either what you wanted or a surprise.
The second half of the standard is governance. A user who needs a property raises a request carrying its identifier, a detailed comment, contact details, the applicant's language and the nature of the request. Experts appraise it, and each can record that a request lies outside their competence. The outcome is validated, rejected, or a request for more information, and the content is always validated by experts, not by whoever asked. The natures of a request form a closed list of six, creation, modification, deactivation, replacement, fragmentation and merging, and the last three break requirements. If a property named in an appointment is fragmented into three, the appointment still names a deactivated property, and its replacements appear nowhere in your documents. The dictionary has improved and the requirement has not kept up. So a requirement records the version of the property set it was written against, for the same reason it records the Uniclass release.
The standard also requires management rules for mapping between dictionaries, so that change requests pass to the dictionaries a change affects. That is the reason to prefer a governed property over one invented for the project, which is quicker today, maps to nothing and becomes the operator's problem. A live implementation you can examine is the buildingSMART Data Dictionary, a free collection of interconnected dictionaries whose publisher says it implements concepts from ISO 12006-3, which supplies the object oriented model dictionaries rest on, together with ISO 23386 and ISO 23387. In the UK, the National Foreword to BS EN ISO 23386 names PAS 14191 of 2020 as the UK localisation, adding process requirements for managing dictionaries and networks of dictionaries. PAS 14191 is current, and I describe it only as that foreword does, so nothing here rests on its own text.
Back at the campus, the curtain walling specification asks for thermal performance. That is a phrase, not a property, and ten suppliers will answer it ten ways. A property has a definition, a physical quantity and a unit. The requirement then says where the definition lives, who may change it, and, where the supply chain is international, where it applies.
The fourth step, then, comes down to one test. A property is fit to require only when it is defined, held in a governed place, protected against silent change and fixed to a version.
The fifth step assembles properties into templates under ISO 23387, in its second edition of 2025, whose title changed at that edition to Data templates for objects used in the life cycle of assets. There are four concepts. The object type is the kind of thing described, such as an air handling unit or a door set, ideally defined from a standard. The data template is the whole of one information delivery, made for one context or one stated purpose, and named for its scope, so a product data template or a system data template. The group of properties is optional and holds a subset of the template's properties. And the property is the thing asked for, defined under ISO 23386.
The relationship rules come first in any appraisal. An object type must be related to at least one data template, because it needs a template to have properties related to it, so an object type never carries properties directly. One object type may belong to several templates. A template may be composed of other templates, as a wall is of its layers. And a group of properties can neither contain a template nor be assigned to an object type. Groups live inside templates, and only there.
The campus shows why the template sits between the object type and its properties. The air handling unit at tender needs whatever lets the council compare bids. The same unit at handover needs whatever lets the operator maintain it. If the properties hung off the object type there would be one set, the union of every purpose, which is how organisations end up asking for two hundred properties nobody uses. With the template in between, one object type carries as many purpose-specific views as it needs. That gives the appraisal test for any template, which is what its purpose is, and whether it is complete for that purpose and nothing more. A template cannot be complete in the abstract. The other checks follow from that one, whether the object type is defined, whether each property is a definition or merely a column heading, where the definitions come from, and at which exchange the template is answered.
The defect you will meet most often is one template serving two purposes. Someone builds it for tender comparison, and someone else adds maintenance data rather than building a second. Each set is then trimmed to keep the whole manageable, so the template is incomplete for both. The symptom is a supplier asking which of these you need at tender. The cure is already in the structure, because one object type belonging to several templates is the designed behaviour.
Then the scope limit, the most useful sentence in ISO 23387. Its scope clause says that supplying the content of any data template is outside what the document covers. It provides a machine interpretable concept of templates, a method for creating and maintaining them in a dictionary, guidance on linking them to classification systems, and a schema. It does not tell you which properties to ask for, deliberately, because content depends on the object, the market, the regime and the purpose.
So who does supply it? There are five candidates, each legitimate and each with a cost. A published data dictionary gives governed, mappable definitions, at the cost of the governance queue when something is missing. A product or test standard gives a characteristic with the test conditions that produce it, which is the pairing a property needs, but its coverage is uneven. A trade body template gives a ready set, with governance that varies. A manufacturer gives everything it holds in its own structure, which will not compare with the next bidder's. And your own project register gives exactly what you need, maps to nothing and passes to the operator for the life of the asset. The failure is not choosing the wrong one. It is choosing none.
The campus shows three answers. A standard product with a mature dictionary entry needs only the dictionary property and its version. The curtain walling is a performance specified system, so its characteristics and their measurement conditions come from product and test standards, and naming them means every bidder answers the same question. And a bespoke item, say specialist teaching equipment for the laboratory, is defined in a project register, with a named owner for the definitions and an explicit handover of the register to the operator. That is not a failure. It is a decision with a stated cost.
So the fifth step resolves. A template is a view for one purpose, its standard gives structure and leaves content to someone else, and the requirement has to name who.
The sixth step turns all of this into requirements. A requirement is an instruction somebody has to price, somebody has to answer and somebody has to test. Take the first half of the council's sentence, that all information shall be classified to Uniclass. It names no release, so a supplier coding in January and a checker checking in October may use different tables. It names no tables, so task teams guess differently. It sets no level. It does not say where codes are held, so some end up in file names. It says nothing about the next release, or about who checks. And it is worse than a blank, because it looks like a requirement, so nobody asks the questions.
A classification requirement has to say six things. The system and its release, with the date. The tables in scope and what each is for. The level required, for each purpose. Where the classification is held. What happens at the next release, where re-baselining each time and holding the appointed release are both defensible, and silence is not. And how a checker will test it, because a supplier who can see the test prices the work, while one who cannot prices the risk.
The level is where requirements most often overreach. Coding to object level everywhere is slow, expensive and mostly unused, so it is done badly under pressure. The level follows the purpose. Finding and filtering needs group or sub-group. A cost plan needs section level, with the estimator's breakdown structure deciding where to stop. Performance at system level needs section or object, so a system can be told from its neighbours. And an asset register for an operator needs object level, because the operator maintains specific things. So a good requirement sets a level per purpose, recorded in an object schedule.
The parts then go into two documents. The project's information standard, established under clause five point one point four of ISO 19650-2, carries what is the same for every appointment, the system and release, the tables, where classification is held, the release policy and the check. The exchange information requirements, established under clause five point two point one, carry what differs by appointment, which objects are classified, at what level, for what purpose and by which exchange. Put everything in the information standard and no appointment knows what it must do. Put everything in the exchange information requirements and the same paragraphs are copied into every appointment, where they drift apart at the first amendment. The episode The Delivery Phase in ISO 19650 Part 2 places both clauses in the wider sequence.
The clause for the information standard can be short. Classification shall use the system named in this standard, at the release identified in its version record, applying the tables listed, held as a container attribute and not carried in the identifier, with code and description in separate properties. The release sits in one version record, so a new release changes one entry. The matching clause in the exchange information requirements points to the object schedule, which carries for each object the table, the minimum level, the purpose and the exchange. Minimum, because classifying deeper than asked is not a failure. This is where the curtain walling is settled. Its row names the Systems table at section level at least, so the architect and the facade contractor now code the same assembly the same way, and each may still add codes from the elements and products tables, one from each. The clause also requires any classification that does not fit to be recorded and submitted as an exception. Awkward objects are normal, and a temporary site hoarding on the campus is a fair example, a construction aid that never forms part of the finished work. Without an exceptions route a supplier either forces a bad code in silence or stops to ask and loses days.
Then the check. Five of the six checks are mechanical, and software can run them over an exported schedule. Presence, that every object in scope carries a classification. Table, that the code comes from a named table. Level, that it reaches the minimum. Release, that the recorded release matches the project's. And pairing, that the description travels with the code. The sixth, whether it is the right code for this object, needs a person who knows the object and the tables. Say that the five run on every exchange, and that the sixth is sampled, and by whom.
The structured data requirement is harder, because there is no published content to point at. It has to say five things. The source of the definitions and its version, chosen per property or set from the five candidates. The template, with its purpose and its exchange point, because a template with no moment attached never falls due. The responsible party for each property, because some values are the designer's, some the manufacturer's and some the installer's, and a template that does not say produces gaps at exactly those boundaries. The measurement conditions, wherever a value depends on them. And which checks are machine testable, because presence, data type and unit can be tested by software, and whether the value is right cannot.
The drafted clause reads like this. For each object type in the data schedule, the supplier shall provide the properties listed against it, using the definitions from the source stated, at the version stated, by the information exchange stated, and shall record the conditions assumed wherever a property's value depends on them. That last phrase is the one the council needed. Here is the air handling unit row of its data schedule. The object type, with where it is defined. The property, named as its source names it. The definition source, a product standard, because that defines both the characteristic and how it is measured. A dated version. The data type and unit. The operating point, recorded as a connected property, which is the provision ISO 23386 makes for properties whose values bear on one another. The responsible party, the mechanical appointed party at tender, not the installer. The exchange point, the tender return, and handover again if what is installed differs. And what is machine checkable, presence, type and unit, but not the correctness of the figure. With that row in place, the three bidders return three figures at stated conditions, and the council can compare them.
The three jobs from the first step now sit in three clauses. Classification says what each object is. The level of information need says how much is required, for what purpose, at which milestone. Structured data says what shape the answer arrives in. The commonest drafting error is one clause doing two jobs, and the council's sentence, classification in its first half and sufficient information in its second, is exactly that. If a clause does two jobs, split it.
Beyond this point the work becomes automation. The buildingSMART Information Delivery Specification, version one point zero, was announced as a final buildingSMART standard on the fourth of June 2024. It is not an ISO standard, and it is how a requirement becomes something software checks automatically. Everything drafted in this step can be written, answered and checked without it, so do not let automation become a precondition for good specification. One look forward, labelled as such. Draft revisions of ISO 19650 Parts 1 and 2 were open for public comment from March to May 2026, and a draft revision of Part 3 followed, open for comment until July 2026. None of them is in force, and no publication date has been announced. The published editions, Parts 1 and 2 of 2018 and Part 4 of 2022, remain the ones to cite. When a revision is published, the clause numbers in your requirements will need re-pointing, which is a task for periodic review, not a reason to change anything now.
So the sixth step resolves. A requirement is complete when it can be priced, answered and tested, and that comes from saying the specific things, placing each in the right document, and being honest about which checks a machine can run.
The campus can now be given its answer. The question was what it takes for information to be machine readable rather than merely digital. The answer is three things, each specified on its own terms. A shared name, from a classification system built on ISO 12006-2, which in the UK means Uniclass, named by release, by table and by level for each purpose, and held in metadata rather than in the file name. A stated quantity, set by the level of information need under ISO 7817-1. And a defined structure, a data template under ISO 23387 whose properties are defined under ISO 23386, sourced from a named place at a named version, owned by a named party, answered at a named exchange and measured under recorded conditions. Two of those standards deliberately refuse to supply their own content, so the requirement has to say who does. For the council, that means splitting its one sentence into separate clauses. The curtain walling gets one code from the Systems table, at a stated level, so both parties describe the same assembly. The air handling unit gets a data schedule row with a defined property and a recorded operating point, so the three figures can be compared and the tender need not go back.
Three questions are worth carrying into any project. When you meet a requirement that names a classification system and stops, which of the three jobs has it done, and which has it left open? When you specify a property, where does its definition live, who may change it, and which version did you write against? And when you draft any clause, how will a checker test it, and which of those checks can software run and which need a person? A supplier who can see the answer to that last question can price the work.
For reading, start with ISO 12006-2, especially clauses three and four and Annex A, then ISO 23386 and ISO 23387, and the UK National Annexes to ISO 19650-2 and ISO 19650-4. PD 19650-0, withdrawn guidance now read as history, records the expectation that classification is held as metadata. Keep the current Uniclass release beside them. Among the other episodes, Level of Information Need in ISO 7817-1 covers the second of the three jobs, The Common Data Environment: Process Before Platform covers naming and container attributes, and Information Exchange in ISO 19650 Part 4 covers the decisions at which information moves between parties. The next episode, Information Delivery Manuals in ISO 29481, is about how you specify an information exchange precisely enough that software can check it.
Find a requirement on a project you know, in practice or in research, that names a classification system and stops, and list the two jobs it has left for someone else. I am Dr Sepehr Abrishami, and that list is where Reimagining AEC would have any specification begin.