Liquid cooling of AI data centers

Sep 15, 202616 minAudioEpisode 73
ShareXLinkedInFacebookWhatsAppEmail

As AI data centers push server power to unprecedented levels - reaching 600 kilowatts by 2027 and potentially megawatt-scale by the 2030s - the challenge of keeping these systems cool has never been more critical. In this episode of "We Power AI" on Podcast4Engineers, host Kelsey Markl sits down with Muzaffer Albayrak, Application Marketing Manager at Infineon, to explore the evolving world of data center cooling technologies. Together, they break down the shift from traditional air cooling to advanced liquid cooling methods, including direct-to-chip cooling, rear door heat exchangers, and immersion cooling, while examining the crucial role of Power Usage Efficiency (PUE) in measuring data center performance. The conversation dives into the semiconductor solutions - from silicon to wide-bandgap materials like silicon carbide and GaN - that power the fans, pumps, and inverters keeping these massive systems from overheating. Whether you're curious about cooling distribution units, centralized cooling architectures, or the future of AI infrastructure, this episode offers essential insights into one of the most pressing engineering challenges in the AI revolution.

Audio and video play straight from the show's own hosting. PodSubs stores and serves no media.

Transcript

From the show. Tap a time to play from there.

(intense music)

-What is happening in the server room? They're increasing the heat. Okay. Because by increasing all the server capabilities, one server, it will reach around the 600 kilowatt level in 2027. Mm-hmm. And they have the outlook to reach the megawatt level, 2030s. It's very challenging. Yeah? Sounds like it could get pretty hot. Yeah, it will be very. On the one hand, it's fascinating to reach such kind of the capability on the server rooms.

On the other hand, the question, how do you cool? (intense music) (intense music continues)

-This is the "Podcast4Engineers", the podcast you just have to listen to if you're interested in what's going on in the semiconductor market. My name is Kelsey Markl, and I'm your host on another episode from our "We Power AI" series. Today, we're diving into cooling, cooling our AI data centers. And I'm joined by my colleague, Muzaffer Albayrak, who is an Application Marketing Manager at Infineon, specializing in industrial drives applications. He comes with more than 15 years of experience in semiconductors, and I'm super excited to have you here.

-Thank you for having me. Okay. And maybe our listeners with a keen ear have noticed you are responsible for industrial drives applications, but we're talking Right.

Kelseyabout cooling. What do industrial drives have to do with cooling?

-The cooling will be realized through this two applications, fan and pump, and that these both applications counted inside the Infineon below the industrial drive. Therefore, I'm sticking in front of you. Okay, good. So, now that we've got that out of the way, why is cooling so important in AI data centers? It's very easy. The energies which incoming, electrical energies, converted in the server rack in the terminal energies.

And terminal energies need to be efficient way remove out of the server. Therefore, the cooling is mandatory segment for the data centers.

-So, I assume then with what you're saying, more power leads to more need for cooling off that thermal dissipation. Are data center operators investing a lot in cooling? It is roughly, there are some level based on the technology, selected technology for the coolings, but there's roughly 10 to 20 percentage around this, the investment needed over all this CapEx cost for the cooling structures. Okay. Then, how do we measure that?

How do we know if we're creating efficiently cooled data centers?

-There are some parameter which call PUE, power usage efficiency. Mm-hmm. And these value reflecting how efficient data center is structured. And especially for the AI data center target is to reach below 1.1. The PUE value is calculated by in either relation, in one relations, in incoming energy related to the IT server energies

which has been consumed during the processing in the IT service.

-Okay. So, basically like everything you need to keep a data center up and running, including like, does that include lighting and like everything? It's correct. This is the PUE we use. Let's take one example. For example, 11 megawatts energy is incoming. Mm-hmm. And 10 megawatt is using or consuming by server racks. And so, one megawatt, which is required for the, all the other auxiliary equipment, lighting, cooling, all the other stuff.

-Okay. So, it seems like cooling does play a big role in the overall efficiency of data centers. How can we cool? What options are there? Typically, they are two way, air cooling and liquid cooling. Until today, the air cooling was a dominated technology on the market for the data centers. But by increasing of the energy demand of the AI data center required more cooling capabilities.

And the air cooling, which CRAC and CRAH is a computer room conditioning,

-and also Mm-hmm. the in CRAH is a computer room air handling. It's a two-way of the air cooling is going to be or already on the limit. So, market requires next solution. Therefore, the liquid cooling getting more and more share on the market, especially for the AI data centers. Okay. Are there different types of liquid cooling? You mentioned two for air. What different types of liquid cooling are there?

-There are three different kind of solutions existing by the liquid cooling. Rear door heat exchanges. This is a hybrid cooling, which the air and liquid cooling is some in combination working together. Direct-to-chip cooling is, so cooling plate on the GPU and CPUs to cool the water circulations through the cooling plate. And immersion coolings looks like the, some water bed

that the older data server putting inside the waters to cool the water,

-which the servers included. Okay. So, the server racks are then like really just standing In water. in a pool of water. The pool of the waters. Okay. There is possible. Okay. Okay. It doesn't necessarily seem the most practical though. What are businesses actually choosing to go with? Yeah. And the immersion coolings is there are some complexity, of course, yeah. It looks, sounds very interesting, but they have different definities of market share on the market. But direct-to-chip cooling or rear door heat exchanger

is getting more and more share on the market.

KelseyMm-hmm.

-Immersion cooling will stay definitely on the market, but they have some commercial and technical complexity at the moment. Okay. You mentioned direct-to-chip cooling. Can we take a little deep dive onto that one for a second? And can you tell me what exactly that structure looks like in a data center if you go that way? Yeah, of course. Yeah, of course. Let's do this in that way, I would like explain which kind of the sub-segment that is integrated in the AI data centers. Mm-hmm.

-If you talk about the cooling structure, they are three different segments. Cooling tower, chiller. Chiller is not all the time demanded. Yeah, based on the location where the AI data center is located. Okay. If you are in Alaska, maybe you don't need it because there's ambient temperatures or cold that's cooling tower will be up. Plenty of snow. Yeah. (Kelsey chuckles) There you go. Based on this structure of the place, the chiller could be some variable component.

And also, CDU, which cooling distribution unit, inside the server room. And exactly these three cooling structure, which we just now counted down, rear door exchanger, immersion cooling, and direct-to-chip cooling, happening inside the server room.

-Okay. So, you said most of the magic is happening in the CDU, in the server room. That's right. Yeah. Right. Okay. What's actually happening in the server room? What is happening in the server room? Yeah, it's a good, good questions. What's happening in the server room? There's happening in, say, increasing the heat. Okay. Because by increasing all the server capabilities, which one of the big player already mentioned that the one server

will reach around the 600-kilowatt level

-in 2027. Mm-hmm. And they have the outlook to reach the megawatt level, 2030s. It's very challenging. Yeah? Sounds like it could get pretty hot. Yeah, it will be very. I would say this is, on the one hand, is a fascinating to reach such kind of the capability on the server rooms. On the other hand, the question, how do you cool? Mm-hmm. Yeah, this is exactly these some play hand in hand, yeah.

Without having this efficient cooling structure, it doesn't help to reach the such kind of the server capabilities.

-Mm-hmm. Are there any kind of innovative solutions or innovative, I don't know, ideas of how we can cope with that increased power? Just now we mentioned, so direct-to-chip cooling is currently is the, going to be leading way. On the other hand, the other liquid coolings definitely has a very important share. I don't want to then oversee that. There's still they are also interesting giga value

or the market share increasing. The question is how we can cool such kind of the higher demanded energies, terminal energies out of the server rack. And there are several kind of (indistinct) For example, we are talking about the CDU, cooling distribution unit. Cooling distribution unit, they are not only done one way, which is correct. Yeah? There's depend on this design of this AI data center.

Can be a cooling distribution located inside the racks, yeah, with some slide rails. Yeah. They have some pump and water channel, which is allowed to cool the server heat.

KelseyMm-hmm.

-Or there are some sidecar, which cooling distribution units integrated in the sidecar, and responsible for the rack, server rack, which we are calling this in rack cooling. Mm-hmm. And also in the row cooling, which is going to be more in the future perspectives on centralized solution Okay. within high demanded cooling distribution units is responsible for the server racks. Okay.

Since we're a semiconductor company, can you talk a little bit about what factors go into the decision-making process when choosing the right semiconductors

-to support such a system? Mm-hmm. Yeah, we already talk about this power usage efficiency value on the beginning. Target is to keep as small as possible. The IT server racks' capability is clear, 600 or 1 megawatt, or 300, whatever it is. So, additionally, power which we are requiring for lighting, cooling, and so on. So, each component need to be designed very efficient way.

One of them, for example, while I'm sitting here for that, the cooling. Cooling, we learned on the beginning can be happened through the fan and pump. Each end system requires inverters.

-Mm-hmm. Each inverters have some power component inside. And by its selections of the right power semiconductor components allowed to solve this inverter solutions, which is responsible for the cooling in efficient way. Mm-hmm. Are we talking about silicon devices then? This is what I would like also to mention on that. If we talk about the power semiconductor and we talk about the efficiency,

it's a clear answer wide-bandgap is that getting in their mind, definitely. Based, I don't want to then say it's, everything's needed to be wide-bandgaps, depend on the solutions, depend on the requirement on this customer level. This is also the Infineon advantages that the right and wide product portfolio is can focus from silicon IGBT, silicon carbon, most of it, GaN HEMT. We have the really wide product portfolio

which can be addressed for the each sub-segment.

-Okay. And you mentioned before that a centralized solution might offer the most opportunities in the future. What do you think will, we can expect from AI data centers in the next five years? Also the AI data center has been affected from this general trend of the power semiconductor or power, or electrifications. For example, DC grid topics.

Currently, it's not the topics for the cooling today, but it's a very similar. It's like as the conversations from AC to DC centralized somewhere in the futures. Also, the cooling structure will be centralized,

-Mm-hmm. for example, the row cooling, which we are mentioning about that. The one CDU will be responsible for the several racks. These way of solutions, we are expecting this will be then dominating on this AI data center solution. But today, there are several effective solution in the rack and the row cooling. Mm-hmm. Okay. So, I think from what I get from this conversation,

the evolution of data centers are going to be increasing in power and power.

-Correct. But with that, we can't forget about cooling, that it goes hand in hand. Exactly what we are mentioning about this. The old electrification, incoming electrics, is converted in the terminal energies. And terminal energy Mm-hmm. can damage also then components, Mm-hmm. which are very expensive on the server rack, for example. And therefore, this needed to be co-opt by decreasing of the temperature of the each server racks.

And this is the responsibility of the cooling structure in AI data centers.

-Well, I'm very excited about cooling in AI data centers and excited to see where the journey goes. Thank you very much. Thanks so much. And to our listeners out there, be sure to stay tuned for the rest of our episodes in this "We Power AI" series on the "Podcast4Engineers". (intense music)

Open the transcript file

Hosts and Guests

Nobody is credited on this episode yet.

Credit the people on this episode

Be the first to rate this episode

More episodes

All episodes
  1. Electrochemical Impedance Spectroscopy (EIS) for A-BMS

    Nov 17, 202610 minAudio

    In this episode of the Podcast4Engineers, host Kelsey sits down with Christian Walther to explore electrochemical impedance spectroscopy (EIS), one of the most promising trends in automotive battery management systems....

    Credit the people on this episode

  2. GaN, Decoded: What does “fast switching” really mean?

    Nov 9, 202618 minAudio

    What does “fast switching” really mean when we talk about GaN? In the first episode of GaN Decoded, host Peter Balint sits down with Infineon lead principal engineer Edward Jones to explore the difference between...

    Credit the people on this episode

  3. Trends in Battery Management Systems (BMS)

    Oct 30, 202623 minAudio

    In this episode of the Podcast for Engineers, host Kelsey speaks with Infineon system architect Wolfgang Novak about the critical role of Battery Management Systems (BMS) in electric vehicles. They explore how advanced...

    Credit the people on this episode

  4. Powering tomorrow: The global infrastructure behind AI

    Oct 6, 202620 minAudio

    AI may run on data, but its future depends just as much on power. In the eighth and final episode of the "We Power AI" series on Podcast4Engineers, host Kelsey Markl welcomes Andreas Weisl, CSO of the Industrial and...

    Credit the people on this episode

  5. Protecting AI power with solid-state circuit breakers

    Aug 25, 202624 minAudio

    AI data centers are driving power demands to levels that are forcing engineers to rethink how electricity is distributed and protected. In this episode of Podcast4Engineers, Peter Balint talks with Infineon...

    Credit the people on this episode